7.5 Parameter table
Parameter
Display / factory setting
Funktion
Mode
4.00
4.01
Mode
INFO
Information
Δ
p
0 Pa
(0.000 in.wg)
0 Pa
(0.000 in.wg)
Display actual value for differential pressure
Setpoint 1
-
500 Pa
(2.0 in.wg)
Display active Setpoint
Uout
0.0 V
9.9 V
Magnitude of the output voltage 0...10 V
EDR
2.10
2.10
Software version
SETTING
4.01
+
5.01
Setting
Setpoint 1
-
500 Pa
(2.0 in.wg)
Setpoint 1
1
Setpoint 2
-
500 Pa
(2.0 in.wg)
Setpoint 2
1
(active if voltage at terminals 1, 2)
Pband
-
500 Pa
(2.0 in.wg)
Pband
1, 2
Min. Uout
-
0.0 V
Min. output voltage: 0.0...10.0 V (priority
over
“
Max. Uout
”
)
Max. Uout
-
10.0 V
Max. output voltage: 10.0...0.0 V
BASE SETUP
Base setup
Mode
4.00
4.01
Mode
Units
metric: Pa, m
3
/h, K-Factor
inch: in.wg, cfm, K-Factor US
SI units or Imperial units (US)
Measuring
Range
1: 0...1000 Pa
(0...4.0 in.wg)
2: 0...500 Pa
(0...2.0 in.wg)
3: 0...300 Pa
(0...1.2 in.wg)
4: 0...200 Pa
(0...0.8 in.wg)
Adjustable measuring range
Autozero
OFF => ON
Automatic
“
0
”
offset
Offset
0 Pa
(0.000 in.wg)
Sensor offset (automatically when
“
Auto-
zero
”
)
Setting range: +/ - 1000 Pa
(+/- 4.000
in.wg)
1
Setting range:
4.01
: 0...100 % sensor measuring range
2
small value = quick regulation, great value = slow regulation (high stability)
-
Parameter for selected mode not available
(xxx)
Values for Imperial units (US)
Installation and Operating Speci
fi
cation
EDR
Programming
L-BAL-E292-GB 1841 Index 001
Part.-No.
10/15