CONTROL SETTINGS, TROUBLESHOOTING AND WARRANTY

3

1.5. DIP Switch Settings

BIT SWITCH #

FUNCTION DESCRIPTION

SETTING WHEN LEFT (OFF)

SETTING WHEN RIGHT (ON)

1

Tank high limit shutoff - automatically turns off Relay 1 when the 

storage sensor reads switch 4 setting of 160 or 180°F

No high limit function

High limit ON

2

Freeze recirculation - automatically turns on the 

Relay 1 when the collector sensor reads 42°F or below

No freeze recirculation

Freeze recirc. ON

3

Useful collector temperature - automatically turns off Relay 1 when 

the collector sensor reads 80°F or below, even with a satisfactory 

differential (Freeze recirc. can override this function)

No useful collector 

temperature monitor

Useful collector 

temperature monitor ON

4

Tank high limit shutoff  temperature - choose which temperature to 

turn the tank off at 160 or 180°F

180°F

160°F

&

 6

Differential setting - sets which temperature differential will turn on 

and off Relay 1 (Heliodyne recommends both switches OFF for glycol 

systems, and both switches ON for open loop or direct systems)

18°F ON

5°F OFF

9°F ON

4°F OFF

1.7. Troubleshooting

If a controller stops working, most often it is due to a sensor or wire failure.  Detach 
the sensor plug and measure the sensor resistance with a multi-meter and compare 
with the chart below for appropriate reading values.  Because they are inversely 
related to temperature, a short reads as a very hot temperature, and an open reads 
as a very cold temperature.

1.7.0. On/Off Test

This test verifies the controller will turn on and off.  Switch the controller ‘ON,’ power 
is applied to the Normally Open relay point, terminal 2.  This may be verified with an 
DC voltmeter across terminals 2 and 3.  If a pump is connected, it should turn on.

With the switch in the ‘OFF’ position, power is applied to the normally closed relay 
point, terminal 1.  This may be verified with a voltmeter across terminals 1 and 3.  

When the switch is ‘ON’, the pump LED indicator should be on.  If not, consult the 
manufacturer.

1.7.1. Basic Function Test

This test verifies the BIT settings are working correctly.  The BIT switches (figure 2) 
for a particular function must be on to test for that function.

Place BIT switches 1 on and 2 off (remaining switches can be either on or off.)  
Switch controller to ‘AUTO.’  Allow the sensors to come to thermal equilibrium 
(about one half hour.)  Short the screws in positions (see figure 4) 1 and 2 and the 
controller should turn on.  Next, place the collector sensor in a cup of hot water; 
this should turn the controller on.  With the storage sensor screws shorted (positions 
3 and 4), the controller should turn off.  If the controller does not respond to these 
tests, consult the manufacturer.

2.0. Warranty

HELIODYNE shall provide a one-year warranty for defects in compliance with the purchased goods 
delivered after 3/1/2008 as follows: Objects are warranted at HELIODYNE’s discretion by repair of 
the object of purchase or replacement of defective parts, exchange or reduction of price. The right of 
the contractor to convert objects is ceded by common consent. Replaced parts become the property 
of HELIODYNE. Wages and costs spent on installation and disassembly must be covered by the 
client. This provision similarly applies to all warranty agreements. It is at HELIODYNE’s discretion 
to replace defective goods with similar, faultless goods. In this case, any rights to cancel the 
agreement cease. The client expressly waives the right for it and its legal successors to assert claims 
for damages or loss of profit (including without limitation special, indirect, loss of use, contingent, 
or consequential damages) due to defects or nonconformity in the purchased good. The warranty 
set forth above constitutes the sole and exclusive remedy against HELIODYNE for the furnishing 
of any nonconforming or defective goods. THE ABOVE WARRANTY IS EXPRESSLY IN LIEU OF 
ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION ANY 
WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR USE OR PURPOSE. 
Damage resulting from improper or negligent treatment is excluded from the warranty. Claims on 
warranty will only be admitted and considered if they are announced in writing immediately after the 
defect was first noticed. Oral communication or communication by telephone are not sufficient.

For collectors (except broken glass and collector accessories e.g. sheet metal edgings) and storage 
tanks (except attached components), HELIODYNE replaces materials that demonstrably fail to 
meet one of the requirements of the ASHRAE standard 93-77 at no charge, works within five years 
for storage tanks and ten years for collectors, of the date of the invoice issued by the company 
HELIODYNE. HELIODYNE is not liable, however, for damage caused by mechanical stress and/
or changes caused by weather-related influences. Minor variations in color and/or damage to the 
surface that have no effect on the function of the collector are also not covered in the warranty. 
The warranty excludes damage caused by force majeure and malfunction that are due to improper 
assembly, and/or product installation. HELIODYNE is not liable for possible costs resulting from 
defects. In order for HELIODYNE to accept liability:

– Installation must have been carried out by a licensed specialized company (heating contractor or 
plumber) following the version of installation instructions in force;

– HELIODYNE or its representative was given the opportunity to check complaints on site 
immediately after any defect occurred;

– Confirmation exists that the system was commissioned properly and that the system was checked 
and maintenance was performed annually by a specialized company licensed for this purpose. The 
warranty agreed by HELIODYNE is only valid for their clients.

S O L A R   H O T   W A T E R 

   

Ω

 vs 

°F

0

50

100

150

200

250

0

5,000

10,000

15,000

20,000

25,000

30,000

35,000

SENSOR TEMPERA

TURE °F

MEASURED RESISTANCE 

Ω

Отзывы: