9 Electrical Installation
2 stubs – DIP 2
DIP switch 2 is only evaluated if DIP switch 3 is set to “ON” at the same time.
The connection of an external manual button is not considered to be a stub.
OFF
Only one stub with smoke switches is connected to the FSZ Pro. The termination module
AM 142 resp. a magnet must be installed in the last smoke switch (see Fig. 7).
ON
Two stubs with smoke switches are connected to the FSZ Pro. The termination module
AM 142 must be installed in the last smoke switch of each of the two stubs (see Fig. 9).
Line surveillance – DIP 3
If the FSZ Pro is used according to DIN EN 14637, this DIP switch must be set to “ON”.
If the FSZ Pro is used according to DIBt, the system can be used with and without line surveillance.
Irrespective of the type of use, the respective specifications in chapter 8 must be observed!
OFF
The FSZ Pro is operated without line surveillance. A wire jumper is set across contacts 1
and 5 in the last smoke switch (see chapter 6.1 section ).
ON
The FSZ Pro is operated with line surveillance. The termination module AM 142 resp. a
magnet must be installed in the last smoke switch of a stub and at the external manual
release button.
With/without horn – DIP 4
OFF
Horn OFF
ON
Horn ON - The internal piezo signals in case of alarm/fault. It is buffered for 60 seconds
in the event of a power failure.