8 FSZ Pro – applications
8 FSZ Pro – applications
The FSZ Pro allows setting up a hold-open system in three different configurations:
1. According to DIBt without line surveillance
A +24 V wire jumper must be fitted to connector 5 in the last detector to be connected (see Fig. 5).
If no manual button (HAT) is connected, a wire bridge must be implemented to the HAT connection
terminal in the FSZ Pro. If nothing is connected to the external alarm input, a jumper must also be
set there.
The connection lines of the smoke switches and manual buttons must be completely laid in a cable
conduit or cable channel. If this is not possible, the lines must be laid separately.
No more than 20 smoke switches, electromagnetic door retainers (THM) and other consumer
devices may be connected. The total current must not exceed 900 mA. The DIP switches 2 and 3
must be set to OFF.
2. According to DIBt with line surveillance
The line surveillance function must be activated via DIP switch 3 (EN 14637). One termination
module AM 142 or a magnet for ORS 142 must each be connected in the last detector to be
connected and in the manual button (see Fig. 7 resp. Fig. 8). If no manual button is connected the
termination module AM 142 must be connected to the HAT connection terminal in the FSZ Pro. If
nothing is connected to the external alarm input, a jumper must also be set there.
No more than 12 smoke switches, electromagnetic door retainers (THM) and other consumer
devices must be connected to one stub. The total current must not exceed 900 mA. The DIP switch 3
must be set to ON. Depending on the connection DIP switch 2 must set to ON or OFF.
3. According to DIN EN 14637
The line surveillance function must be activated via DIP switch 3 (EN 14637). One termination
module AM 142 or a magnet for ORS 142 must each be connected in the last detector and in the
manual button (see Fig. 7 resp. Fig. 8). If no manual button is connected the termination module
AM 142 must be connected to the HAT connection terminal in the FSZ Pro. If nothing is connected
to the external alarm input, a jumper must also be set there.