Control unit for hold-open systems

FSZ Basis

Edition 17.04.2018

7002878

 

Instruction manual

Содержание FSZ Basis

Страница 1: ...www hekatron de www hekatron de Control unit for hold open systems FSZ Basis Edition 17 04 2018 7002878 Instruction manual...

Страница 2: ...2...

Страница 3: ...ation instructions 12 9 2 Control unit FSZ Basis for hold open systems 14 9 3 Termination module AM 142 16 9 4 FSZ Basis operation 17 9 5 Hold open system according to DIN EN 14637 19 9 6 Connection c...

Страница 4: ...4 11 Maintenance 33 11 1 Obligatory documentation requirement 33 12 Annex 34 12 1 Order data 34 12 2 Drilling template 34 12 3 Technical support and application support 34...

Страница 5: ...es to the equipment are not permitted The equipment must be used only for its intended purpose in an undamaged and perfect condition No other spare parts than those available from the manufacturer mus...

Страница 6: ...or and Tor schlie en Close gate 1 x termination module AM 142 only for version 31 5400002 01 xx and 31 5400002 05 xx 3 Warranty In case of non compliance with the information contained in this Instruc...

Страница 7: ...ording to DIN EN 14637 Distinction between fault causes via the LED flash code on the keypad Alarm storage can be activated via DIP switch Line surveillance can be activated via DIP switch Two smoke s...

Страница 8: ...t 24 V DC 1 alternating contact potential free max 250 V AC max 5 A AC max 30 V DC max 3 A DC max 5 A DC Operating ambient temperature 10 C to 50 C Storage temperature 10 C to 60 C Ambient conditions...

Страница 9: ...ed components of the hold open system The current required for the hold open system consists of the sum total of all currents of the components connected Example calculation The hold open system compr...

Страница 10: ...and dowels The installation position can be selected as desired The FSZ accessories kit which must be ordered separately includes two mounting adapters for installation of the FSZ Basis in a switch ca...

Страница 11: ...switch 1 EN 14637 One termination mod ule AM 142 or a magnet for ORS 142 must each be connected in the last detector to be connected and in the manual button see Fig 7 resp Fig 8 If no manual button i...

Страница 12: ...before assembly work is started 9 1 Installation instructions Installation and electrical connections may only be executed by qualified electricians or by persons appropriately instructed with regard...

Страница 13: ...and to the line length Power supply connection The cross section of the power supply cord must not exceed 2 5 mm Hold open system wiring Recommended line type without smoke switch in combination with...

Страница 14: ...ction terminals Mains connection 230 V AC Potential free alternating contact Connection of smoke switch Terminal points Connection of hold open system Connection of ext manual release and reset button...

Страница 15: ...e COM1 Common potential free contact 3 Relay line voltage NO In operation connected with contact 2 24 V Output voltage 24 V DC GND Output voltage 0 V DC ORS Feedback from ORS alarm loop K Connection p...

Страница 16: ...tion terminals Fig 3 Termination module AM 142 9 3 2 AM 142 connection Coming from the power supply unit or the second to last smoke switch Going to the last smoke switch 24V yellow feedback alarm loo...

Страница 17: ...this DIP switch must be set to ON If the FSZ Basis is used according to DIBt the system can be used with and without line surveillance OFF The FSZ Basis is operated without line surveillance A wire ju...

Страница 18: ...not exceed 9 If no manual button is connected the termination module AM 142 must be connected to the HAT connection terminal in the FSZ Basis 1 A magnet can only be used in combination with an ORS 14...

Страница 19: ...ns with a low inclination to care and diligence i e cases where misuse is probable to a certain degree Digit 2 Stress test of the hold open device Class 5 50 000 test cycles Hekatron s electromagnetic...

Страница 20: ...ions according to DIBt and DIN EN 14637 9 6 1 Connection without line surveillance DIP 1 OFF The system is operated with a smoke switch stub an external manual release button and an external reset but...

Страница 21: ...without line surveillance DIP 1 OFF The system is operated with a smoke switch stub several smoke switches without external manual release button The manual button must be simulated by a jumper Fig 6...

Страница 22: ...th a smoke switch stub and an external manual release button A line surveillance unit with termination module AM 142 is installed according to DIN EN 14637 DIP switch 1 must be set to ON To prevent a...

Страница 23: ...The manual button must be simulated by an AM 142 L N PE NC 1 COM 1 NO 1 24V GND ORS K B THM THM 24 V HAT Reset GND EN 14637 2 Stiche 2 Stubs Al Speicher al storage FSZ Basis OFF ON THM AM 142 RD BK W...

Страница 24: ...are installed according to DIN EN 14637 DIP switches 1 and 2 must be set to ON L N PE NC 1 COM 1 NO 1 24V GND ORS K B THM THM 24 V HAT Reset GND EN 14637 2 Stiche 2 Stubs Al Speicher al storage FSZ B...

Страница 25: ...trical installation 9 6 6 Connection without line surveillance DIP 1 OFF The system is operated with three smoke switches and an external DKT 02 Fig 10 Example connection without line surveillance wit...

Страница 26: ...rical installation 9 6 7 Connection with line surveillance DIP 1 ON and DKT 02 The system is operated with three smoke switches and an external DKT 02 Fig 11 Example connection with line surveillance...

Страница 27: ...uences to indicate the different statuses Every flashing sequence starts with a long pulse 1 5 sec followed by a short pause 0 5 sec Fig 13 If flashing sequences comprise several pulses the long pulse...

Страница 28: ...ton Actuation of the internal manual release button ON OFF Flashes 2 x OFF OFF Alarm External manual release button Actuation of the external manual release button fault of termination module AM 142 O...

Страница 29: ...a ture in FSZ Basis Ambient temperature too high Reduce the ambient temperature ON Flashes 5 x OFF OFF OFF Fault in the loop of the electromagnetic door retainer Short circuit of the con nection line...

Страница 30: ...ral building type approval 2 It must be verified that the labelling of the built in devices corresponds to the labelling specified in the general building type approval 3 The cooperation of all device...

Страница 31: ...erability must be restored immediately and then verified by at least three successive monthly functional tests For the measures to be taken for testing please refer to Section 6 1 of the DIN 14677 sta...

Страница 32: ...proper functioning of the installed hold open system e Check whether the use in the immediate vicinity of the hold open system affects the latter negatively e g occurrence of dust or water vapour f C...

Страница 33: ...s specifications e g fire detectors accumulators and or batteries d Check whether the hold open system is triggered in the event of a power failure or if necessary check whether the hold open system...

Страница 34: ...agnet line surveillance QUP 10 31 4100015 01 xx Servicing and maintenance set IW Set RS 7001949 12 2 Drilling template See following page 12 3 Technical support and application support Hekatron Vertri...

Страница 35: ...asis applications 11 Functional test 32 G General safety information 5 I Installing the FSZ Basis 10 L LED 28 Line length 13 Line surveillance 17 M Maintenance 33 Maintenance instructions 31 Manual re...

Страница 36: ...36...

Страница 37: ...128 128 36 36 8...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...Hekatron Vertriebs GmbH Br hlmatten 9 D 79295 Sulzburg Techn Support 49 0 7634 500 8050 A company of the rs info hekatron de Securitas Group Switzerland www hekatron de...