46202200205
3
Specifications are subject to change without notice.
UNIT INTRODUCTION
This unit is a small packaged gas heat/electric cooling system that
can utilize
the comfort of gas heating packaged along with
efficient electric air conditioning. This unit uses R--410A, the
environmentally balanced refrigerant for cooling.
Starting or Shutting Off Unit
NOTE
: Your combination heating/cooling unit is equipped with
an automatic direct spark ignition and power combustion blower.
To start unit gas heat:
Refer to Fig. 2 for location of unit front access panel. Refer to Fig.
3 for location of gas valve. Refer to Fig. 4 while proceeding with
the following steps.
1. Set the temperature selector on room thermostat to the low-
est temperature setting and set system switch to HEAT.
2. Close the external manual gas shutoff valve.
3. Turn off the electrical supply to the unit.
4. Remove the control access panel with a 5/16--in. nut driver.
(See Fig. 2.)
Compressor
Access
Panel
Filter Access Panel
For Accessory Filter Rack
Blower
Access
Panel
Control
Access
Panel
A09213
Fig. 2 -- Unit Access Panel
5. Move the selector switch on the internal gas valve to the
OFF position and wait 5 minutes.
6. Move the selector switch on the internal gas valve to the ON
position.
7. Replace the control access panel.
8. Turn on the electrical supply to unit.
9. Open the external manual gas shutoff valve.
10. Set the temperature selector on room thermostat slightly
above room temperature to start unit. The induced--draft
combustion air fan will start. Main gas valve will open and
main burners should ignite within 5 seconds. If the burner
does not light within 5 seconds, the ignition module will go
into a Retry Mode after a period of approximately 22
seconds (following the 5--second ignition period). If the
burners do not light within 15 minutes of the initial call for
heat, there is a lockout.
11. Set the temperature selector on room thermostat to desired
setting.
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
1. If the main burners fail to light, or the blower fails to
start, shut down gas heating section and call your dealer for
service.
2. Never attempt to manually light the main burners on unit
with a match, lighter, or any other flame. If the electric
sparking device fails to light the main burners, refer to the
following shutdown procedures, then call your dealer as
soon as possible.
!
WARNING
Burners
Gas Valve
Flue Hood
A14448
Fig. 3 -- Gas Heating/Electric Cooling Unit with Access Panel
Removed
T
o shut off unit gas heat:
FIRE,
EXPLOSION,
ELECTRICAL
SHOCK
HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Do not turn off the electrical power to unit without first
turning off the gas supply.
!
WARNING
NOTE
: If the unit is being shut down because of a malfunction,
call your dealer as soon as possible.
Should overheating occur or the gas supply fail to shut off, shut off
the external manual gas valve to the unit before shutting off the
electrical supply. Do not use this unit if any part has been under
water. Immediately call a qualified service technician to inspect the
unit and to replace any part of the control system and any gas
control which has been under water.
Refer to Fig. 5 while proceeding with the following steps.
1. Set the temperature selector on room thermostat to lowest
temperature setting and set system SWITCH to OFF.
2. Close the external manual shutoff valve.
3. Turn off the electrical power supply to the unit.
4. Remove the control access panel. (See Fig. 2.)
5. Move the selector switch on the internal gas valve to the
OFF position.
6. Replace the control access panel.