background image

1. Insert from outside the room cable into left side  of  the wall

hole, in which the pipe has already existed.

2. Pull out the cable on the front side, and connect the cable

making a loop.

When connecting the cable, con

rm the terminal number of indoor and

outdoor units carefully. If wiring is not correct, proper operation can not

be carried out and will cause defect.

Insert the cable from the back

ƽ

side of  the unit, then pull it out on the front side.

Loosen the screws and insert

ƽ

the cable ends fully into terminal block, then

tighten the screws.

Pull the cable slightly to

ƽ

make sure the cables have been properly inserted and

tightened.

After the cable connection,

ƽ

never fail to fasten the connected cable with the

wiring cover.

When connecting the cable after installing the indoor unit

When connecting the cable before installing the indoor unit

Note:

1. If the supply cord is damaged, it must be replaced by the manufacturer or its

service agent or a similar quali

ed person. The type of connecting wire is

H07RN-F.

2. If the fuse on PC board is broken please change it with the type of 

3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.

5.  A  breaker should be incorporated into

xed wiring. The breaker should be

all-pole switch and the distance between its two contacts should be not less
than 3mm.

T.3.15A/250VAC (Indoor).

To Outdoor unit

Connecting wiring

  4G1.0mm

2

C o d e

in d ic a tio n

T ro u b le d e s c rip tio n

A n a lyze a n d d ia g n o s e

E 1

E 2

E 4

E 7

E 1 4

H e a t-e xc h a n g e
s e n s o r fa ilu re

In d o o r E E P R O M
e rro r

C o m m u n ic a tio n
fa u lt b e tw e e n
in d o o r a n d o u td o o r
u n its

In d o o r fa n m o to r
m a lfu n c tio n

O p e ra tio n h a lt d u e to b re a k in g
o f w ire in s id e th e fa n m o to r;
O p e ra tio n h a lt d u e to b re a k in g
o f th e fa n m o to r le a d w ire s ;
D e te c tio n e rro r d u e to fa u lty
in d o o r u n it P C B ;

In d o o r u n it- o u td o o r u n it s ig n a l
tra n s m is s io n e rro r d u e to w irin g
e rro r;
F a u lty P C B ;

F a u lty E E P R O M d a ta ;
F a u lty E E P R O M ;
F a u lty P C B ;

F a u lty c o n n e c to r c o n n e c tio n ;
F a u lty th e rm is to r;
F a u lty P C B ;

Room temperature 
sensor failure

The power source must be exclusively used for air

ƽ

conditioner.

In the case of installing an air conditioner in a moist place,

ƽ

please install

an ea

For installation in other places, use a circuit breaker as far

ƽ

as possible.

Pipe cutting is carried out with  a  pipe cutter and burs must be removed.

After inserting the

are nut,

aring work is carried out.

Power Source Installation

Cutting and Flaring Work of Piping

Flare tool for R410A

Conventional

are tool

Clutch-type

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

A

0~0.5mm

1.0~1.5mm

1.5~2.0mm

rth leakage breaker.

Lean

Damage of

are

Partial

Too outside

Correct

Incorrect

On Drainage

It becomes

high midway.

The gap with the

ground is too small.

There is the bad
smell from a ditch

It waves.

The end is imm-
ersed in water.

Please install the drain hose so as to be downward slope without fail.

Please don’t do the drainage as shown below.

ƽ

ƽ

Please pour water in the drain pan of the indoor unit, and

ƽ

is carried out surely to outdoor.

In case that the attached drain hose is in a room, please

ƽ

apply heat

insulation to

Less than

5cm

con

rm that

drainage

it without fail.

Crack

Indoor unit

Check Items for Test Run

Gas leak from pipe connecting?

Heat insulation of pipe connecting?

Are the connecting wirings of indoor and outdoor

rmly

Is the connecting wiring of indoor and outdoor

rmly

xed?

Is drainage securely carried out?

Is the earth line securely connected?

Is the indoor unit securely

xed?

Is power source voltage abided by the code?

Is there any noise?

Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performed normally?

Is the operation of room temperature regulator normal?

Please kindly explain to our customers how to

operate through the instruction manual.

inserted to the terminal block?

Ƶ

Put check mark

in boxes

Flare tooling die

1.Cut pipe

2.Remove burs

3.Insert the

are nut

4.Flare pipe

ƽ

ƽ

On Drainage

Check for Installation and Test Run

7

Содержание JS026-B1

Страница 1: ...ion manual before using the air conditioner Keep this operation manual for future reference This appliance is filled with R32 SPLIT TYPE ROOM AIR CONDITION OPERATION MANUAL 0010598298 ER JS026 B1 JS03...

Страница 2: ...ontacts should not be no less than 3mm Such means for disconnection must be incorporated in the Make sure installation is done according to local wiring regulation by professional persons A leakage ex...

Страница 3: ...9 1 2 8 5 Contents PARTS AND FUNCTIONS OPERATION INDOOR UNIT INSTALLAION MAINTENANCE CAUTIONS TROUBLE SHOOTING 10...

Страница 4: ...y 6 TIMER OFF display TIMER ON display 7 TEMP display 16 LOCK button Used to lock buttons and LCD display 25 RESET button When the remote controller appears abnormal use a sharp pointed article to pre...

Страница 5: ...de but only in FAN mode AUTO is not available in FAN mode And temp setting is disabled In FAN mode sleep operation is not available Emergency Operation Use this operation only when the remote controll...

Страница 6: ...after SLEEP mode starts temp will become 2 lower than temp setting After another 1 hours temp decrease by 2 rises by 1 futher The unit will run for further 3 hours then stops Temp is lower than temp...

Страница 7: ...electrical and electronic products conditioning system treatment of the refrigerant of oil and of other part must be done by a qualified installer in accordance with relevant local and national legisl...

Страница 8: ...disturbed Place possible to drain easily where piping can be conne cted with the outdoor unit Place where cold air can be spread in a room entirely Place nearby a power receptacle with enough space ar...

Страница 9: ...the drain hose then fasten them with the adhesive tape Left Left rear piping In case of left side piping cut away with a nipper the lid for left piping In case of left rear piping bend the pipes accor...

Страница 10: ...to wiring error Faulty PCB Faulty EEPROM data Faulty EEPROM Faulty PCB Faulty connector connection Faulty therm istor Faulty PCB Room temperature sensor failure The power source must be exclusively us...

Страница 11: ...door unit using vacuum cleaner or flaping them lightly otherwise its performance will be affected the cool and dry conditions For Smart Use of The Air Conditioner Replacement of Air Purifying Filter T...

Страница 12: ...TION PROHIBITION PROHIBITION PROHIBITION Do not start or stop the operation by disconnecting Do not channel the air flow directly at people especially at infants or the aged Do not try to repair or re...

Страница 13: ...is it with the type of T 3 15A 250V outdoor broken change it with the type of T 25A 250V The refrigerating circuit is leak proof 1 Applicable ambient temperature range Specifications The machine is a...

Страница 14: ...1 2 8 5 10 6SLV WUH FL I I FUNKCJE 2 6 8GA M217 JEDNOSTK 1 TRZNEJ KONSERWACJA 52 26752 12 CI R2 1 PROBLEM W tej instrukcji 32 producenta powierzchni co najmniej 1 2m2 8 lokalnymi normami 07RN F 3 R32...

Страница 15: ...ego modelu kratka wlotu mo e si r ni si w rzeczywisto ci od tej pokazanej w instrukcji obs ugi 2 3 1 2 3 1 Wy wietlacz Wska nik trybu pracy zapala si gdy spr arka pracuje Wy wietlacz temperatury pomie...

Страница 16: ...RZDQLD 2 0 872 LVSOD FLUFXODWHG 3UDFD DZDU MQD L NRQWUROQD 5HJXODFMD NLHUXQNX QDZLHZX SRZLHWU D 3UDFD DZDU MQD 2SFM SUDF DZDU MQHM QDOH Z NRU VW ZD MHG QLH ZWHG JG SLORW GDOQHJR VWHURZDQLD RVWDQLH XV...

Страница 17: ...OL V PERO EXG LND ODZLV 21 50 1 Z ZR D ZWHG IXQNFM SUDF QRFQHM 8ZDJD D F HQLH IXQNFML 785 2 Z WU ELH FK RG HQLD 22 VSRZRGXMH QLHUyZQRPLHUQ UR N DG WHPSHUDWXU Z SRPLHV F HQLX 8WU P ZDQLH SU H G X V F D...

Страница 18: ...U E SUDF L WHPSHUDWXU QLFMRZDQLH IXQNFML GURZRWQHJR QDGPXFKX SRZLHWU D FLVNDM F NODZLV 75 81 7 21 QDOH SU HM GR IXQNFML GRGDWNRZ FK L Z EUD MHGQ GZyFK RSFML QDGPXFKX SRZLHWU D QD ZSURVW XSZDUGHU Z Gy...

Страница 19: ...iedni przestrzeni wok Miejsce w odleg o ci 1m od odbiornik w telewizyjnych radiowych urz dze bezprzewodowych i wietl wek W sytuacji zamontowania pilota do ciany miejsce gdzie jednostka wewn trzna b dz...

Страница 20: ...ie ci w szczelinie materia u izolacyjnego jednostki wewn trznej 2 Umie ci wewn trzno zewn trzny kabel elektryczny z tylnej strony jednostki wewn trznej i wyci gn go z przodu a nast pnie pod czy 3 Prz...

Страница 21: ...5 2 0mm Prawid owy Nieprawid owy Nachylony Uszkodzony ko nierz P kni cie Cz ciowy Zbyt rozchylony na zewn trz 7 Odp yw W odprowadzaj cy skropliny powinien tworzy lekk pochy o ku do owi Nie nale y wyk...

Страница 22: ...h rodk w czyszcz cych 4 Zamontowa filtr standardowy konieczne UWAGA Bia a strona filtra fotokatalicznego powinna by zwr cona na zewn trz a czarna ku urz dzeniu Z kolei zielona strona filtra antybakter...

Страница 23: ...j cego ZABRONIONE Wk adanie przedmiot w do otworu wylotowego i wlotowego zabronione Zabrania si pod czania i od czania urz dzenia od pr dy przez ci gniecie kabla Zabrania si kierowania strumienia powi...

Страница 24: ...iep a rodki ostro no ci Zastawienia lub przykrywanie kratek klimatyzatora zabronione Wk adanie palc w i innych przedmiot w do wlotu i wylotu oraz pomi dzy prowadnice zabronione Obs uga urz dzenia prze...

Отзывы: