10.6 Timer  -  time schedule 

There  are  2  timer  periods  for  each  day  available. 
Tapping  the  slider  in  the  top  right  corner  will 
change between 1 or 2 time periods.  

The times for the first time periods are on the top of 
the  screen,  the  times  for  the  second  timer  period 
are on the bottom of the screen. Times can be ad-
justed in 15 minute intervals using the buttons. 

When  the  timer  is  active,  an  icon  will  appear  on 
the home screen giving information about the next 
switch time. 

10.7 External switches 

There is a provision for 2 remote switches than can 
be wired into the air curtain with. The switches must 
be voltage free type, NO or NC configuration.  

SW1 can be connected to a door switch or occu-
pancy sensor installed in the door area.  When the 
function  is  activated,  the  door  switch  will  enable 
the air curtain when the door is open and disable it 
when  the  door is  closed.  The  second  slider is used 
to configure the system for the correct switch type. 
When the air curtain is disabled by the door switch, 
the heater will operate at a low fan speed. This will 
allow  for  a  fast  start-up  when  the  door is  opened. 
When SW1 is active, the home screen will show the 
status of the door switch. 

SW2  is  intended  for  a  remote  switch  that  can  be 
used to disable the air curtain from a remote loca-
tion. Usually this would be a simple BMS or external 
timer  connection.  Once  disabled  using  remote 
switch  the  air  curtain  can’t  be  controller  by  the 
touchscreen  controller  and  will  remain  disabled 
until enabled remotely. 

 

10.8 Operating Mode selection

 

One of four operating modes can be selected. 
Each  mode  uses  a  different  method  of  select-
ing heat and fan settings when the air curtain is 
not  in  stand-by  mode.  Use  the  settings  button 
to configure each mode. 

 10.9 Manual Mode

 

In  manual  mode  user  can  select  required  fan 
and  heat  output  by  tapping  +  or  -  symbols  on 
the home screen next to the fan and heat bars. 

There  are  8  fan  speeds  and  8  heat  settings 
available.  It  is  possible  set  maximum  and  mini-
mum  limits  for  fan  speed  and  heat  output. 
Once  limits  are  set  and  functions  activated, 
only limited fan speed and heat output will be 
available  on  home  screen  when  in  manual 
mode. 

Содержание HSAC12000E

Страница 1: ...epaired by any person not authorised by us This guarantee is offered to you as an extra benefit and does not affect your legal rights The correct electricity supply voltage is shown on the rating label attached to the appliance Reasonable care has been taken to ensure that this guide is accurate at the time of printing In the interest of progress the Company reserve the right to vary specification...

Страница 2: ... 6 3 Internal wiring of the heating element for 3 phase operation 6 4 Modification of internal wiring of the heating element for single phase operation 6 5 Modification for use on single phase HSAC9000E only 7 Installation Details 7 1 Screw location for grille removal 7 2 Mounting 7 3 Electrical Supply 7 4 Installation 8 Fault detection and LEDs 8 1 Fault detection 8 2 Overheat protection reset 9 ...

Страница 3: ...ight of the appliance 1 3 Electrical Supply This heater must be permanently connected to the electricity supply via a double pole switch having 3mm gap on each pole There are no exceptions All units must be wired in accordance with I E E regulations for the Electrical Equipment of Buildings BMS control time switches and door interlocks can be installed at the discretion and responsi bility of the ...

Страница 4: ... 1 6 28 127 167 5 7 5 6 25526 9 70263 5 25 6 9 867 QWURGXFWLRQ 2 2 Mechanical Switch Controller Each air curtain is supplied with HSRCU1 me chanical switch More details at Installer wiring section This controller will provide 2 fan speed and 3 heat setting options 2 3 Optional Upgrade Colour Controller Provides energy saving options Optional Color touch screen controller not supplied with the heat...

Страница 5: ... LPHQVLRQV L LQJ ORFDWLRQV LU XUWDLQ LPHQVLRQV L LQJ RFDWLRQV ...

Страница 6: ...KD 0D PRWRU SRZHU WHUQDO IXVH VL H DPSV SKD RQWUROOHU 5HPRWH VZLWFK RU 7RXFK FRORXU VFUHHQ FRQWUROOHU RQWUROOHU ZLULQJ FRUH PPð RU 7 7 ZLWK 5 FRQQHFWRUV DEOH WHUPLQDO VL H PP ð0D 0DLQV WHUPLQDO EORFN SRVLWLRQ HQWUH RI EDVH XQLW 7HUPLQDOV 1 RQWURO WHUPLQDO SRVLWLRQ HQWUH RI EDVH XQLW LU DWD LU YROXPH 0D VSHHG Pñ K LU YHORFLW 0D VSHHG 0 P V 0D VSHHG 0 P V 0D VSHHG 0 P V 0D VSHHG 0 P V 0D HOWD 7 XWR ...

Страница 7: ...U WHUQDO IXVH VL H DPSV SKD RQWUROOHU 5HPRWH VZLWFK RU 7RXFK FRORXU VFUHHQ FRQWUROOHU RQWUROOHU ZLULQJ FRUH PPð RU 7 7 ZLWK 5 FRQQHFWRUV DEOH WHUPLQDO VL H PP ð0D 0DLQV WHUPLQDO EORFN SRVLWLRQ HQWUH RI EDVH XQLW 7HUPLQDOV 1 RQWURO WHUPLQDO SRVLWLRQ HQWUH RI EDVH XQLW LU DWD LU YROXPH 0D VSHHG Pñ K LU YHORFLW 0D VSHHG 0 P V 0D VSHHG 0 P V 0D VSHHG 0 P V 0D VSHHG 0 P V 0D HOWD 7 XWR VSHHG 10 1RLVH O...

Страница 8: ...8 LULQJ HWDLOV QVWDOOHU LULQJ dϱ ĐĂďůĞ Optional external temperature sensor ...

Страница 9: ...9 DFWRU LULQJ ...

Страница 10: ...ain with a unique address DIP switch setting 000X is reserved for when a controller or BMS is not used E g air curtain 1 DIP switches set to 1000 External and door switches are connected between COM and SW1 or SW2 Their behaviour can be configured in the controller settings menu E g air curtain 2 DIP switches set to 0100 All possible addresses are 1 100X 2 010X 3 110X 4 001X 5 101X 6 011X 7 111X ...

Страница 11: ...select fan speed range For installation height of 2 3m set the DIP switches to 0000 For installation height of 3 4m set the DIP switches to 0001 SW1 on off SW2 low speed high speed SW3 1 3 heat output SW4 2 3 heat output CAT5 cable with RJ45 connectors can be used to network up to 7 air curtains in a daisy chain configuration The 2 DIP switches on all 7 connected air curtains must be set to differ...

Страница 12: ...scribe how to change the internal wiring After the internal wiring has been modified it is necessary to change labelling of the connector as shown on the picture below and also new rating label showing single phase supply must be use to cover the existing 3 phase operation rating label This has to be followed exactly SKDVH LQWHUQDO ZLULQJ 6LQJOH SKDVH LQWHUQDO ZLULQJ 0RGLILFDWLRQ IRU XVH RQ VLQJOH...

Страница 13: ...13 QWHUQDO ZLULQJ RI WKH KHDWLQJ HOHPHQW IRU SKDVH RSHUDWLRQ 0RGLILFDWLRQ RI LQWHUQDO ZLULQJ RI WKH KHDWLQJ HOHPHQW IRU VLQJOH SKDVH RSHUDWLRQ 0RGLILFDWLRQ IRU XVH RQ VLQJOH SKDVH HSAC9000E Only ...

Страница 14: ...14 0RGLILFDWLRQ IRU XVH RQ VLQJOH SKDVH HSAC9000E Only 0RGLILFDWLRQ IRU XVH RQ VLQJOH SKDVH HSAC9000E Only ...

Страница 15: ...ead screws 7 4 Installation It is the sole responsibility of the installer to ensure that the points of attachment to the building are sound Consultation with the consultant architect or owner of the building is recommended to ensure that a sound mechanically stable installation is achieved All attachments must be capable of supporting the weight of the product QVWDOODWLRQ HWDLOV Step 1 Carefully ...

Страница 16: ...DVXUHPHQW ZKHQ WULDFV VZLWFKHG RII 5HVSRQVH XWR UXQ PRWRU 0RWRU IDXOW 5HVSRQVH LVDEOH KHDWLQJ 7ULDF KHDWVLQN RYHUKHDW 5HVSRQVH 5HGXFH KHDWLQJ RZ SRZHU PHDVXUHPHQW ZKHQ WULDFV VZLWFKHG RQ DXVHV 7KHUPDO FXW RXW RSHUDW HG EORZQ IXVH PLVVLQJ SKDVH 1XPEHU RI IODVKHV DXOW Main PCB Main PCB Main PCB Secondary PCB Secondary PCB DXOW GHWHFWLRQ 2YHU KHDW SURWHFWLRQ UHVHW The heater is equipped with electron...

Страница 17: ...erface MODBUS RTU 9600 baud 8 bits 1 start bit no parity 2 stop bits mark parity 1 stop bit Supported MODBUS function codes 0x03 read multiple input registers 0x04 read multiple holding registers 0x06 write single holding register 0x10 write multiple holding registers 16 Bit Input Registers 1 Status 2 Temp 1 3 Temp 2 4 Temp Heatsink 5 Temp External 6 External Switches Temperatures are formatted as...

Страница 18: ...mer function 10 4 Lock PIN function can be enabled to prevent unwant ed operation of the heater or changing the set tings The PIN can be completely disabled enabled for settings only or all functions The default Pin is set as 1234 but can be changed using the Change Pin button If the PIN is forgotten contact Heatstore for technical help 10 5 Timer The 7 day timer function allows scheduling auto ma...

Страница 19: ...e air curtain is disabled by the door switch the heater will operate at a low fan speed This will allow for a fast start up when the door is opened When SW1 is active the home screen will show the status of the door switch SW2 is intended for a remote switch that can be used to disable the air curtain from a remote loca tion Usually this would be a simple BMS or external timer connection Once disa...

Страница 20: ... 10 12 Temperature Mode 2 This operating mode is suitable for situations where the heater is used to maintain the room temperature or where the requirement is to ad just the heat output based on the indoor outdoor temperature This operating mode can use either the internal or supplied external temperature sensor The temperature on the left defines the starting point below which the air curtain use...

Страница 21: ...e are general status faults and sensor screens The links to the faults and sensor screens are hid den when no faults have been identified 10 13 Heater status cont The general status screen shows details about the heater and all of the internal blower units The heater needs to be run before some of the values can be calculated The faults screen can provide detailed diagnos tics of faults for each i...

Страница 22: ...22 01 08 03 2022 Contact details Heatstore Unit 12 Access 18 Bristol BS11 8HT Telephone 0117 923 5375 Email enquiries heatstore co uk http www heatstore co uk ...

Отзывы: