Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

outdoors or spaces open to the outdoors. These 
include attics* and crawl spaces. Follow the National 
Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 
Air for Combustion and Ventilation for required size of 
ventilation grills or ducts.

*IMPORTANT:

 Do not provide openings for inlet or 

outlet into attic. If attic has a thermostat-controlled 
power vent, heated air entering the attic will activate 
the power vent.

IMPORTANT:

 Vent-free heaters add moisture to 

the air. Although this is benefi cial, installing heater 
in rooms without enough ventilation air may cause 
mildew to form from too much moisture. See Fresh 
Air for Combustion and Ventilation, pages 3 
through 5. 

INSTALLATION

NOTICE:

 This heater is intended for the use as 

supplemental heat. Use this heater along with your 
primary heating system. Do not install this heater as 
your primary heat source. If you have a central heating 
system, you may run system’s circulating blower while 
using heater. This will help circulate the heat throughout 
the house. In the event of a power outage, you can use 
this heater as your primary heat source for the duration 
of the outage. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 
heater, Gas furnace, Vented gas heater, Gas 
fi replace logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-
vent draws combustion air from the outdoors and 
vents to the outdoors.

Example:

Gas water heater 

40,000 Btu/hr

Vent Free   20,000 Btu/hr

Total   =60,000 

Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.

Example: 51,800 Btu/hr (maximum Btu/hr the   
 

space can support)

 

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confi ned 
space because the actual Btu/hr used is more than 
the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 
are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfi ned 
space, remove door to adjoining room or add 
ventilation grills between the rooms. See Ventilation 
Air From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Fig. 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfi ned. 

If actual Btu/hr used is less than the maximum 
Btu/hr the space can support, the space is an 
unconfi ned space. You will need no additional fresh 
air ventilation.

VENTILATION AIR

Ventilation from Inside Building

This fresh air would come from an adjoining unconfi ned 
space. When ventilation to an adjoining unconfi ned 
space, you must provide two permanent openings: one 
within 12” of the ceiling and one within 12” of the fl oor 
on the wall connecting the two spaces (see options 
1 & 2 of fi gure 2). You can also remove door into 
adjoining room (see option3, fi g 2). Follow the National 
Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 
Air for Combustion and Ventilation for required size of 
ventilation grills or ducts.

 WARNING:

 Rework worksheet, adding the space 

of the adjoining unconfi ned space. The combined 
space must have enough fresh air to supply all 
appliance in both spaces. 

Ventilation from Outdoors

If necessary provide extra fresh air by using ventilation 
grills or ducts. Connect these items directly to the 

Ventilation 
Gills into 
Adjoining 
Room - Op-
tion 1

Ventilation Gills into Ad-
joining Room - Option 2

12”

12”

Or remove 
door into 
Adjoining 
Room - 
Option 3

INLET 
AIR

OUTLET 
AIR

VENTILATION CRAWL SPACE

TO CRAWL 
SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 
ATTIC

OUTLET AIR

Figure 2

Figure 3.

Содержание HSVFBF10LPTS

Страница 1: ...not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installe...

Страница 2: ...nversion is not permitted WARNING Do not use any accessory not approved for use with this heater WARNING Any change to this heater or its controls can be dangerous Do not place clothing or other flammable ma terial on or near the appliance Due to high temperatures heater should be kept out of traffic and away from furniture and draperies Surface of heater becomes very hot when running Keep childre...

Страница 3: ...ir If heater keeps shutting off it requires servicing 5 Turn off and let cool before servicing Only a qualified service person should service and repair heater 6 Do not run heater Where flammable liquids or vapors are used or stored During dusty conditions 7 Before using furniture polish wax carpet cleaner or similar products turn heater off If heated the vapors from these products may create a wh...

Страница 4: ...smaller than defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by the methods described in the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 or applicable local codes SAFETY DEVICE This heater has a pilot with an Oxygen Depletion Sensor ODS safety shut off system The ODS pilot shuts off the heater if there ...

Страница 5: ... space can support 60 000 Btu hr Actual amount of Btu hr used The space in the above example is a confined space because the actual Btu hr used is more than the maximum Btu hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet and the space of an adjoining room If the extra space provides an unconfined space remove door to adjoining room or a...

Страница 6: ...t 18 inches above floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to heater Installing heater next to vinyl or cloth wall covering or operating heater where impurities such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc are present in the air may discolor walls WARNING...

Страница 7: ...is firmly fastened to wall studs Attaching to Wall using Anchor For attaching mounting bracket to hollow walls wall areas between studs or solid walls concrete or masonry Note Wall anchors mounting screws and spacer are in hardware package The hardware package is provided with heater 1 Drill holes at marked locations using 5 16 drill bit For solid walls concrete or masonry drill at least 1 deep 2 ...

Страница 8: ...off valve union and plugged 1 8 NPT tap Locate NPT tap within reach of test gauge hookup NPT tap must be upstream from heater see figure 11 A CSA AGA certified equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the CSA AGA certified equipment shutoff valve from your dealer IMPORTANT Install an equipment shutoff valve in an accessible location Th...

Страница 9: ...r front panel OPERATING YOUR HEATER FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance has a pilot that must be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sur...

Страница 10: ...back and forth while depressed until pilot lights 7 Keep control knob depressed in for ten 10 seconds after lighting pilot If pilot goes out repeat steps 4 5 6 and 7 If pilot does not stay lit refer to Troubleshoot ing pages 12 13 Also contact a qualified service person or gas supplier for repairs If control knob does not pop up when released contact a qualified service person or gas supplier for ...

Страница 11: ...tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 psig This can be done by using a vacuum cleaner in the blow position using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could damage the burner or pilot assembly In addition the directions that follow shou...

Страница 12: ...6 Replace thermocouple 7 Replace Control valve Burner does not light after ODS pilot is lit 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Clean burner orifice see Cleaning and Maintenance on page 11 or replace burner orifice 2 Replace burner orifice 3 Contact local gas company Delayed ignition of burner 1 Manifold pressure is too low 2 Burner orif...

Страница 13: ...ing Gas Connections page 9 2 Replace control valve Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See WARNING statement at top of page 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Connections page 9 Heater produces a clicking ticking noise just after burner is lit or shut off 1 Metal expanding while heati...

Страница 14: ...sembly w Thermocouple LP 1 20 70640 Thermostat Valve 1 8 80017 Burner Assembly 1 21 80019 Ignitor Pulse 1 9 80009 Orifice 1 22 80014 Ignitor Wire 1 10 80069 Burner Right Bracket 1 23 8001 1 Ignitor Bracket 1 11 80016 Elbow Adapter 90 Regulator Connection 1 24 80010 Thermostat Valve Mounting Bracket 1 12 80078 Regulator 1 25 80034 Glass Bracket 1 13 80055 Regulator Mounting Bracket 1 26 70569 Hose ...

Страница 15: ...PART DESCRIPTION QTY 1 80040 Wire Guard 1 1 1 80020 Regulator Connection 1 2 80051 Front Panel 1 12 80058 Floor Mounting Feet 1 3 80024 Reflector 1 13 80052 Back Panel 1 4 80030 Burner Assembly 1 14 80036 Wall Mounting Bracket 1 5 80056 ODS Pilot Assembly w Thermocouple LP 1 15 80028 Heat Shield 1 6 80032 ODS Bottom Bracket 1 16 80053 Back Heat Shield 1 7 80050 Fireproof Plate 1 17 70640 Thermosta...

Страница 16: ...rom defects in material and workmanship for a period of 5 year from date of purchase Enerco Technical Products Inc will repair or replace this product free of charge if it has been proven to be defective within the 5 year period and is returned at customer expense with proof of purchase to Enerco Technical Products Inc within the warranty period This warranty gives you specific legal rights and yo...