HeatStar HSVFB10LPT Скачать руководство пользователя страница 15

15

Installation Instructions and Owner’s Manual

Unvented Liquid Propane Fired Room Heater

* Item Not Shown  ** Must purchase assembly

70640

70640

Содержание HSVFB10LPT

Страница 1: ...ce agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be prov...

Страница 2: ...unning Keep children and adults away from hot surfaces to avoid burns or clothing igni tion Heater will remain hot for a time after shutdown Allow heater surfaces to cool before handling Young childre...

Страница 3: ...heater 4 If heater shuts off do not relight until you provide fresh outside air If heater keeps shutting off it re quires servicing 5 Turn off and let cool before servicing Only a quali fied service p...

Страница 4: ...ght con struction provide adequate combustion and ventila tion air by the methods described in the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 or applicable local codes 3 Add the Btu hr of...

Страница 5: ...space because the actual Btu hr used is more than the maximum Btu hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet and the space of an adj...

Страница 6: ...eater pilot and burner must be at least 18 inches above floor Locate heater where moving vehicle will not hit it CAUTION This heater creates warm air currents These currents move heat to wall surfaces...

Страница 7: ...screws until mounting bracket is firmly fastened to wall studs Attaching to Wall using Anchor For attaching mounting bracket to hollow walls wall ar eas between studs or solid walls concrete or mason...

Страница 8: ...Use of floor mounting feet will require you to use a 3 8 NPT street elbow to make gas connection CAUTION Never connect heater directly to the Propane supply This heater requires an external regulator...

Страница 9: ...for leaks in next section Low Pressure Test Pressure Equal To or Less Than psig 3 5 kPa 1 Close equipment shutoff valve see figure 13 2 Pressurize supply piping system by either using compressed air o...

Страница 10: ...ess knob is pushed in slightly Do not force 4 Wait five 5 minutes Then smell for gas in cluding near the floor If you smell gas STOP Follow B in the safety information above If you do not smell gas go...

Страница 11: ...rush to clean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit every 2 500 hours of operation or every three months We also recommend that you keep the burner tube and pilot a...

Страница 12: ...thermocouple 7 Replace Control valve Burner does not light after ODS pilot is lit 1 Burner orifice is clogged 2 Burner orifice diameter to small 3 Inlet gas pressure is too low 1 Clean burner orifice...

Страница 13: ...g Gas Con nections page 9 2 Replace control valve Gas odor during combustion 1 Foreign matter between control valve and burner 2 Gas leak See WARNING statement at top of page 1 Take apart gas tubing a...

Страница 14: ...14 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater UNVENTED LP GAS FIRED ROOM HEATER Model IR10LP BF10LP...

Страница 15: ...15 Installation Instructions and Owner s Manual Unvented Liquid Propane Fired Room Heater Item Not Shown Must purchase assembly 70640 70640...

Страница 16: ...em in all communication LIMITED WARRANTY Heatstar by Enerco warrants its heaters and accessories to be free from defects in material and workmanship for a period of 5 year from date of purchase Heatst...