5. Before installation

5.1 Installation regulations

5.2 Installation requirements

The unit should not be used in association with any of 

the following:

 

`

Water supplies that have either inadequate 

pressure or where the supply may be intermittent. 

(Minimum dynamic pressure 0.5 bar).

 

`

In areas where the water consistently contains a 

high proportion of solids, e.g. suspended matter 

that could block the strainer,  unless adequate 

filtration can be ensured.

 

`

In areas where the water supply contains chloride 

levels that exceed 250mg/L.

For information or advice regarding any of the above 

contact Technical Enquiries on: 0344 871 1535. 

 

The unit can be connected directly to the 

water supply source provided that a minimum dynamic 

pressure    of  0.5  bar  and  maximum  pressure  of  10  bar. 

If the measured inlet pressure exceeds this value then a 

pressure  reducing  valve  must  be  fitted,  this  is  available 

through supply partners detail on back page.

5.3 Transport and storage

If the unit has to be stored prior to installation, it must be 

in a secure area free from frost, excessive dampness 

and humidity.

5.4 Choice of location

The unit must be vertically wall mounted the following 

points should be considered:

The unit should be sited to ensure minimum dead leg 

distances, particularly to the point of most frequent use. 

However there should be a minimum height between 

the hot water outlet and the highest draw off point, 

outlet tap, of 1.2 meters.

Avoid  installations  where  extreme  cold  temperatures 

will be experienced. All exposed pipe work should be 

insulated.

The breather pipe work from the top of the unit should 

have a continuous fall, and ideally vent to an outside 

wall in a safe manner via the tundish supplied. 

Access to associated controls must be available for the 

servicing and maintenance of the system, the heater 

requires access from the front and underside for this 

purpose, refer to figure 6 page 12. Ensure that the wall 

the unit is mounted on, is perpendicular and capable 

of permanently supporting the weight when it is full of 

water 

see Table 1 on page 6 for the unit weights.

5.5 Positioning and access

It is important that as much access available is 

provided around the unit as is practical. In the event 

of a component failure, full access to the front and 

underside of the unit is required for servicing. A 

minimum of 150mm above the top of the unit must be 

kept clear for access, refer to figure 6, page 12. 

Access to all isolation valves and control valves in the 

water circuits, both hot and cold are also required for 

normal operation and servicing.

WARNING

Installation of the appliance must be carried 

out  by  a  qualified  engineer  in  accordance 

with prevailing and national regulations as 

listed below.

 

`

Building Regulations

 

`

The Building Standards (Scotland)

 

`

The Building Regulations (Northern 

Ireland)

 

`

I.E.E Electrical Regs

 

`

UK Water Regulations

WARNING

 

`

In the unlikely event that water from the 

unit should vent from this breather pipe 

then the water could be at an excessive 

temperature  exceeding  95  degrees. 

Therefore it is essential that the 

breather pipe work selected is capable 

of withstanding this temperature and 

must have no obstruction and allow free 

and safe passage for this hot water.

CAUTION

 

`

Ensure that the unit is correctly 

positioned. Consideration should 

be given to the access and space 

requirements for operating and 

servicing the unit.

 

The breather pipe assembly at the top can be 

positioned on either the left or right.

Figure 5: Breather pipe assembly 

Содержание R 45 PLUS 3KW

Страница 1: ...R PLUS Installation operation and maintenance manual...

Страница 2: ...Wall fixing 14 6 3 Water connections 16 7 Commissioning 18 7 1 General 18 7 2 Checklist before commissioning 18 7 3 Commissioning procedure 18 8 Operation 19 8 1 General 19 8 2 Overview 19 8 3 Temper...

Страница 3: ...ituation causing serious physical injury WARNING Risk of a dangerous situation causing slight physical injury CAUTION Risk of material damage Signals important information 1 3 Abbreviations DHW Domest...

Страница 4: ...sers liability To guarantee optimum operation of the appliance the user must adhere to the following instructions Read and follow the instructions given in the manuals provided with the appliance Call...

Страница 5: ...UTION Ensure the drain valve is covered securely with the supplied cap to ensure accidental use does not occur WARNING Only competent persons having received the appropriate training are permitted to...

Страница 6: ...fiche Technical parameters in accordance with European Commission regulations 814 2013 and 812 2013 Direct Suppliers name or trade mark R PLUS Supplier s model identifier 25L 3kW 45L 3kW 70L 3kW 120L...

Страница 7: ...G Item 25L 45L 70L 120L A 830 882 1221 1021 B 510 609 609 660 C 380 425 425 457 D 74 76 76 76 E 204 245 245 396 F 235 276 276 429 G 180 220 220 362 H 148 188 188 325 I 415 463 463 562 Figure 2 Genera...

Страница 8: ...N W L1 L2 L3 J5 Electronic control L N Thermistor Solenoid valve Element Figure 3 Circuit diagram Upper level sensor Lower level sensor Terminal block Earth ground Thermal cutout Thermostat 1 2 3 4 5...

Страница 9: ...e via an immersion heater The hot water temperature programmed in the unit is factory set to 60 degrees centigrade but can be adjusted to suit the installation requirements by adjusting the temperatur...

Страница 10: ...ored water temperature during this function exceeds that which is safe for hand wash requirements if the stored hot water is used for hand washing then an appropriate water tempering device must be fi...

Страница 11: ...t to an outside wall in a safe manner via the tundish supplied Access to associated controls must be available for the servicing and maintenance of the system the heater requires access from the front...

Страница 12: ...12 Figure 6 Clearance diagram 10 10 150 1000 80 A 80 10 B 250 10 C R 25L PLUS R 45L PLUS R 70L PLUS R 120L PLUS A 510 609 609 660 B 830 882 1221 1020 C 235 275 275 429 Table 5 Clearance dimensions...

Страница 13: ...Hot water outlet 22mm open end pipe Breather pipe 22mm open end pipe Initial Breather Pipe with tundish supplied in kit A full bore isolating valve must be inserted into the 15mm cold water inlet pip...

Страница 14: ...ly used by the water heater being replaced see tables 6 and 7 below When fitting the wall bracket ensure that the fixings used are suitable for the wall structure and the weight of the water heater wh...

Страница 15: ...with the fixing bracket attached the water heater will not sit flat to the floor and therefore will be unstable Care must be taken not to allow the heater to topple over Refer to table 1 page 6 for t...

Страница 16: ...rn Ireland must be adhered to The above regulations require the following A full bore servicing valve shall be installed on the inlet pipe Schedule 2 Section 16 2 A full bore servicing valve shall be...

Страница 17: ...lready exists move the assembly to the correct side of the water heater Once installed connect the breather pipe to the 22mm compression fitting on the Tundish ensure connection is tight secure all pi...

Страница 18: ...0 seconds the heater will switch the solenoid valve on and allow water to flow into the heater If this does not happen refer to section 10 page 25 Troubleshooting Check all pipe work and the water hea...

Страница 19: ...s essential that a suitable low pressure water tempering valve is fitted in the hot water supply circuit The installer must ensure that this is carried out during installation As an end user if you ar...

Страница 20: ...ully disconnect the Tundish from the breather pipe by unscrewing the small nut on the 15mm pipe side of the Tundish Carefully split the connection between the 15mm pipe and the Tundish once apart this...

Страница 21: ...ter must be replaced see spares list page 29 spare 13 9 3 2 1 Inlet Pipe Filter replacement If the mesh filter requires replacement the inlet control pipe may have to be replaced item 28 in the spares...

Страница 22: ...he start of this section Once removed inspect the end of the stainless steel bolt that is on the water side Carefully remove any build up of scale using the tip of a flat blade screwdriver Lightly lub...

Страница 23: ...25 ECO sensor connection Remove fixing bolts as shown in figure 26 Gently loosen the immersion heater from its housing Once loose remove the immersion by twisting the immersion in an arc and then ver...

Страница 24: ...could permanently damage the immersion heater Inspect the immersion heater for excess build up of scale all coils should be free of scale build up between them and there should be no build up of scal...

Страница 25: ...supply drain unit and investigate the fault Leaking pipe work Turn off the power turn off the water supply drain unit and investigate the fault Leaking immersion seal Turn off the power turn off the w...

Страница 26: ...LED 3LED 2 LED 1 On Figure 30 LED s close up Fault error code Fault Cause of fault Remedy E1 Indicates that a fault has been detected by the Controller linked to the thermistor The thermistor is Open...

Страница 27: ...minutes during this period the lower level sensor has not detected water No water supply Check water inlet feed Filter blocked Check the condition of the filter in accordance with section 9 page 21 So...

Страница 28: ...te the water supply Drain the unit Disconnect the unit Remove the unit Cap pipe work 11 2 Environmental Information Products are manufactured from many recyclable materials At the end of their useful...

Страница 29: ...34207 15 Bottom fixing bracket 7034212 16 Main PCB Flat back 7034155 17 PCB clip 7034163 18 M5 x 10mm screw 7034189 19 Base shield 25L white 7034167 Base shield 45L 70L white 7034168 Base shield 120L...

Страница 30: ...45L 70 wiring 7034201 Thermistor 120L wiring 7034202 34 ECO sensor 7034199 35 Wiring loom 25L RPLUS 7034194 Wiring loom 45L 70L RPLUS 7034195 Wiring loom 120L RPLUS 7034196 Description Part Number Pac...

Страница 31: ...31 1 3 4 5 7 8 9 10 2 6...

Страница 32: ...32 15 9 10 11 12 13 14...

Страница 33: ...33 16 17 18 22 19 21 20 1 23 22 23 24 28 26 25 27 29...

Страница 34: ...34 30 31 32 33 34 35...

Страница 35: ...proof of purchase to register the product The Heatrae Sadia R PLUS product has not been modified in any way other than by Heatrae Sadia or Heatrae Sadia approved engineers The Heatrae Sadia R PLUS pr...

Страница 36: ...What type of scale reducer has been fitted What is the hot water thermostat set temperature C What is the hot water temperature at the nearest outlet C All appropriate pipes have been insulated up to...

Страница 37: ...ompany name Telephone No Gas safe register No Comments Signature SERVICE 02 Date Engineer name Company name Telephone No Gas safe register No Comments Signature SERVICE 03 Date Engineer name Company n...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...and sustainability charters and reduce our printed material we encourage you to download product brochures from our website In designing these files we have taken into account the need to access data...

Отзывы: