cover. Turn the backing disc over and refit to the knob ensuring the
notch  locates with the boss

 

on

 

the underside of the cover. Refit the

terminal cover, the thermostat will now be

 

locked in the “mid-

range” position.

5.10 Setting the “hot” position:

Rotate the thermostat knob to mid way through the hot graduated
range (red graphic). Follow the procedure detailed above, however
in this case the knob should be held in the “hot” position previously
set. When the terminal cover has been refitted the thermostat will be
locked in the “hot” position. This position is recommended when
using the heater in conjunction with a thermostatic blending valve.

6.0 MAINTENANCE - DESCALING

Little maintenance is required, however in hard water areas the unit will
require periodic descaling to ensure efficient operation. To descale the
unit:

6.1

Switch off and disconnect the electrical supply. Turn off the water
supply to the unit.

6.2

Open a hot tap to relieve any system pressure. Disconnect the
plumbing connections to the unit and remove from the wall bracket
(note full weights of units). Empty unit through the outlet connec-
tion.

6.3

Remove the terminal cover by using a large flat bladed screwdriver to
depress the 3 snap lugs located in the top 3 rectangular depressions.

6.4

Remove the plastic disc from the thermostat spindle. Remove the
insulating pad from the terminal housing. Disconnect the electrical
terminations to the thermostat. Disconnect earth links to the earthing
stud.

6.5

Remove the element plate assembly by unscrewing the five securing
screws, a tapped jacking point is provided. Remove any loose scale
from the container. Carefully clean off any scale from the element and
thermostat pocket. DO NOT clean scale from interior container walls.

6.6

Re-assemble the element plate assembly fitting a new sealing gasket.
Note the correct orientation of the element plate by reference to
Diagram 5 overleaf. Rewire the unit with reference to the Wiring
Diagrams. Refit the insulating pad and plastic disc to ensure the
correct operation of the thermostat.

6.7

Re-commission the unit following the INSTALLATION and COM-
MISSIONING instructions.

Содержание MULTIPOINT 10

Страница 1: ...tre Unvented Water Heaters HEATRAE SADIA HEATRAE SADIA HEATRAE SADIA HEATRAE SADIA HEATRAE SADIA The quality name in water heating Please read and understand these instructions before starting work Pl...

Страница 2: ...AND LEAD TO A DANGEROUS INSTALLATION 1 2 Expansion can take place within the cold water supply PROVIDED THAT BOTH a Backflow in the main is not prevented by any stopvalve with loose jumper check valv...

Страница 3: ...pansion in main supply is not possible Diagram 3 For inlet water pressures above 4 1 bar 60 p s i WARNING IF WATER FLOWS FROM THE PRESSURE RELIEF VALVE OR TEMPERATURE PRESSURE RELIEF VALVE THE ELECTRI...

Страница 4: ...hidden services electricity gas or water below the surface of the wall 2 5 DO NOT install where the unit may freeze 2 6 Refer to the section IMPORTANT INSTALLATION POINTS to determine which valves an...

Страница 5: ...or a 0 75m 3 core 2 5mm2 cable on the 4 5kW model The electicity supply should be fused 13 Amp for a 3kW model and 20 Amp for a 4 5kW model and be via a double pole isolating switch with a contact sep...

Страница 6: ...hat all water and electrical connections are tight 5 4 Open a hot water tap turn on mains water supply to the heater 5 5 Allow unit to fill and leave hot tap running for a short while to purge any air...

Страница 7: ...isconnect the plumbing connections to the unit and remove from the wall bracket note full weights of units Empty unit through the outlet connec tion 6 3 Remove the terminal cover by using a large flat...

Страница 8: ...ld have a precharge pressure of 4 1 bar 60 p s i This can reduce over time and eventually require re charging To do this 8 1 Turn off water supply to the unit open a hot tap to relieve system pressure...

Страница 9: ...assembly 10 litre 3kW 95606 921 Element plate assembly 15 litre 3kW 95606922 Element plate assembly 10 litre 4 5kW 95606923 Element plate assembly 15 litre 4 5kW 95606924 Combined thermostat thermal...

Страница 10: ...LATION POINTS 1 Fit Pack U2 see IMPORTANT possible 1 Expansion in mains not intermittently Presure Relief Valve Discharge of water from 2 Fit Packs U1 and U2 4 1 bar 60 p s i 2 Mains pressure exceeds...

Страница 11: ...B This will not protect other system pipework 12 2 The thermostat can also be locked in either the mid range or a hot recommended when using in conjunction with a Thermostatic Blending Valve position...

Страница 12: ...potable water 5 Within 60 days of installation the user completes and returns the certificate supplied along with proof of purchase to register the product The unit is not guaranteed against damage by...

Отзывы: