Pairing the Thermostat

Pairing With the UH1-W Wiring Centre 

• 

On the receiver, press and hold the Pairing button until the Comms LED lights up.

• 

With the thermostat turned OFF, press & hold the A button for 5 seconds ...........

• 

The thermostat will send a signal for 1 minute and will flash the RF signal icon ...

• 

If pairing is successful, the Comms LED on the receiver will flash.

• 

Press the Power button on the thermostat once to confirm pairing ........................

If pairing is unsuccessful, check features 06 to 08 have been configured correctly.

To eliminate a possible signal issue, reposition the thermostat closer to the receiver and 
repeat the pairing process again.

On the UH1-W wiring centre, take note of the number set on 

the rotary switch (Board ID number 1-9). 
Each UH1-W on the system needs to have a different ID number.
With the thermostat turned OFF:

• 

Press & hold the Clock button until 2 sets of numbers appear on screen ..............

• 

The small number 01 in the top right corner of the LCD is the feature number.

• 

Press Clock repeatedly until you see feature 06 (Receiver Type) .......................

The options within feature 06 are: 00 = UH1-W or 01 = RC1-W receiver.

• 

Use the Up/Down keys to set feature 06 to 00 (UH1-W) ..............................

• 

Press Clock again until you see feature 07 (UH1-W Board Address) ................

• 

Use the Up/Down keys to set the large digits to the board address

of the UH1-W. This is the number set on the UH1-W rotary switch...

(You must set a unique board address for each UH1-W installed).

• 

Press Clock again until you see feature 08 (Zone number, 01-08) ....................

• 

The UH1-W is an 8 zone receiver.

Use the Up/Down buttons to select the zone this thermostat

should be linked to ....................................................................................................

• 

Press Clock again until you see feature 09 .................................................................

(00 = Underfloor heating, 01 = Radiators.)

• 

Use the Up/Down buttons to specify whether the thermostat is

controlling underfloor heating or radiators .....................................................

• 

Press A to confirm settings and the display will go blank ....................................

• 

Press the Power button once to turn the thermostat back ON .........................

• 

Press the Up key to set the target temperature above the room

temperature; the flame symbol will appear and the assigned

zone on the UH1-W will be activated ..........................................................................

This indicates pairing between the thermostat and the UH1-W is successful.

Содержание PRT-W1

Страница 1: ...1 Model PRT W Model PRT W...

Страница 2: ...Replacing the Batteries Pairing with the RC1 W Receiver Pairing with the UH1 W Wiring Centre LCD Display Setting the Clock Temperature Display Setting the Comfort levels Locking the Thermostat Settin...

Страница 3: ...fires televisions wall or table lamps may also prevent the thermostat from working properly What is a Programmable Room Thermostat A programmable room thermostat is both a programmer and a room thermo...

Страница 4: ...own in the diagram on page 30 Mark 2 hole positions on the wall using the backplate as a positioning template Drill at the marked positions and insert a wall plug into each hole Step 3 Screw the therm...

Страница 5: ...access the battery holder push and release the compartment door located on the bottom face of the thermostat Insert the batteries in the empty battery holder ensuring that each battery is orientated f...

Страница 6: ...u must set a unique receiver address for each receiver installed Press Clock again until you see feature 08 Zone number You are able to connect two PRT W thermostats to one RC1 W receiver Use the Up D...

Страница 7: ...the LCD is the feature number Press Clock repeatedly until you see feature 06 Receiver Type The options within feature 06 are 00 UH1 W or 01 RC1 W receiver Use the Up Down keys to set feature 06 to 0...

Страница 8: ...verriding the program HOLD FOR and the time period are displayed 7 Set Displayed when changes are made to programs or temperature set points 8 Holiday Indicator Displayed when the programmer is in hol...

Страница 9: ...minutes Press H to confirm settings Use the Up Down keys to set the day of the week Press A to confirm settings and return to main display Temperature Display Room Temperature Set Temperature This is...

Страница 10: ...different comfort levels To program comfort levels press Clock once Use the Up Down keys to enter the required WAKE time Press H to confirm settings Use the Up Down keys to enter the required WAKE te...

Страница 11: ...return to main display Set Temperature Set Icon Locking the Thermostat The thermostat has a keypad lock facility To activate the lock follow these steps Press and hold the A and Down keys together for...

Страница 12: ...temperature hold function allows you to manually override the current operating program and set a different temperature for a desired period Press H to commence temperature hold Use the Up Down keys...

Страница 13: ...g be turned on whilst in frost mode the flame icon will be displayed To cancel the frost protect mode press the Power button once again Frost Mode Heating On Off The heating is indicated ON when the f...

Страница 14: ...or Heating or Radiator Zone UH1 W Only This setting determines whether the thermostat will activate the pump boiler output on the UH1 W If set to 00 the outputs will be activated 00 UFH 01 Radiators F...

Страница 15: ...tes 00 Default 00 UH1 W 01 RC1 W 00 Default UH1 W 01 09 RC1 W 01 32 00 Default UH1 W 01 08 RC1 W 01 02 Underfloor Heating 00 Radiator Zone 01 00 Disabled 01 Enabled 01 Default 00o 10o C 00o C Default...

Страница 16: ...the Up Down keys to configure the new temperature Press A to confirm settings Press the Power button once to turn the thermostat back ON Factory Reset To perform a factory reset follow these steps Pr...

Страница 17: ...Call our support team on 44 0 1254 669090 Or view technical specifications directly on our website www heatmiser com PDF FAQ Heating Professionals Request a copy of our product installation guide cont...

Отзывы: