GAS PIPING AND GAS PRESSURE REQUIREMENTS 

HVF36-BB & HVF42-BB 

All gas piping must be installed to comply with local codes or, in the absence of local codes

with the latest edition of the 

National Fuel Gas Code ANSI 223.1/NFPA 54. 
Unions in gas lines shall be of the ground joint type. Compounds used on threaded joints of gas piping must be resistant 
to the action of liquefied petroleum gas. 
Gas piping must be of sufficient size to provide a minimum natural gas pressure at the appliance of  7” water column or 
11” for LP gases. The maximum inlet pressure to the unit must not exceed 10” for natural gas and 13” for LP gases. Mani-
fold pressure for natural gas is 4”WC and 10”WC for LP gas.  If this unit is to be supplied with LP gas (bottled propane) the 
tank or bottle supplying the gas must have a regulator that reduces the gas pressure to between 11 and 13 inches water 
column. The control will not operate with gas line pressure directly from the tank and may leak gas due to this excessive 
pressure.

 

DANGER: 

OPERATION OF THIS UNIT ON LP GAS WITHOUT AN APPROVED REGULATOR AT THE SUPPLY CON-

TAINER WILL LEAD TO GAS LEAKS AT THE CONTROL WITH POSSIBLE FIRE OR EXPLOSION. 

 

Include a manual shutoff valve and union in the line so the control or heater may be disconnected for servicing. Include a 
drip leg and a plugged 1/8-inch N.P.T. tapping in the line also. The tapping must be accessible for test gauge connection 
immediately upstream of the gas supply connection to the unit. 

 

Use a soap-water solution or a liquid gas leak detector to coat each joint in the piping system and look for bubbles, which 
indicate gas leaks. Repair all gas leaks. 

  

CAUTION: 

THE LOG SET AND ITS INDIVIDUAL SHUTOFF VALVE MUST BE DISCONNECTED FROM THE GAS SUP-

PLY PIPING SYSTEM DURING PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2 
PSIG.  THE  UNIT  MUST  BE  ISOLATED  FROM  THE  GAS  SUPPLY  PIPING  SYSTEM  BY  CLOSING  ITS  INDIVIDUAL 
MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING OF THE GAS SUPPLY  PIPING SYSTEM AT TEST 
PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG. PRESSURES IN EXCESS OF 1/2 PSIG WILL CAUSE DAMAGE 
TO THE CONTROL VALVE AND MAY CAUSE DAMAGE TO THE SHUTOFF VALVE. 

 

DANGER: 

DO  NOT  USE  CANDLES,  MATCHES  OR  OTHER  IGNITION  SOURCES  WHEN  CHECKING  FOR  LEAKS. 

FUEL GASES ARE VERY FLAMMABLE AND, IN CERTAIN CONCENTRATIONS, EXPLOSIVE. CHECKING FOR LEAKS 
WITH AN OPEN FLAME MAY LEAD TO FIRE OR EXPLOSION.   
 
 
 
                                                  

 

Fireplace screens need to be closed before operation of this unvented decorative room heater.

 

This firebox has no chimney; therefore, 

DO NOT

 burn anything such as household refuse, paper, firewood, or manufac-

tured composition logs.   Burning anything in this firebox other than properly plumbed LP or Natural gas connected to a 
decorative type unvented room heater is strictly prohibited.  Doing so will cause an immediate hazard and void any and all 
warranties associated with this product. 

IMPORTANT: SAFETY 

 

Содержание HVF36-BB

Страница 1: ...ON INSTALLER LEAVE THIS MANUAL WITH THE APPLIANCE CONSUMER RETAIN THIS MANUAL FOR FUTURE VENT FREE FIREBOX MODEL HVF36 BB HVF42 BB INSTALLATION OPERATION AND MAINTENANCE MANUAL FOR USE ONLY WITH LISTE...

Страница 2: ...cal building officials to assure compliance with local regulations and codes and to obtain any required permits A qualified installer or service agency must perform installation and service All instru...

Страница 3: ...panels or surrounds shall not seal ventilation openings in the fireplace 7 Make sure to leave adequate clearances for accessibility for purposes of servicing and proper operation 8 Combustible floorin...

Страница 4: ...NCES COMBUSTIBLE SIDE WALL INSTALLATION COMBUSTIBLE SIDE WALL PLACEMENT HVF36 BB FOR HVF36 BB HVF42 BB COMBUSTIBLE SIDE WALL INSTALLATION HVF42 BB GUIDELINE DIMENSIONS FOR CORNER APPLICATION HVF36 BB...

Страница 5: ...3 8 Framing dimension for width 38 1 4 44 1 4 Framing dimension for Depth 24 3 4 24 Fireplace Model Inner Dimensions HVF36BB HVF42BB Height of rear wall 22 22 1 2 Width of front opening 29 1 2 35 1 2...

Страница 6: ...ick tile or various other natural or man made materials CAUTION THE BLACK PAINTED FACE OF THE FIREBOX EXCLUDING NAIL FLANGES MUST NOT BE COVERED WITH COMBUSTIBLE MATERIALS SOME MAN MADE BRICKS OR STON...

Страница 7: ...e line also The tapping must be accessible for test gauge connection immediately upstream of the gas supply connection to the unit Use a soap water solution or a liquid gas leak detector to coat each...

Страница 8: ...RONT BOTTOM HVFBB36 02 14 HVFBB42 02 18 1 11 OUTER CAP BRACE HVFBB 02 18 HVFBB 02 18 3 12 COVER PLATE HFB 02 13 HFB 02 13 1 13 THERMODISC 11 1395 11 1395 1 HOOD NOT SHOWN HVFBB36 02 25 HVFBB42 02 25 1...

Страница 9: ...ng or other delivery to Heatmaster LLC American Gas Log LLC shall be borne by the purchaser The mailing address is Heatmaster LLC American Gas Log LLC 3625 Benson Rd Angier NC 27501 3 Along with the p...

Отзывы: