Heatilator • Birmingham BIR50-B Installation Manual • 4059-701 • Rev G • 06/29/15
(4) Roof
Radiation
Shields
Chimney Section
Chimney Section
Attic Insulation
Shield & Collar
Square Frame
Firestop
Square Frame
Firestop
Chimney Section
74 1/8 in.
(1883 mm)
Effective
Height
Termination
Cap
Storm
Collar
Chase Top
Flashing
Figure 4.1
Determine the chimney components needed to complete
your particular installation:
• Measure the total vertical height of the fireplace
installation from the base of the fireplace assembly to
the approximate location of the bottom of the termination
cap.
• Subtract the effective height of the fireplace assembly
(see Figure 4.1) from the total vertical height to determine
the overall height of the chimney installation.
• Create a schematic for your application similar to Figure
4.1 showing components required (referring to Table 4.1).
• Install a ceiling firestop whenever the chimney penetrates
a floor/ceiling.
NOTICE:
A maximum of two offset and return may be
used.
CAUTION!
Risk of Fire and/or Asphyxiation!
DO
NOT
connect this fireplace to a chimney flue servicing
another appliance. Do NOT connect to any air distribu
-
tion duct or system. These actions could cause over
-
heating/fire in the chimney flue, or release of exhaust
fumes into the living areas.