background image

Heatilator  •  ADI-ZCFB-S  •  2032-910 Rev. i  •  6/09

30

A.  Standing Pilot Ignition System

13 

Troubleshooting 

 

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service.  If you do 

experience a problem, this troubleshooting guide will assist a qualifi ed service person in the diagnosis of a problem and the 

corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed service technician. 

Symptom

Possible Causes

Corrective Action

1.  After repeated triggering 

of the red or black piezo 

ignitor button, the spark 

ignitor will not light the pilot.

a. Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode 

wire is properly connected, replace the ignitor.

b. Defective pilot or misaligned 

electrode (spark at electrode).

Using match, light the pilot. If the pilot lights, turn off the pilot and 

trigger the red piezo ignitor button again. If the pilot lights, an im-

proper gas/air mixture caused the bad lighting and a longer purge 

period is recommended. If the pilot will not light, ensure the gap 

at the electrode and pilot is one-eighth (1/8) inch to have a strong 

spark. If the gap is OK, replace the pilot.

c. No gas or low gas pressure.

Check the remote shut-off valves from the fi replace. Usually, there 

is a valve near the gas main. There can be more than one (1) valve 

between the fi replace and the main.

d.  No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.  The pilot will not stay lit 

after carefully following the 

lighting instructions.

a. Defective thermocouple.

Check that the pilot fl ame impinges on the thermocouple. Clean 

and/or adjust the pilot for maximum fl ame impingement.
Ensure that the thermocouple connection at the gas valve is fully 

inserted and tight (hand tighten plus 1/4 turn).
Disconnect the thermocouple from the valve, place one millivolt 

meter lead wire on the tip of the thermcouple and the other meter 

lead wire on the thermocouple copper lead. Start the pilot and hold 

the valve knob in. If the millivolt reading is less than 15mV, replace 

the thermocouple.

b.  Defective valve.

If the thermocouple is producing more than 15 millivolts, replace 

faulty valve.

3.  The pilot is burning, 

there is no burner fl ame, 

the valve knob is in the ON 

position, and the ON/OFF 

switch is in the ON position.

a. ON/OFF switch or wires 

defective.

Check the ON/OFF switch and wires for proper connections. Place 

the jumper wires across the terminals at the switch. If the burner 

comes on, replace the defective switch. If the switch is OK, place the 

jumper wires across the switch wires at the gas valve. If the burner 

comes on, the wires are faulty or connections are bad.

b. Thermopile may not be gener-

ating suffi cient millivoltage.

If the pilot fl ame is not close enough physically to the thermopile, 

adjust the pilot fl ame.
Be sure the wire connections from the thermopile at the gas valve 

terminals are tight and that the thermopile is fully inserted into the 

pilot bracket.
Check the thermopile with a millivolt meter. Take the reading at 

TH-TP&TP terminals of the gas valve. The meter should read 325 

millivolts minimum, while holding the valve knob depressed in the 

pilot position, with the pilot lit, and the ON/OFF switch in the OFF 

position. Replace the faulty thermopile if the reading is below the 

specifi ed minimum.
With the pilot in the ON position, disconnect the thermopile leads 

from the valve. Take a reading at the thermopile leads. The read-

ing should be 325 millivolts minimum. Replace the thermopile if the 

reading is below the minimum.

Содержание ADI-ZCFB-S

Страница 1: ...ed on the rating plate Leave this manual with party responsible for use and operation DO NOT DISCARD Important operating and maintenance instructions included Read understand and follow these instruct...

Страница 2: ...appliance can be found on the rating plate usually located in the control area of the appliance Homeowner Reference Information Not for use with solid fuel Ne doit pas entre utilise avec un combustib...

Страница 3: ...ppliance A Venting Components 12 B Connecting Vent Pipe 12 C Placing Securing and Leveling the Appliance 14 D Installing Adaptor and Termination Cap 15 8 Gas Information A Fuel Conversions 16 B Gas Pr...

Страница 4: ...o ANSI standards for Vented Gas Appliance Heaters and applicable sections of Gas Burn ing Heating Appliances for Manufactured Homes and Recreational Vehicles and Gas Fired Appliances for Use at High A...

Страница 5: ...cal regional state and national codes and regulations Consult insurance carrier local building re of cials or authorities having jurisdiction about restrictions installation inspection and permits A D...

Страница 6: ...ure lines or spider webbing on the surface of the material Cracks that are less than 1 32 in wide and less than 3 in long If cosmetically unacceptable such cracks may be repaired with the SRV PACK ser...

Страница 7: ...f c and away from furniture and draperies The rebrick refractory glass doors screen rails screen mesh and log grates can be removed from a factory built rebox in order to gain minimum gas insert openi...

Страница 8: ...isk Locate and install appliance to all clearance speci cations in manual Fire Risk Odor Risk Clearance to combustible material under the insert is 1 4 inch 0 6 cm Use leveling legs to raise insert mi...

Страница 9: ...to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7...

Страница 10: ...n of this appliance or other appliances connected to the ue Vent this appliance directly outside Use separate vent system for this appliance B Horizontal Venting Horizontal venting is NOT allowed 5 Ve...

Страница 11: ...fuels unless all original parts have been replaced and the replace re approved by the authority having jurisdiction F Remote Control The receiver for the remotes must be installed BETWEEN the base pan...

Страница 12: ...ence instructions in the termination kit Install the 3 inch exible vent pipe s down through the chimney Secure the exhaust exible vent pipe to the 3 foot section stainless steel flexible vent pipe usi...

Страница 13: ...C ADPB For Flashing Class A Pipe TERMINATION CAP SQUARE FLASHING REMOVED EXHAUST VENT PIPE SUPPLIED WITH TERMINATION KIT INLET AIR VENT COLLAR LINK DV30 SHOWN ALTERNATIVE INSTALLATION FOR VENTING THRO...

Страница 14: ...her to shorten Install fiberglass insulation pieces to back face of surround Attach surround Follow instructions accompanying surround Push insert so that surround becomes tight against face of replac...

Страница 15: ...ith self tapping screws included in kit Figure 7 4 To help eliminate cold air drafts it may be necessary to place non combustible insulation around the ues as they go though the damper Note The LINK D...

Страница 16: ...2 psig Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1 2 psig Verify inlet pressures High pressure may cause over re condition Low pressure ma...

Страница 17: ...e check with the local gas utility If installing this appliance at an elevation above 4500 feet in Canada check with local authorities CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk Ch...

Страница 18: ...0 120 VAC to operate It is recommended that a 110 VAC junction box be connected for use with fan or remote control See Figure 9 2 for junction box wiring Prevent accidental appliance operation when no...

Страница 19: ...Detach exible liner from back of unit if insert is installed Remove the four screws on the cover plate see Figure 9 3 Figure 9 3 RUBBER GROMMETS FAN ATTACH GROUND WIRE COVER PLATE Bend up the tabs on...

Страница 20: ...GROUND WHT BLK BLK BLK REMOTE RECEPTACLE INSERT STUD THROUGH HOLE AND SECURE WITH WING NUT WING NUT TEMP SWITCH BRACKET FAN TEMPERATURE SENSOR SWITCH SPEED CONTROL RHEOSTAT REMOTE OUTLET FAN OUTLET B...

Страница 21: ...vertical and corresponding maximum horizontal dimensions of appliance mantels or other combustible projections above the top front edge of the appliance not the surround 10 Finishing Figure 10 1 Clea...

Страница 22: ...nt Explosion Risk Follow ember placement instructions in manual Do NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interferes with proper burner op...

Страница 23: ...TRUCTIONS Log Placement CAUTION Logs are fragile Carefully remove the logs from the packaging FIREBOX LOG 1 FIREBOX LEDGE LOG 1 SRV2032 701 Place log 1 on the rebox ledge as shown The front portion of...

Страница 24: ...he tab on right front of the burner such that left end of log contacts log tab near the center of the burner LOG 2 SRV2032 702 Position log 2 by locating its slot over the tabs on left front of the bu...

Страница 25: ...LATCH GLASS ASSEMBLY PULL TO RELEASE LEFT SIDE G Air Shutter Setting Optimal ame appearance is dependent on the air shutter setting Adjustments should be made by a qualified technician Handle glass d...

Страница 26: ...ion manual provided with this appliance For assistance or additional information consult a quali ed installer service agency or the gas supplier Do NOT use this appliance if any part has been under wa...

Страница 27: ...mbustion and ventilation air If not installed operated and main tained in accordance with the man ufacturer s instructions this product could expose you to substances in fuel or fuel combustion which...

Страница 28: ...oducts used in the paint and logs During this break in period it is recommended that some windows in the house be opened for air circulation This will help avoid setting off smoke detectors and help e...

Страница 29: ...ance Combustible materials may ignite ISSUE SOLUTIONS Condensation on the glass This is a result of gas combustion and temperature variations As the appliance warms this condensation will disappear Bl...

Страница 30: ...mpingement Ensure that the thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt meter lead wir...

Страница 31: ...Check the LP propane tank Re ll the fuel tank b Inner vent pipe leaking exhaust gases back into the system Check venting system for damage Replace repair improperly assembled pipe sections c Glass to...

Страница 32: ...bly with care NOTE Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white lm on glass CAUTION When cleaning glass door Avoid striking scratch...

Страница 33: ...int condition warpage corrosion or perforation Sand and repaint as necessary 2 Replace appliance if rebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and alig...

Страница 34: ...16 in 27 mm Two 2 13 16 in 71 mm B 4 3 8 in 111 mm 1 9 16 in 40 mm 15 Reference Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For framing d...

Страница 35: ...sory Kits see Figure 15 3 Flash Damp Zero clearance damper ashing kit for use with LINK DV 30B or LINK DV4 30B liner kits LINK ZC ADP Zero clearance chimney adapter SVRLINK ADP Adapter kit colinear to...

Страница 36: ...Heatilator ADI ZCFB S 2032 910 Rev i 6 09 39 D Limited Lifetime Warranty...

Страница 37: ...Heatilator ADI ZCFB S 2032 910 Rev i 6 09 40 D Limited Lifetime Warranty continued...

Страница 38: ..._____________________________________________________ ________________________________________________________________________________ Printed in U S A Copyright 2009 This product may be covered by on...

Отзывы: