Heatiator GDST3831I Скачать руководство пользователя страница 22

Heatilator  •  GDST3831I  •  2127-900 Rev. L  •  3/13

22

Figure 6.3  Minimum Clearances for Termination

O

N

P

R

Q

X

= AIR SUPPLY INLET

V

= VENT TERMINAL

= AREA WHERE TERMINAL IS NOT PERMITTED

C

J

B

D

B

F

B

A

E

V

V

V

V

V

V

M

H or i

V

G

X

V

H

A

V

V

H

Electrical 

Service 

K

K

L

C

Q

MIN

R

MAX

1 cap

3 feet

 2 x Q 

ACTUAL

2 caps

6 feet

 1 x Q 

ACTUAL

3 caps

9 feet

2/3 x Q 

ACTUAL

4 caps

12 feet

1/2 x Q 

ACTUAL

Q

MIN

 = # termination caps x 3     R

MAX

 = (2 / # termination caps) x Q

ACTUAL

  

Covered Alcove Applications 

(Spaces open only on one side and with an overhang)

Measure horizontal clearances from this surface.

Measure vertical clearances from this surface.

CAUTION! Risk of Burns!  Termination caps are HOT, 

 

consider proximity to doors, traffi c areas or where people 
may 

pass or gather (sidewalk, deck, patio, etc.)

.  Listed cap 

shields available.  Contact your dealer.

•   Local codes or regulations may require different 

clearances.

•   Vent system termination is 

NOT

 permitted in screened 

porches.

•    Vent system termination is permitted in porch areas with 

two or more sides open. 

•    Hearth & Home Technologies assumes no responsibility 

for the improper performance of the appliance when the 
venting system does not meet these requirements.

•    Vinyl protection kits are suggested for use with vinyl siding.

=   6 inches................. clearance from sides of electrical 

service

L = 

12 

inches................ 

clearance above electrical service

Location of the vent termination must not interfere with access to the 
electrical service.

A  

=  12 inches.................clearances above grade, veranda, 

porch, deck or balcony

B = 

 

12 inches.................clearance to window or door that may 

be opened, or to permanently closed 
window

  

C = 

18 inches.................clearance below unventilated soffi t

 

 

18 inches.................clearance below ventilated soffi t

 

    30 inches .................clearance below vinyl soffits and 

electrical service 

=  6 inches...................clearance to outside corner

=  6 inches...................clearance to inside corner

=  3 ft. (Canada) ..........not to be installed above a gas me-

ter/regulator assembly within 3 feet 
horizontally from the center-line of the 
regulator

G = 

ft 

...........................clearance to gas service regulator 

vent outlet

=   9 inches   (U.S.A)

 

 

12 inches (Canada). clearance to non-mechanical (unpow-

ered) air supply inlet, combustion air 
inlet or direct-vent termination

=  3 ft. (U.S.A.)

 

 

6 ft. (Canada) ...........clearance to a mechanical (powered) 

air supply inlet

All mechanical air intakes within 10 feet of a termination cap 

must be a minimum of 3 feet below termination.
J = 

ft. 

......................... 

On 

public

 property:  clearance above 

paved sidewalk or a paved driveway.

A vent shall not terminate directly above a sidewalk or paved 

driveway which is located between two single family dwellings 
and serves both dwellings.

M   =  18 inches ....................clearance under veranda, porch, deck, 

balcony or overhang

 

 

42 inches ................vinyl or composite overhang

Permitted when veranda, porch, deck or balcony is fully open 

on a minimum of 2 sides beneath the fl oor.

=  6 inches ........... non-vinyl sidewalls

 

  

12 inches ......... vinyl sidewalls

O = 

18 inches ......... non-vinyl soffi t and overhang

 

  

42 inches ......... vinyl soffi t and overhang

P = 

ft.

Содержание GDST3831I

Страница 1: ... the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional Leave this manual with party responsible for use and operation DO NOT DISCARD WARNING Important operating and maintenance instructions included Read underst...

Страница 2: ...Type of Gas Model Number Not Not for for use use with with solid solid fuel fuel Ne Ne doit doit pas pas entre entre utilise utilise avec avec un un combustible combustible solide solide This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes codes if if any any if if not not follow follow ANSI ANSI Z223 1 Z223 1 in in the the USA U...

Страница 3: ...s Qualified Service Technician 14 Installer Guide 4 Getting Started A Typical Appliance System 16 B Design and Installation Considerations 17 C Tools and Supplies Needed 17 D Inspect Appliance and Components 17 5 Framing and Clearances A Selecting Appliance Location 18 B Constructing the Appliance Chase 19 C Clearances 19 D Mantel and Wall Projections 20 6 Termination Locations A Vent Termination ...

Страница 4: ...ll Projections 45 B Facing Material 45 C Splatter Guard 46 14 Appliance Setup A Remove Fixed Glass Assembly 48 B Remove the Shipping Materials 48 C Clean the Appliance 48 D Accessories 48 E Lava Rock Mystic Embers and Glowing Ember Placement 48 F Install the Log Assembly 49 G Fixed Glass Assembly 51 H Install Trim Kits and Surrounds 51 I Air Shutter Setting 51 15 Troubleshooting A Intellifire Igni...

Страница 5: ...hase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warranty per...

Страница 6: ...IED ABOVE WARRANTY EXCLUSIONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melted items or other exter...

Страница 7: ...ssed pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electri...

Страница 8: ...ating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installed in accord...

Страница 9: ...ontact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one HOT SURFACES Glass and other surfaces are hot during operation AND cool down Hot glass will cause burns DO NOT touch glass until it is cooled NEVER allow children to touch glass Keep children away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to ...

Страница 10: ... not present or help is needed to properly install one For more information refer to the instructions supplied with your decorative door or front G Remote Controls Wall Controls and Wall Switches Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote controls o...

Страница 11: ...r because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT LINE VOLT AGE 110 120 VAC OR 220 240 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Re fer to the owne...

Страница 12: ...n will disappear Blue flames This is a result of normal operation and the flames will begin to yellow as the fireplace is al lowed to burn for 20 to 40 minutes Odor from fireplace When first operated this fireplace may release an odor for the first several hours This is caused by the curing of materials from manufacturing Odor may also be released from finishing materials and adhesives used near t...

Страница 13: ...red due to lint from carpeting or other factors Control compartment burner and circulating air passageway of the fireplace must be kept clean CAUTION Risk of Burns The fireplace should be turned off and cooled before servicing When properly maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds Front...

Страница 14: ...re is no damage to glass or glass frame Replace as necessary Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged Replace as necessary Logs Frequency Annually By Qualified Service Technician Tools needed Protective gloves Inspectfordamagedormissinglogs Replaceasnecessary Refer to Section 14 for log placement instructions Verify correct log plac...

Страница 15: ...ttery failure or leaking Check for smooth lighting and ignition carryover to all ports Verify that there is no ignition delay Inspect for lifting or other flame problems Verify air shutter setting is correct See Section 14 for required air shutter setting Verify air shutter is clear of dust and debris Inspect orifice for soot dirt and corrosion Verify orifice size is correct See Service Parts List...

Страница 16: ...TOP ON FLOOR OF ATTIC SECTION 8 C VERTICAL TERMINATION CAP SECTION 10 C VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8 C FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 C MANTEL AND MANTEL LEG SECTION 5 D VENT PIPE SECTION 8 and 10 STORM COLLAR SECTION 10 C NON COMBUSTIBLE ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE SECTION 10 C FRAMING...

Страница 17: ...ged parts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Non corrosive leak check solution Hammer Phillips screwdriver Gloves Framing square Voltmeter Electric drill and bi...

Страница 18: ...ings and for service access Due to high temperatures the appliance should be locat ed out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference Figure 5 1 Appliance Locations 36 in 914 mm 36 in 914 mm GDST3831I...

Страница 19: ...extending full width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secured to prevent accidental contact The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making co...

Страница 20: ...Non Combustible Zone Figure 5 5 Combustible Mantel Leg or Wall Projections Acceptable on both sides of opening SHEETROCK AIR SPACE REQUIRED 3 5 in 5 6 7 8 9 10 3 4 5 12 11 10 9 8 7 6 TOP OF HOOD OR FIREPLACE OPENING MIN MAX 4 12 13 11 32 CEILING TOP VIEW 3 1 4 in Min 1 2 in Min Unlimited FIREPLACE OPENING Figure 5 3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles Figure 5 4 Mini...

Страница 21: ...IN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overheating and fire WARNING Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If using decorative cap co...

Страница 22: ...e vent termination must not interfere with access to the electrical service A 12 inches clearances above grade veranda porch deck or balcony B 12 inches clearance to window or door that may be opened or to permanently closed window C 18 inches clearance below unventilated soffit 18 inches clearance below ventilated soffit 30 inches clearance below vinyl soffits and electrical service D 6 inches cl...

Страница 23: ... of install the elbow heat shield may be screwed to the exhaust pipe see Figure 6 6 Cut the tabs as shown and bend down Secure the heat shield to the pipe maintain ing 3 inch to 4 inch between the pipe and shield Refer to Cinch Pipe and Termination Cap installation in structions Continue adding vent components locking each suc ceeding component into place Ensure that each succeeding vent component...

Страница 24: ...ween two 45º elbows see Figure 7 1 Figure 7 1 7 7 Vent Information and Diagrams B Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams D Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the effective length of pipe see Figure 7 2 Horizontal terminati...

Страница 25: ...required at each change in venting direction and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 7 3 requires only enough sup port to maintain the necessary clearance to combustibles However the vent attachment point and the firestop loca tion are considered to be supports 1 in CLEARANCE FLEX VENT 3 in CLEARANCE TERM...

Страница 26: ... may be level F Vent Diagrams H1 V1 Figure 7 4 One Elbow 1 Top Vent Horizontal Termination V1 Minimum H1 Maximum 90 Elbow 2 ft 610 mm 1 2 ft 152 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 Max 14 ft 4 3 m V H Max 40 ft 12 2 m See Warning WARNING Note There MUST be a 25 reduction in total H when using flex vent except...

Страница 27: ...V1 Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 7 3 WARNING Fire Risk When using SLP HRC SS and SLP HRC ZC SS termination caps on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow When using DVP TB1 termination cap on top vented fireplaces a three foot minimum...

Страница 28: ...See Warning Below Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 7 3 WARNING Fire Risk When using SLP HRC SS and SLP HRC ZC SS termination caps on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow When using DVP TB1 termination cap on top vented fireplaces a thr...

Страница 29: ...eight If the vent configuration has a total vertical of 15 50 feet an exhaust restrictor may be needed The exhaust restrictor can be located in the appliance manual bag Exhaust restrictor Instructions 1 Center the exhaust restrictor in the open end of the ex haust outlet and secure through the slots on the exhaust restrictor with the 2 1 4 in self tapping screws provided in the appliance manual ba...

Страница 30: ...t 1 4 m 15 ft 4 6 m H Max 15 ft 4 6 m No specific restrictions on this value EXCEPT V1 V2 H1 cannot exceed 40 ft 12 2 m V1 Minimum H1 H2 Maximum V2 V1 V2 Min 90 Elbow 1 2 ft 152 mm 1 2 ft 152 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m H1 H2 MAX 14 ft 4 6 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 canno...

Страница 31: ...earance at wall shield firestops 1 in 25 mm clearance bottom and sides Heat Shields Wall Shield Firestop WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections Figure 6 1 Horizontal venting clearances to combustible materials B Wall Penetration Framing Combustible Wall Penetration Whenever a combustible wall is penetrated you must frame a hole for the wall shield firestop The ...

Страница 32: ...installed with a attic insulation shield It must be under joists between floors that are not insulated Refer to Figure 8 4 Secure with three fasteners on each side WARNING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating Figure 8 3 Installing Ceiling Firestop Figure 8 4 Installing the Attic Shield 3 FASTENERS PER SIDE INSTALL AT...

Страница 33: ...o maintain air space clearance Figure 8 5 Attic Insulation Shield Vaulted Ceiling Installation The attic insulation shield has been laser etched with cut lines and ceiling pitches to make field trimming easier Remove one shield from box NOTICE Cut previously installed batt insulation to make room for the attic insulation shield Cut the attic insulation shield if application is for vaulted ceiling ...

Страница 34: ...tion making sure to maintain proper clearance to combustibles 3 Level the appliance from side to side and front to back It is acceptable to use wood shims under the appliance 4 Fasten the appliance to the floor using the pilot holes located at the bottom of the appliance 5 Bend out nailing tabs on each side making sure to keep the nailing tabs flush with the framing 6 Using a framing square make s...

Страница 35: ... preceding component Commercial Multi family Multi level exceeding two sto ries or High Rise Applications For Installation into a commercial multi family multi level exceeding two stories or high rise applications All outer pipe joints must be sealed with high temperature silicone including the slip section that connects directly to the hori zontal termination cap Apply a bead of silicone sealant ...

Страница 36: ...ealing the inner flue is not required All unit collar pipe slip section elbow and cap outer flues shall be sealed Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pilot holes in the slip section See Figure 10 4 Figure 10 5 Securing Vertical Pipe Sections Figure 10 6 Securing Horizo...

Страница 37: ...ews A decorative cathedral ceiling support box can be installed on a cathedral ceiling through which the vent passes Use a plumb bob to mark the center line of the venting system on the ceiling and drill a small hole through the ceiling and roof at this point Locate the hole and mark the outline of the cathedral ceiling support box on the outside roof Remove shingles or other roof covering as nece...

Страница 38: ...ts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation Sheet metal edges are sharp Connect both halves of the storm collar with two screws see Figure 10 13 Wrap the storm collar around the exposed pipe section closest to the roof and align brackets Insert a bolt provided through the brackets and tighten the nut to complete the storm collar assembly Make sure t...

Страница 39: ...WARNING Risk of Fire To prevent overheating and fire heat shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10 17 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other ...

Страница 40: ...iate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 6 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures...

Страница 41: ... DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire Explosion High pressure will damage valve Low pressure may cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are operating Install regulato...

Страница 42: ...tched circuit Incorrect wiring will override IPI safety lockout Refer to Figure 12 2 Intellifire Pilot Ignition IPI Wiring Diagram This appliance is equipped with an Intellifire control valve which operates on a 3 volt system Plug the 3 volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries not included into the battery pack before use NOTIC...

Страница 43: ...gnition Wiring Diagram with Wall Switch or Thermostat TRANSFORMER 3 VAC PLUG IN PLUG IN BLACK RED BATTERY PACK REMOTE WIRES TO BROWN ORANGE GREEN VALVE GROUND TO FIREPLACE CHASSIS HOT NEUTRAL WHITE ORANGE IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR I S Figure 12 2 Intellifire Ignition Wiring Diagram with Remote Receiver NOTE 1 Ignition module valve pilot and wall switch operate on 3 volts 110...

Страница 44: ...UPPLY WIRES WHITE RED BLACK GREEN WHITE MINIMUM 14 3 AWG WITH GROUND JUNCTION BOX KNOCKOUT Figure 12 5 Junction Box Wired to Wall Switch or BC10 ROMEX CONNECTORS Figure 12 4 Junction Box Detail NOTICE DO NOT wire 110 120 VAC to wall switch E Junction Box Installation The junction box must be wired from the INSIDE of the appliance Determine which side of the appliance the junction box is located on...

Страница 45: ...plying combustible materials Seal joints between the finished wall and appliance top and sides using a 300 F minimum sealant Refer to Figure 13 3 WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum clearances to combustibles as specified in this manual Overlapping materials could ignite and will interfere with proper operation of doors and ...

Страница 46: ...Step 3 Crease flaps on left and right sides of splatter guard using the scored line as the guide See Figure 13 6 Step 4 Center the splatter guard in front of the unit as shown in Figure 13 8 Place the splatter guard in the unit by guiding the top flap into proper position and then con tinuing to guide the tabs on the side flaps into the top slot on the left and right sides of the appliance The top...

Страница 47: ...ght bottom of splatter guard and fit them into the square holes The tabs are now inside the front of the splatter guard carefully bend them down See Figure 13 12 To Close the Lower Access Panel Carefully disengage the tabs from the square holes and bend the access panel to its original position Bend the center bottom flap and insert it into the bottom of the ap pliance To Remove the Splatter Guard...

Страница 48: ...ember material annually Improperly placed embers interfere with proper burner operation Placing the Ember Material Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trail of ports from back to front When placing Glowing Embers onto the burner care should be taken so that the ports...

Страница 49: ...of the appliance verify that the pilot is on the left side See Figure 2 Log Set Assembly LOGS 2126 Models ST 550T IPI GDST3831I STEP 2 Log 1 SRV2126 700 Place Log 1 so that the large cutout on the bottom of the log fits over the pilot shield as shown in Figure 4 The hole in the bottom of Log 1 interlocks with the head of the shoulder screw on the burner 1 1 3 3 2 2 PILOT PILOT 1 1 2 2 STEP 3 Log 2...

Страница 50: ...P 5 Log 3 SRV2126 702 Place the remaining Log 3 2 of 2 identical logs into the fireplace so that the bot tom of the log rests in the notch on the ledge on the front side of the basepan Then place the top of Log 3 on top of Log 1 so that the flat spot is hidden The complete log set assembly is shown in Figure 11 See the fireplace Owner s Manual for instructions on how to place the Mystic Embers and...

Страница 51: ...for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a complete assembly Air Shutter Settings H Install Trim Kits and Surrounds Install optional trim kits and or surrounds using the instructions included with the accessory Use non combustible materials to cover the gap between the sheet rock and the app...

Страница 52: ...ed sparker wire or cracked insulator around electrode Replace pilot if necessary 2 Pilot won t light there is no noise or spark a No power or transformer installed incorrectly Verify that transformer is installed and plugged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 a...

Страница 53: ...rifice is installed and gas inlet is set to pressure specifications Polish flame sensing rod with fine steel wool to remove any contaminants that may have accumulated on flame sensing rod c Module is not grounded Verify module is securely grounded to metal chassis of appliance Verify that wire harness is firmly connected to the module d Damaged pilot assembly or contami nated flame sensing rod Ver...

Страница 54: ...ensions and clearances refer to Section 5 Figure 16 1 See Through Dimensions Location Inches Millimeters H 4 1 4 108 I 1 1 2 38 J 8 203 K 8 3 4 222 L 34 1 2 876 M 16 406 N 31 1 4 794 Location Inches Millimeters A 31 1 8 791 B 37 5 8 956 C 21 533 D 30 1 4 768 E 1 25 F 2 1 8 54 G 4 1 8 105 B C FRONT VIEW RIGHT VIEW ELECTRICAL ACCESS GAS LINE ACCESS LEFT VIEW A J K D F G H N i L M E ...

Страница 55: ...op SLP WS Wall Shield Firestop 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 11 16 in 220 mm 1 1 2 in 38 mm 12 in 305 mm 12 in 305 mm 5 1 2 in 146 mm B Vent Components Diagrams EFFECTIVE HEIGHT LENGTH Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 152 SLP12A 2 12 51 305 SLP FLEX 2 24 610 SLP FLEX ...

Страница 56: ...o 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 203 mm 12 in 305 mm Max Effective Length 14 7 ...

Страница 57: ...34 mm 10 9 16 in 269 mm 14 in 356 mm SLP FLEX TRAP Horizontal Termination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap DVP FBHT Horizontal Termination Cap 13 1 2 in 343 mm 28 1 2 in 724 mm 10 11 16 in 271mm Figure 16 4 SLP Series Vent Components B Vent Components...

Страница 58: ... 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm SLP HRC SS SLP HRC ZC SS HORIZONTAL TERMINATION CAP DVP TB1 HORIZONTAL TERMINATION CAP When using DVP TB1 termination cap on top vented fireplaces a three foot minimum vertical ventsectionisrequired before installing first elbow SLP90 SL...

Страница 59: ...e Harness PVI WH100 PVI SLP Power Vent Inline Note Wire harnesses required to power the PVI SLP connect to the appliance and are ordered separately from PVI SLP Contact your dealer to order 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm 12 1 2 IN 318 mm 20 3 4 IN 527 mm 13 5 8 IN 346 mm EFFECTIVE LENGTH 32 IN 813 m...

Страница 60: ...ked at Depot ITEM DESCRIPTION COMMENTS PART NUMBER Log Set Assembly LOGS 2126 Y 1 Log 1 SRV2126 700 2 Log 2 SRV2126 701 3 Log 3 Qty 2 req SRV2126 702 4 Sheetrock Ledge 2126 118 5 Refractory Qty 2 req 2127 017 6 Burner NG LP 2126 007 Y 7 Base Pan 2126 115 8 Glass Door Assembly GLA 550TR Y 9 Valve Assembly Refer to valve page 10 Junction Box 4021 013 Y 11 Junction Box Bracket 2128 128 12 Pilot Shiel...

Страница 61: ...PTION COMMENTS PART NUMBER 9 1 Battery Pack 593 594A Y 9 2 3 Volt Transformer 593 593A Y 9 3 Module Wire Assembly 593 590A Y 9 4 Module 593 592 Y 9 5 Valve Bracket 2118 104 9 6 Valve NG 750 500 Y Valve LP 593 501 Y 9 7 Flex Ball Valve Assembly 302 320A Y 9 8 Flexible Gas Connector 530 302A Y 9 9 Orifice NG 44C 582 844 Y Orifice LP 55C 582 855 Y 9 10 3 hole Grommet 2118 420 9 11 Pilot Assembly NG 2...

Страница 62: ... at Depot ITEM DESCRIPTION COMMENTS PART NUMBER Exhaust Restrictor 530 299 Fiberglass Rope Ring 045 455 Gasket Assembly 2128 081 Contains Vent Seal Cap Burner Neck Shutter Bracket and Valve Plate Gaskets Glass Latch Assembly Pkg of 2 33858 2 Y Lava Rock 2005 790 Mineral Wool 050 721 Thermostat Wire 2118 170 Y Surround Overlay contains overlay for top bottom and sides SRV2126 FACE Touch Up Paint TU...

Страница 63: ..._____________ ________________________________________________________________________________ Printed in U S A Copyright 2013 DO NOT DISCARD THIS MANUAL NOTICE Leave this manual with party responsible for use and operation Important operating and maintenance instructions included Read understand and follow these instructions for safe installation and operation Heatilator a brand of Hearth Home Te...

Отзывы: