HeatFab Saf-T Vent CI Plus Скачать руководство пользователя страница 3

Figure 5

Guy Support

Guy Support,
Preferred Option

Guy Support,
Option Two

Guy Line

Stack Above 6'

Guy Line

Roof

APPLICATION 2. 

Support Above a Roof (Figure 5).

Required if stack extends more than 6' above the roof.

Note

: When using a guy support above a roof, the stack below the roof must be supported.

Install the guy support between the last 2 sections of straight vent.  Attach guy wires or chains, with a
minimum rated capacity of 500 lbs. to the four hole locations on the guy brackets.  Anchor the guy lines
to the top of the chase or other structure utilizing best construction methods to stabilize the system.

Preferred Option

: Install the Guy Support above the Boot Tee (preferred).

Option Two

: Install the Guy Support below the Boot Tee.