20
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
Modbus Register Mapping
TO READ/WRITE PARAMETERS OVER EXTERNAL MODBUS (cont.)
Field Name
Data Address
Type
Quantity of Registers
Decoding Method
RO/RW?
Defrost 11 Schedule
0x402A
Integer
1
Same as Defrost 1
schedule
RW*
Defrost 12 Schedule
0x402B
Integer
1
Same as Defrost 1
schedule
RW*
Defrost Failsafe Time
0x402C
Integer
1
Unit – Minutes
RW
Defrost End Temperature
0x402D
Integer
1
Real number multiplied
by 10
RW
Refreeze Time Safety
0x402E
Integer
1
Unit – Minutes
RW*
Refreeze Suction Setpoint
0x402F
Signed Integer
1
Real number multiplied
by 10
Alarm High Box Temperature
0x4030
Signed Integer
1
Real number multiplied
by 10
RW
Alarm Low Box Temperature
0x4031
Signed Integer
1
Real number multiplied
by 10
RW
Alarm Delay Time
0x4032
Integer
1
Unit – Minutes
RW
Alarm Door Open Time
0x4033
Integer
1
Unit – Minutes
RW
Country
0x4034
Integer
1
USA-0
CANADA-1
RW
Time Zone
0x4035
Integer
1
MST-0, NST-1, AST-2,
EST-3, CST-4, MST-5,
PST-6, AKST-7, HAST-
8, SST-9, CHST-10,
WAKT-11
RW*
UTC Offset
0x4036
Signed Integer
1
Real number multiplied
by 10
RW*
Follow DST
0x4037
Integer
1
1 – YES, 0 – NO
RW
12/24 Hour Clock
0x4038
Integer
1
0 – 12, 1 – 24
RW
Number of Units
0x403A
Integer
1
RO
Controller Address
0x403B
Integer
1
RO
Box Temperature
0x403C
Signed Integer
1
Real number multiplied
by 10
RO (Box temp thermis-
tor value of the iRC iIC
is attached with)