11
Please keep these instructions for future reference.
Equipment assembly and Wiring is required before using this Guide.
For assembly please consult Intelligen Assebly and Wiring Guide.
PRIOR ASSEMBLY NEEDED
IMPORTANT!
This Quick Start Guide is
only for Intelligen Series XXKSJFS Model.
IMPORTANT!
Since product improvement is a continuing effort, we reserve the
right to make changes in specifications without notice.
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
US. Customer Service
Normal Business Hours – 8:00 AM – 8:00 PM EDT
(800) 321-1881
After Hours (after 5:00 PM EDT, weekends and holidays)
(877) 482-7238
heatcraft.com/intelligen/support
Canada Customer Service
QUICK START GUIDE
INTELLIGEN 00049DFS
MARCH 2018*
*REPLACES JANUARY 2018
PART NO. 099483
S.No
Property Name
Property ID
Type
Read/Write
Decoding:
1
Date/Time
513
BACnet date-time
Read
Time in UTC,
Byte 1 – Year MSB,
Byte 2 – Year LSB,
Byte 3 – Month,
Byte 4 – Day,
Byte 5 – Hour,
Byte 6 – Minutes,
Byte 7 – Seconds,
Byte 8 – Week Day
2
Defrost Type
514
Integer
Read
AIR -0,
Medium Temp
Electric – 1,
Low Temp Electric - 2
3
Defrost Style
515
Integer
Read
TIMED -0,
SMART – 1,
DEMAND - 2
4
Refrigerant
516
Integer
Read
R404A - 0, R507A - 1,
R407A - 2, R407C - 3,
R407F - 4, R22 - 5,
R448A - 6, R449A - 7
5
Box Temperature Setpoint
517
Real
RW
When reading, divide
read number by 10;
Example: Byte 1 –
0x01 Byte 2 – 0x5E >
To be read as 35.0 F
When writing,
multiply desired
setpoint by 10;
Example- to set
box temp set-point
to 20.0F, Write
0x00C8. Box Temp
Setpoint must be
in whole number
increments, non-
whole number inputs
will be rounded to the
nearest ones place.
6
Box Temperature Setpoint
Differential
518
Integer
Read
Real number divided
by 10
7
Box Load Mode Time Delay
519
Integer
Read
Unit - Minutes
8
Low Superheat Setpoint
521
Real
Read
Real number divided
by 10
9
Box Load Mode Maximum
Override Time
520
Integer
Read
Unit - Minutes
10
Minimum Runtime
522
Integer
Read
Unit – Minutes
11
Minimum Off Time
523
Integer
Read
Unit – Minutes
12
Temperature Units
524
Integer
Read
CELSIUS – 1,
FAHRENHEIT - 0
13
Pressure Units
525
Integer
Read
PSIG – 0,
KPA -1,
BAR – 2
BACnet Mapping – “Global Settings Object Type”
OBJECT ID – 129