background image

13

NOTE: All adjustable controls and valves must be field 

adjusted to meet desired operation. There are no 

factory preset controls or valve adjustments.

System Balancing - Compressor Superheat 

 

   

IMPORTANT:  In order to obtain the maximum capacity     

                             from a system, and to ensure trouble- 

                             free operation, it is necessary to balance  

                             each and every system.

This is extremely important with any refrigeration system.
The critical value which must be checked is suction superheat.
Suction superheat should be checked 

at the compressor

  

as follows: 

 

 

1.  Measure the suction pressure at the suction service  

 

 

valve of the compressor and determine the saturation 

  

 

temperature corresponding to this pressure from a  

 

 

“Temperature-Pressure” chart. 

 

 

2.  Measure the suction temperature of the suction line 

  

 

about one foot back from the compressor using an    

 

 

 accurate thermometer. 

 

 

3.  Subtract the saturated temperature from the actual  

 

 

suction line temperature. The difference is superheat.

Too low a suction superheat can result in liquid being returned 

to the compressor. This will cause dilution of the oil and 

eventual failure of the bearings and rings or in the extreme 

case, valve failure.
Too high a suction superheat will result in excessive discharge 

temperatures which cause a break down of the oil and results 

in piston ring wear, piston and cylinder wall damage. 
It should also be remembered that the system capacity 

decreases as the suction superheat increases. For maximum 

system capacity, suction superheat should be kept as low as 

is practical. Copeland mandates a 

minimum

 superheat of 

20˚F 

at the compressor

Heatcraft Refrigeration Products

 

recommends that the superheat 

at the compressor

 be 

between 30˚F and 45˚F.
If adjustments to the suction superheat need to be made,  

the expansion valve at the evaporator should be adjusted.

Operational Check Out 

 

After the system has been charged and has operated for at 

least two hours at normal operating conditions without any 

indication of malfunction, it should be allowed to operate 

overnight on automatic controls. Then a thorough recheck of the 

entire system operation should be made as follows: 

 

(a)  Check compressor discharge and suction pressures. 

    

If not within system design limits, determine why and 

 

 

 take corrective action. 

 

(b)  Check liquid line sight glass and expansion valve  

 

 

operation. If there are indications that more refrigerant  

 

 

is required, leak test all connections and system  

 

 

components and repair any leaks before adding  

 

 

refrigerant.  

 

(c)  Thermostatic expansion valves must be checked for  

 

 

proper superheat settings. Feeler bulbs must be in 

 

 

positive contact with the suction line and should be  

 

 

insulated. Valves set at high superheat will lower  

 

 

refrigeration capacity. Low superheat promotes liquid  

 

 

slugging and compressor bearing washout. 

 

(d)  Using suitable instruments, carefully check line voltage  

 

 

and amperage at the compressor terminals. Voltage  

 

 

must be within 10% of that indicated on the    

 

 

 

condensing unit nameplate. If high or low voltage is    

 

 

indicated, notify the power company. If amperage draw  

 

 

is excessive, immediately determine the cause and  

 

 

take corrective action. On three phase motor   

 

 

compressors, check to see that a balanced load is  

 

 

 

drawn by each phase.  

 

(e)  The maximum approved settings for high pressure  

 

 

controls on Heatcraft air cooled condensing equipment  

 

 

is 400 psig. On air cooled systems, check as follows:    

 

 

Disconnect the fan motors or block the condenser  

 

 

inlet air. Watch high pressure gauge for cutout point.   

 

 

Recheck all safety and operating controls for proper    

 

 

operation and adjust if necessary.  

 

(f)  Check winter head pressure controls for pressure  

 

 

setting.

 

(g)  Check crankcase heater operation if used. 

 

(h)  Install instruction card and control system diagram for   

 

 

use of building manager or owner.

Содержание H-IM-FL1A

Страница 1: ...riers Sight Glasses 5 Refrigerant Oils 6 Phase Loss Monitor 7 Recommended Refrigerant Piping Practices 7 Refrigeration Pipe Supports 7 Suction Lines 8 Suction Line Risers 8 Liquid Lines 8 Evacuation and Leak Detection 11 Refrigerant Charging Instructions 12 Field Wiring 12 Check Out and Start Up 12 Operational Check Out 13 System Balancing Compressor Superheat 13 System Troubleshooting Guide 14 Pr...

Страница 2: ...turerʼs recommendations or if the serial number has been altered defaced or removed MOTOR COMPRESSORS Motor compressors furnished by SELLER are subject to the standard warranty terms set forth above except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer not at SELLERʼs factory and no freight shall be allow...

Страница 3: ...d Location Requirements for Air Cooled Condensing Units and Remote Condensers Units in Pits The top of the unit should be level with the top of the pit and side distance increased to 2W If the top of the unit is not level with the top of pit discharge cones or stacks must be used to raise discharge air to the top of the pit This is a minimum requirement Decorative Fences Fences must have 50 free a...

Страница 4: ...ess Provide adequate space at the compressor end of the unit for servicing Provide adequate space on the connection side to permit service of components Spring Mounted Compressor Compressors are secured rigidly to make sure there is no transit damage Before operating the unit it is necessary to follow these steps a Remove the upper nuts and washers b Discard the shipping spacers c Install the neop...

Страница 5: ... drier The sight glass is designed to give a visual indication of moisture content in the system Generally it requires no field service However in cases of extreme acid formation in a system after a compressor burnout the acid may damage the sensing element or etch the glass This would require that the sight glass be replaced along with the liquid line drier after any compressor motor burnout CAUTI...

Страница 6: ...introduction of the Polyol ester lubricants Table 3 below summarizes which oils lubricants are approved for use in Copeland compressors Polyol Ester Lubricants Hygroscopicity Ester lubricants POE have the characteristic of quickly absorbing moisture from the ambient surroundings This is shown graphically in Figure 3 where it can be seen that such lubricants absorb moisture faster and in greater qu...

Страница 7: ... the base of each suction riser of four 4 feet or more to enhance oil return to the compressor e For desired method of superheat measurement a pressure tap should be installed in each evaporator suction line in the proximity of the expansion valve bulb f When brazing refrigerant lines an inert gas should be passed through the line at low pressure to prevent scaling and oxidation inside the tubing ...

Страница 8: ...superheat at the compressor Figure 6 Suction P Traps Slope 1 4 per 10 ft toward compressor Suction Lines NOTE If the suction line must rise to a point higher than the suction connection on the evaporator a suction line trap at the outlet of the evaporator must be provided Horizontal suction lines should slope away from the evaporator toward the compressor at the rate of 1 4 inch per 10 feet for go...

Страница 9: ...Tee Straight Through 1 2 2 3 4 4 5 7 8 10 12 14 16 Table 4 Pressure Loss of Liquid Refrigerants in Liquid Line Risers Expressed in Pressure Drop PSIG and Subcooling Loss F Liquid Line Rise in Feet 10ʼ 15ʼ 20ʼ 25ʼ 30ʼ 40ʼ 50ʼ 75ʼ 100ʼ Refrigerant PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F R22 4 8 1 6 7 3 2 3 9 7 3 1 12 1 3 8 14 5 4 7 19 4 6 2 24 2 8 0 36 3 12 1 48 4 16 5 R134a 4...

Страница 10: ... 1 3 27 26 39 63 86 1 24 134a 64 2 2 57 14 26 40 61 1 91 1 3 8 22 63 5 3 50 27 42 64 93 1 33 R507 404A 55 0 4 98 40 58 95 1 32 1 87 134a 90 9 3 65 20 37 57 87 1 30 1 5 8 22 90 0 4 96 37 59 90 1 33 1 88 R507 404A 78 0 7 07 56 82 1 35 1 86 2 64 134a 158 6 34 34 64 98 1 51 2 24 2 1 8 22 156 8 61 65 1 03 1 57 2 30 3 26 R507 404A 134 12 25 98 1 43 2 35 3 23 4 58 134a 244 9 78 52 99 1 51 2 32 3 47 2 5 8...

Страница 11: ...CFCʼs There is a view that even small quantities of chlorine may act as a catalyst encouraging copper plating and or corrosion and should therefore be avoided WARNING HFC 134a has been shown to be combus tible at pressure as low as 5 5 psig at 350 F when mixed with air at concen trations more than 60 air by volume At lower temperature higher pressures are required to support combustion Therefore a...

Страница 12: ...ng until system has sufficient refrigerant for proper operation Do not overcharge Remember that bubbles in a sight glass may be caused by a restriction as well as a shortage of refrigerant i Do not leave unit unattended until the system has reached normal operating conditions and the oil charge has been properly adjusted to maintain the oil level at the center of the sight glass CAUTION Extreme car...

Страница 13: ...ve at the evaporator should be adjusted Operational Check Out After the system has been charged and has operated for at least two hours at normal operating conditions without any indication of malfunction it should be allowed to operate overnight on automatic controls Then a thorough recheck of the entire system operation should be made as follows a Check compressor discharge and suction pressures...

Страница 14: ... system 3 Check for leaks Repair and add charge 4 Low suction pressure 4 See corrective steps for low suction pressure 5 Variable head pressure valve 5 Check valve setting High suction pressure 1 Excessive load 1 Reduce load or add additional equipment 2 Expansion valve overfeeding 2 Check remote bulb Regulate superheat Low suction pressure 1 Lack of refrigerant 1 Check for leaks Repair and add ch...

Страница 15: ... and components Verify that all electrical and ground connections are secure tighten as required Check condition of compressor and heater contactors Look for discoloration and pitting Replace as required Check operation and calibration of all timers relays pressure controls and safety controls Clean electrical cabinet Look for signs of moisture dirt debris insects and wildlife Take corrective acti...

Страница 16: ...ATE MODULE R1 R4 RELAYS TD7 8 START TIMER FIELD WIRING FACTORY WIRING CB1 CB7 CIRCUIT BREAKERS F1 FUSE CLASS CC CCH CRANKCASE HEATERS C1 C4 COMPRESSOR CONTACTORS C1A1 C4A1 C1 C4 AUXILIARY CONTACTS C5 C12 CONDENSER FAN CONTACTORS FCT FAN CYCLE TEMP CONTROL LSV LIQUID LINE SOLENOID VALVE HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH LEGEND w 30 MIN TIME DELAY 25 A M1 M3 C5 25 A C6 25 A M5 M7 C7 2...

Страница 17: ...TE MODULE R1 R4 RELAYS TD7 8 START TIMER FIELD WIRING FACTORY WIRING CB1 CB7 CIRCUIT BREAKERS F1 FUSE CLASS CC CCH CRANKCASE HEATERS C1 C4 COMPRESSOR CONTACTORS C1A1 C4A1 C1 C4 AUXILIARY CONTACTS C5 C12 CONDENSER FAN CONTACTORS FCT FAN CYCLE TEMP CONTROL LSV LIQUID LINE SOLENOID VALVE HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH LEGEND w 30 MIN TIME DELAY 25 A M1 M3 C5 25 A C6 25 A M5 M7 C7 25...

Страница 18: ...18 Control Circuit Wiring Diagram for BACU51 and BACU59 ...

Страница 19: ...19 Submittal ...

Страница 20: ...20 Submittal ...

Страница 21: ...t Serial ________________________________________ Compressor Model ____________________ Compressor Model _________________ Compressor Serial ____________________ Compressor Serial __________________ Electrical _________________ Volts __________________ Phase _______ Voltage at Compressor L1__________ L2 ___________ L3 ___________ Amperage at Compressor L1__________ L2 ___________ L3 ___________ Se...

Страница 22: ...22 Notes ...

Страница 23: ...23 Notes ...

Страница 24: ...PLACE BOULEVARD STONE MOUNTAIN GA 30087 USA 770 465 5600 FAX 770 465 5990 WWW HEATCRAFTRPD COM Since product improvement is a continuing effort we reserve the right to make changes in specifications without notice Visit us online at www heatcraftrpd com ...

Отзывы: