Fireplace Size Requirements
A. Minimum Fireplace Opening
Minimum
¿
replace opening requirements are shown in
Figure 3.1.
• The
¿
rebrick (refractory), glass doors, screen rails,
screen mesh and log grates can be removed from a
factory built
¿
rebox in order to gain minimum gas insert
opening requirements.
• Any smoke shelves, shields and baf
À
es may be removed
from a factory built
¿
rebox if attached with mechanical
fasteners.
• The metal floor of the factory built firebox may be
removed to facilitate the installation of the insert only
when a 1/4 inch airspace is provided between the insert
and the
À
oor of outer wrap.
Figure 3.1 Fireplace Opening
NOTE: For actual appliance dimensions refer to Section 16.
20-3/8 in.
14-7/16 in.
29-1/8 in.
18-15/16 in.
GAS INLET
5-9/16 in.
1-1/16 in.
15 in.
Fire Risk
Provide adequate clearance:
• Around air openings
• To combustibles
• For service access
Locate appliance away from traf
¿
c areas.
WARNING
FB-ZC MINIMUM FIREPLACE SIZE
Location
Inches
Millimeters
A
Front Width
30-7/8
784
B
Rear Width
25-5/8
651
C
Depth
15
381
D
Height 19-1/2
495
* NOTE: If exhaust collar on insert and
¿
replace damper do not line up, add 4 inches (102 mm) to minimum
¿
replace height for bends in vent pipe.