16
MPC Platinum Installation and Operation Manual
HT# 059085-00
F
AUTO/BYPASS SWITCH
• The switch must be in the
AUTO
position for the MPC Platinum to control the heating
system.
• The
BYPASS
position overrides all automatic control of the MPC Platinum.
• If the MPC Platinum has power and is operational, switching to
BYPASS
automatically
activates the Motorized Valve, the Burner, and the System output.
• Switching the control to
BYPASS
manually during a power outage, activates the
Motorized Valve, Burner , and System outputs.
ALERT
Switching the MPC Platinum into Bypass overrides all automatic operation In
Bypass, the boiler will run constantly on its own limits or the valve will be fully open
MPC
Platinum
MADE IN U.S.A.
PREV.
(DEL)
SAFETY
GROUND
MUST BE
CONNECTED
OUT
TEMP
AUX
INPUT 0
AUX
TEMP 0
AUX
TEMP 1
MENU FUNCTIONS
SELECT enters menus or accepts changes
ADJUST selects menu items or changes settings
BACK returns to previous menu
DAY selects next day
PREV./NEXT steps through output status
DAY
HELP
NEXT
PRESS TO
SELECT
BACK
MON
12/01/2010 10:01Am
ADJUST
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
AUX
TEMP 2
DO NOT APPLY ANY VOLTAGE
TO SENSOR TERMINALS
A13
A14
A15
A16
A17
A18
NETWORK
PROVE
SHUTDOWN
SYSTEM
TEMP
BYPASS
ALL SENSORS MUST BE
GOLD SERIES SENSORS
INPUTS
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
T
T
T
Cycle On 13/15
Cutoff = 55
o
F Day
OD = 31
o
F SYS = 138
o
F
AUTO
T
T
C O R P O R A T I O N
R
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY
15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz
30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
SYSTEM
AUX
CLOCK
OPTION
1
OPTION
2
OPTION
3
BURNER
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
LINE
NEUTRAL
B
R
W
MOTORIZED
VALVE
OUTPUT
SYS
OPTION
3
OPTION
2
OPTION
1
AUX
CLOCK
SETTING THE CONTROL
DISPLAY AND CHANGING SETTINGS
The MPC Platinum comes with an 80 character (20 character per row x 4
rows) digital display with simple English menus.
ADJUST/SELECT
This knob turns to ADJUST and when pressed
it SELECTs. Turn the knob to scroll through
settings. Press a menu option to accept a setting,
BACK
Use to go back to the previous menu,
NEXT
In Schedules, goes to next schedule period,
DAY
In Schedules, advances through weekdays,
PREV.(DEL)
Clears a specific schedule setting.
HELP
Provides help instructions regarding the current
menu function.
PREV.
(DEL)
DAY
HELP
NEXT
PRESS TO
SELECT
BACK
ADJUST
MON
12/01/2010 10:01Am
Cycle On 13/15
Cutoff = 55
o
F Day
OD = 31
o
F
SYS = 138
o
F
Depress the knob to move
forward through the menus and to
accept changes. To change a
setting's value, rotate the knob.
Depress the button to go back
through the menus, or to view a
setting value without changing it
Digital display shows the date, heating
status, and cutoff, outdoor, and system
values. To view and adjust settings,
press the Adjust/Select button.
Date and Time
Messages
Cutoff and Schedule
Sensor Status
MENU TYPES
When powering up the MPC Platinum for the first time, it will take you through an 70
second count down followed by the System Startup Settings then another 10 second boot
setup and finally end with the default screen. Once the control is mounted and wired, set
up an initial pilot program.
•
Set and adjust System Startup Settings:
The contractor sets these values after installing
the control for the first time. End users should avoid changing these settings as they
will change the control operating logic. If the Startup Settings are not correct, the MPC
Platinum may operate the system incorrectly.
•
Set and adjust System Settings:
These settings adjust the
system to the specific building
characteristics. These are general settings that control the amount of heat provided. The
default settings will generally work in most applications, but adjustments should fine-
tune the performance of your system.
•
Set and adjust Maintenance:
Provide calibration tools for the sensors and allow a
password to be set.
•
Set and adjust Schedules:
Sets the Day/Night heat schedule and the Aux clock schedule.
Four pairs of Day/Night times can be set for each day of the week. In addition, the Aux
relay is capable of following the Aux Schedule. It is programmable to turn on or off up
to eight times per day.
•
Shift:
Allows you to temporarily shift from Day (higher heat level) to Night (lower
heat level) settings, or vice versa, without reprogramming the times of the Day/Night
Schedule.
- SYSTEM SETTINGS -
Season
Winter
Day Heat Adjust E
Night Heat Adjust B
Day Cutoff
55 F
Night Cutoff
40 F
<More Settings>