059305-00 Rev. D
Heat-Timer Corp.
Control Mode
Display Unit
Selections:
ETV, ETV + TMC,
TMC Only
Default:
ETV
Available in Control Modes:
All
Menu Path:
/System Startup > Control
Mode
Description:
ETV
– controls the electronic mixing valve to regulate the water temperature. This mode can also accept
the Flow Prove input to determine the mixing valve position during no flow periods.
TMC
– triggers an alarm and shuts the hot water supply to the system using a TMC valve when
experiencing excessive mixed temperature. This mode does not accept the Flow Prove input.
ETV + TMC
– controls the electronic mixing valve to regulate the water temperature and the TMC valve and
alarm to manage the hot water inlet. This mode also accepts the Flow Prove input to determine the mixing
valve position during no flow periods. See “Wiring the Flow Prove” on page
.
Selections:
°F, °C
Default:
°F
Available in Control Modes:
All
Menu Path:
/
System Startup > Control Mode > Display Unit
Description:
This option changes the sensors' display and all temperature settings standard to Fahrenheit or
Celsius.
Platinum Plus Display and Programming 37
Содержание ETV Platinum Plus
Страница 9: ...ETV Platinum Plus Stainless Steel Valve Dimensional Specifications 9 059305 00 Rev D Heat Timer Corp...
Страница 31: ...Piping Diagrams 31 059305 00 Rev D Heat Timer Corp Figure 14B Two Mixing Valves and a TMC Safety Valve...
Страница 54: ...059305 00 Rev D Heat Timer Corp Notes 54 ETV Platinum Plus Installation and Operation Manual...
Страница 55: ...059305 00 Rev D Heat Timer Corp Notes ETV Platinum Plus Installation and Operation Manual 55...