NOTE:
The valve and actuator can be mounted vertically (upright) or horizontally.
DO NOT
mount the valve
and actuator upside down. Leave at least 12 inches (30.5cm) service clearance on all sides between the valve/
actuator and any objects (walls, pipes, controls, etc.).
1.
Piping the valve as shown below is considered the "DEFAULT" configuration.
Ensure to follow the port letter designation or the valve flow direction label.
NOTE:
The ETV valve body can be oriented in such a way that the COLD Port A and HOT Port B are
interchangeable to accommodate existing piping. In this "alternate" configuration Port A
becomes the HOT port and Port B becomes the COLD port.
CAUTION
Use a two-wrench method (using one wrench to prevent the valve body from
turning or twisting) when tightening piping onto the valve body connections. Failure
to support the valve body in this manner may cause damage to the valve body, or
result in the "B" port coming loose, resulting in water leakage.
Figure 3:
Mounting of the ETV valve and actuator
Figure 4:
"Default" ETV
valve configuration
14 ETV Platinum Plus Installation and Operation Manual
Содержание ETV Platinum Plus
Страница 9: ...ETV Platinum Plus Stainless Steel Valve Dimensional Specifications 9 059305 00 Rev D Heat Timer Corp...
Страница 31: ...Piping Diagrams 31 059305 00 Rev D Heat Timer Corp Figure 14B Two Mixing Valves and a TMC Safety Valve...
Страница 54: ...059305 00 Rev D Heat Timer Corp Notes 54 ETV Platinum Plus Installation and Operation Manual...
Страница 55: ...059305 00 Rev D Heat Timer Corp Notes ETV Platinum Plus Installation and Operation Manual 55...