The DIGI-SPAN VSP 

Elite

 establishes ambient 

comfort by varying the temperature of the Secondary 

Loop’s circulating hot water in response to changes 

in the loop temperature.  The temperature of the 

heating water is controlled by regulating the speed 

of a pump which injects water from a hot Boiler 

Loop (Primary Loop) into a cooler heating loop 

(Secondary Loop).  As the speed of the pump 

increases, more hot water is sent into the Secondary 

Loop resulting into warmer water temperature.

The VSP 

Elite

 can be used as an outdoor reset 

control.  The VSP can also be used as a set point 

control.   In this mode of operation, the VSP will 

control the injection pump speed to hold a constant 

temperature (determined by the user) in the 

Secondary Loop.  In addition, it provides an outdoor 

temperature based cutoff and system pump control.

Three new features have been added to this control.  

A customized reset ratio curve for specialized 

buildings , a manual pump speed control to manually 

adjust the pump speed based on a well balanced 

system, and a minimum pump speed adjustment to 

allow for pump operation at all heating levels.

INSTALLATION AND OPERATION INSTRUCTIONS

VSP DIGI-E

lItE

Variable Speed Pump Control

®

Elite Series

Injection Pump Control for Hydronic Heating in 

Outdoor Reset or Set Point Applications

 WARNING

This Heat-Timer control is strictly an operating control; it should never be used as a primary limit or safety control.  All 

equipment must have its own certified limit and safety controls required by code.  The installer must verify proper operation 

and correct any safety problems related to the installation of this Heat-Timer control.

This control must be installed by a licensed electrician.

White

Yellow (System Output)

Injection Pump Output

Boiler

SYS

Pump

DHW

Pump

SET

®

C  O  R  P  O  R  A  T  I  O  N

R

SYSTEM =  

147F

TARGET =  

150F

DECREASE

SYSTEM

INCREASE

2 Line Alphanumeric Display

Displays sensor values and 

menu settings

Output Lights indicate

output status

Display Section Locking Screws

Black (120VAC power)

Содержание DIGI-SPAN VSP Elite

Страница 1: ...for specialized buildings a manual pump speed control to manually adjust the pump speed based on a well balanced system and a minimum pump speed adjustment to allow for pump operation at all heating l...

Страница 2: ...ng Type of Radiation in Building Reset Ratio Offset Radiators Steel Cast Iron 1 00 O 1 00 S 0 F Baseboard Finned copper tube Cast Iron 1 00 O 1 00 S 0 F Radiant High Mass Concrete 4 00 O 1 00 S 10 F R...

Страница 3: ...h side of the building Be sure the location is away from doors windows exhaust fans vents or other heat or cool sources The sensor should be mounted approximately 10 feet above ground level Adhere the...

Страница 4: ...op between the Secondary Loop and the Boiler Loop The VSP Elite will control the Injection Pump up to a maximum output of 1 2 Amp 1 8 HP i e B G NRF 33 Taco 0010 Grundfos 26 64 or equivalent The pump...

Страница 5: ...ng The Injection Pump and pipe size selection MUST be done properly by a qualified engineer or trained technician to insure proper operation and prevent excessive or under heat zones as well as hazard...

Страница 6: ...n the Default Screen is displayed pressing the SET Button views the MENU When in the Menus and settings the SET Button accepts the selected entry or setting value When in the menus pressing the Up and...

Страница 7: ...et SYS Temp 1 100 F CONTROL MODE Outdoor Reset Set Point OUTDOOR RESET Reset Ratio 7 Offset 0 F Cutoff 60 F Min Tgt 120 F Max Tgt 200 F Back Cutoff 70 F Reset Ratio O S Custom 1 8 00 1 00 2 4 00 1 00...

Страница 8: ...Output On Output Off Sensor Fault Options Output On Output Off Default Output On SET System Startup Sensor Fault The Sensor Fault will determine the operating status of the output relays when a senso...

Страница 9: ...factory defaults all control settings will be over written and will no longer exist Default Display The default display will show the current Secondary Loop System temperature and the Target temperatu...

Страница 10: ...election to 1 25 O 1 00 S The Custom option gives the user the capability of creating a specialized Reset Ratio curve Setting two points on the Reset Ratio chart generates the customized curve Each po...

Страница 11: ...utdoor Cutoff setting screen will automatically appear after the temperature Set Point has been selected and saved Cutoff 60 F The outdoor and its cutoff temperatures can be viewed from the default sc...

Страница 12: ...losing shorting the P terminals using an external timer N O S P S T Output Wiring 120VAC Power Wiring 120VAC Power Source BLACK BLACK Boiler Output Wiring N O YELLOW T1 T2 T3 COM COM T3 EXT EXT P P CO...

Страница 13: ...50 Minimum Speed Adjustment Options From 5 to 5 Default 0 T T T T T SET Maintenance Min Speed This is the slowest speed at which the VSP Elite is allowed to run the Injection Pump The VSP Elite will...

Страница 14: ...at the boiler or other hot water source is providing hot water to the Boiler Loop and no valve obstruction between the Boiler Loop and the Injection Loop Check that the Injection Pump is running by me...

Страница 15: ...Secondary Loop Pump Heat Load Balancing Valve T1 T2 COM COM T3 T3 EXT EXT P P System Sensor Outdoor Sensor Enable Dry Contact Setback Dry Contact Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R...

Страница 16: ...ve Maximum 1 8HP at 120VAC 50 60Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Setback from 0 F 0 C to 80 F 44 C Boost Yes 30Mi...