background image

DHW Energy Saver Installation and Configuration Manual  

7

HT# 059106-00C

Using the Supply or Return Sensor

Yes, No 

Default: No

SELECT 

Maintenance/DHW Settings/Supply Settings/Use Sensor

 

Supply Sensor

SELECT 

Maintenance/DHW Settings/Return Settings/Use Sensor

 

Return Sensor

•   By activating the Supply Sensor feature, the Platinum control will utilize Aux Temp 0 input 

as the Supply Sensor.

•   By activating the Return Sensor feature, the Platinum control will utilize Aux Temp 1 input 

as the Return Sensor.

•   Any of the two features can be enabled either using the Platinum control menus or the 

Platinum control ICMS webpage at (http://www.htcontrols.com).

USE SUPPLY SENSOR

 No

 Yes

USE RETURN SENSOR

 No

 Yes

Supply or Return Set Point

Boiler is adjustable from 60°F/16°C to 200F°/93°C 

Boiler Default: 140°F/60°C

Pump is adjustable from 60°F/16°C to 200F°/93°C 

Pump Default: 120°F/49°C

SELECT 

Maintenance/DHW Settings/Supply Settings/Setpoint

 

Supply Sensor

SELECT 

Maintenance/DHW Settings/Return Settings/Setpoint

 

Return Sensor

•   The Supply Set Point determines the maximum temperature at which the boiler/ water 

heater relay will de-energize.  It is the maximum DHW target temperature the DHW Energy 

Saver will try to achieve.  The relay will energize whenever the supply temperature drops 

below this set point less the differential.  See next setting.

•   The Return Set Point determines the maximum temperature at which the DHW pump relay 

will de-energize.  The circulating pump relay will energize whenever the return temperature 

drops below this set point less the differential.  See next setting.

DHW SUPPLY SETPOINT

     140 F

[

        ]

DHW RETURN SETPOINT

     120 F

[

        ]

Supply or Return Peak and Light Differential

Peak is adjustable from 5F°/3C° to 100F°/56C° 

Peak Default: 10F°/6C°

Light is adjustable from 5F°/3C° to 100F°/56C° 

Light Default: 20F°/11C°

SELECT 

Maintenance/DHW Settings/Supply Settings/Peak Diff or Light Diff

  Supply Sensor

SELECT 

Maintenance/DHW Settings/Return Settings/Peak Diff or Light Diff

 Return Sensor

•   Any of the differentials is subtracted from the set point to determine the temperature at 

which the boiler/water heater or pump relay will energize.

•   The DHW Energy Saver has two independent differentials for each of the supply and return.  

The Peak Differential is used to keep a tight control over the DHW temperature during 

heavy usage.  This differential is used when the DHW Schedule is in the Peak period.  Its 

value must be less than or equal to the Light Differential for the same sensor.

•   The Light Differential is used during the night, low DHW usage, or when a tight control of 

the temperature is not required.  It allows the boiler or pump relay to turn on for a slightly 

longer period.  However, due to the reduced usage, the relay will remain off for a much 

longer period.  This type of differential is used when the DHW Schedule is in the Light 

period.  Its value must be greater than or equal to the Peak Differential for the same sensor.

DHW SUPPLY PEAK DIFF

     20 F

[

        ]

DHW SUPPLY LIGHT DIFF

     40 F

[

        ]

DHW RETURN PEAK DIFF

     20 F

[

        ]

DHW RETURN LIGHT DIFF

     40 F

[

        ]

Содержание DHW Energy Saver

Страница 1: ...y an operating control it should never be used as a primary limit or safety control All equipment must have its own certified limit and safety controls required by local codes The installer must verif...

Страница 2: ...re Sensor 5 Return Temperature Sensor 5 PLATINUM CONTROL MENU SETTINGS 6 ICMS WEB MENU SETTINGS 6 Using the Supply or Return Sensor 7 Supply or Return Set Point 7 Supply or Return Peak and Light Diffe...

Страница 3: ...the supply temperature drops below the Supply Set Point and differential the Control will energize the boiler output The boiler output will remain energized until the supply temperature reaches the Su...

Страница 4: ...ol Connect the transformer outputs to the DHW Energy Saver s left most terminals Power polarity is not observed WARNING DO NOT share the DHW Energy Saver transformer with other devices This may cause...

Страница 5: ...anual operation of the pump DHW Energy Saver Boiler Pump 6 7 8 9 COM 3 4 5 A GND B 16VAC 1 2 DHW Pump L N Bypass Switch Optional Temperature Sensor Wiring Only use a Standard Brass Tube sensor provide...

Страница 6: ...HW SETTINGS Supply Settings Return Settings Demand Schedule Copy Schedule DHW Settings DHW SUPPLY SETTINGS Use Sensor Yes Setpoint 140 F Peak Diff 20 F Light Diff 40 F DHW RETURN SETTINGS Use Sensor Y...

Страница 7: ...relay will de energize The circulating pump relay will energize whenever the return temperature drops below this set point less the differential See next setting DHW SUPPLY SETPOINT 140 F DHW RETURN S...

Страница 8: ...on the ICMS web site Select Alarm Delivery Setup and then Add Delivery for the Sensor Fault WARNING The boiler water heater must have its operating and limit controls installed and wired in a way so...

Страница 9: ...X CLOCK T T C O R P O R A T I O N R 2 3 4 5 5A 6 7 8 9 11 12 13 14 15 16 17 OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WI...

Страница 10: ...ESS TO SELECT BACK MON 12 28 04 10 43Am ADJUST A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 AUX TEMP 2 DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS A13 A14 A15 A16 A17 A18 NETWORK PROVE SHUTDOWN SYSTEM TEMP...

Страница 11: ...OUTPUT RATINGS 120VAC 6A RESISTIVE 1A PILOT DUTY 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS 115VAC 60Hz 30VA MAX USE COPPER WIRE CLASS 1 WIRE ONLY ENCLOSED ENERGY MANAGEMENT EQUIPMENT 99RA PREV DEL OUT...

Страница 12: ...ltage Input 16 VAC transformer provided minimum 10VA Output Relays 2 N O SPST Each a maximum HP pump or 6 Amp resistive load at 120 VAC 60 Hz Outputs DHW boiler water heater and DHW pump Communication...

Отзывы: