Fault Code

Meaning of Code

OFF

The desired programmed temperature point is lower than 60°F (15°C).

LP & LP3

Shortage of refrigerant gas in the unit or faulty low pressure control. The unit will show
(LP3) after 

3

LP faults and shuts down the unit and 

pool pump

for protection. If this

occurs, you should call for service.

HP & HP6

Low water flow in the unit or faulty high pressure control. Check water flow/backwash. The
unit will show (HP6) after 6 HP faults. This will stop the unit for protection.

FLo & FL3

Possible causes:
• The filter is in backwash position.
• The filter pump is stopped.
• The filter is dirty.
• Shortage of water to pool pump.
• 

FIL parameter must be set to activate pool pump.

• Water pressure switch must be adjusted or it is broken.
• The unit is in the protection mode and will show (FL3), press any key to restart the unit.
FL3 code will stop the unit and 

pool pump

.

FS

Unit is in the defrosting cycle.
(The fan works but the compressor is stopped.)

- -

Keypad is pressing down on both buttons. Replace keypad.

Table A: Control Board Fault Codes

Service Call Verification

Before you make a service call, 

first

determine if the

problem is:

Warranty Service

Unit  operation  (power  supply,  water  flow,  or  time
clock adjustment)

Power Supply

Verify that all circuit breakers are reset and work-
ing properly.

If  the  temperature  display  or  the 

Power

lamp  on

the  control  panel  still  does  not  light,  contact  the
installing dealer, since it may be a power problem
requiring an electrician.

NOTE:

The 

MANUFACTURER  IS  NOT  RESPON-

SIBLE

for these adjustments.

Water Flow

Verify that the pool filter is clean to provide good
flow.

Verify that valves are properly positioned to allow
adequate water flow through the unit.

Time Clock Adjustment

Verify that the time clock is set to permit the unit to run
long enough to heat properly.

11

Содержание 5356 Series

Страница 1: ...this manual are for the use of qualified individuals specially trained and experienced in the installation and maintenance of this type of equipment and related system components Installation and ser...

Страница 2: ...Further advice should be obtained from your pool or spa builder accredited pool shop or chemical supplier for the correct levels for your water Recommended Level s Fiberglass Pools Fiberglass Spas Oth...

Страница 3: ...erature in C or F 8 System Start Up 8 Seasonal Start Up or Annual Check 8 Summer Shutdown 9 Freeze Protection 9 System Drain Down 9 Continuous Pump Operation 9 Maintenance 9 Air Coil Cleaning 9 Cabine...

Страница 4: ...d the heat pump pool heater CAUTION Elevated water temperature can be hazardous The U S Consumer Product Safety Commission has these guidelines 1 Spa water temperatures should never exceed 104 F 40 C...

Страница 5: ...h side of the unit at least 1 ft 30 cm from walls pipes and other obstructions Recirculation of cold discharge air back into the evaporator coil will greatly reduce the unit s heat ing capacity and ef...

Страница 6: ...on requirements Locate the equipment disconnect means within 3 feet 90cm of the heater s electrical enclosure or as close to the heater as possible Always satisfy applicable codes and standards In siz...

Страница 7: ...should be at least equal in size to the main pool spa circulation pip ing 4 In cold weather freeze zone areas shutoff valves ball or gate type must be installed at the unit inlet and outlet to facilit...

Страница 8: ...approximately 5 seconds Then the digital display will display the actual pool water temperature To Select Temperature in C or F Press the SET key until you see F _C By pressing the UP or DOWN key you...

Страница 9: ...uring the summer months secure and protect it as follows 1 Turn the unit circuit breaker or disconnect switch to OFF 2 Leave the valves set the way they are unless addi tional circulation is required...

Страница 10: ...do this reset the time clock dial for the longer running time or manually operate the pump with the timer override switch Since the unit capaci ty and efficiency are both greater at higher ambient ai...

Страница 11: ...to restart the unit FL3 code will stop the unit and pool pump FS Unit is in the defrosting cycle The fan works but the compressor is stopped Keypad is pressing down on both buttons Replace keypad Tabl...

Страница 12: ...K VALVE CHEMICAL INTRODUCTION WATER OUT TO POOL OR SPA Fig 4 For systems with pumps of less than 2 HP under 80 gpm no external bypass is required Connections are 2 inch unions Plumb the heat pump pool...

Страница 13: ...A Fig 5 For systems with pumps of 2 HP or greater over 80 gpm an external bypass is required Adjust the bypass valve to divert a minimum of 40 gpm through the heat pump pool heater Connections are 2 i...

Страница 14: ...Fig 6 Pool Piping for Heat Pump Pool Heater and Gas Pool Heater 14...

Страница 15: ...Fig 7 Pool Piping for Heat Pump Pool Heaters Multiple Primary Secondary UNITS UNITS UNITS 15...

Страница 16: ...Wiring Diagram 220 240V Single Phase 16...

Страница 17: ...Wiring Diagram 200 220V Three Phase 17...

Страница 18: ...18 Wiring Diagram 380 420V Three Phase...

Страница 19: ...OFF is displayed Wait until a temperature is displayed before beginning the next step 2 Push the SET key until SPA is displayed then push the UP arrow to 104 F 40 C Wait until a temperature is displa...

Страница 20: ......

Отзывы: