Step 11.  Before Lighting  the Fireplace

Before

 lighting the fireplace, be sure to do the following:

Remove all paperwork from underneath the fireplace.
Review safety warnings and cautions

• Read the 

Safety and Warning Information

 section at

the beginning of this 

Installers Guide

.

Double-check for gas leaks

• Before lighting the fireplace, double-check the unit for

possible gas leaks.

Double-check vent terminations and front grilles for

obstructions.

• Before lighting the fireplace, double-check the unit for

possible obstructions that could be blocking the vent ter-

minations or the front grilles.

Double-check for faulty components

• Any component that is found to be faulty 

MUST BE

 re-

placed with an approved component. ampering with the

fireplace components is 

DANGEROUS

 and voids all war-

ranties.

A small amount of air will be in the gas supply lines. When

first lighting the fireplace, it will take a few minutes for the

lines to purge themselves of this air. Once the purging is

complete, the fireplace will light and will operate normally.
Subsequent lightings of the fireplace will not require this

purging of air from the gas supply lines,

 unless

 

the gas

valve has been turned to the OFF position

, in which

case the air would have to be purged.

NOTE:

 The fireplace should be run for 8 hours on the initial

start-up. This will help to cure the chemicals used in the

paint and logs.

Step 12.   Lighting the Fireplace

You’ve reviewed all safety warnings, you’ve checked the

fireplace  for  gas  leaks,  you  know  the  vent  system  is

unobstructed, and you’ve checked for faulty components.

Now you’re ready to light the fireplace.

WARNING: PLEASE REFER TO THE USER’S

MANUAL FOR ALL CAUTIONS, SAFETY,  AND

WARNING  INFORMATION  PERTAINING  TO  THE

LIGHTING AND OPERATION OF THE FIREPLACE.

After the Installation

LEAVE THIS INSTALLATION MANUAL WITH

THE APPLIANCE FOR FUTURE REFERENCE.

!

!

Placing the Ember Material

Ember material is shipped with this gas fireplace. The bag

labeled Glowing Ember (050-721) is standard glowing ember

material. To place the ember material:

• Pull the four glass latches out of the groove on the glass

frame. Remove glass door from the unit (see Figure 39).

• Place dime size pieces of Glowing Ember (050-721)

ember material about 1/2 inch apart near port holes in

burner top. Do NOT press embers into burner ports. Cover

the top of the burner with a single layer of ember mate-

rial. For best performance do NOT place embers on the

ports at the rear of the burner.

• Save the remaining ember materials for use during fire-

place servicing.

• Replace the glass door and a front trim door on the unit.

• Pull out and latch the glass clips into the groove on the

glass frame.

Glass Specifications:

BE-41:      24 1/2  X  35 1/2    TEMPERED

CAUTION:  IT  IS  STRONGLY  RECOMMENDED  THAT

TRIM DOORS WITH OPTIONAL MESH SCREENS BE IN-

STALLED ON PROPANE MODELS.

Figure 40.   Placement of the Ember Material

Figure 39.  Glass Assembly

Содержание BE-41

Страница 1: ...UTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyforusewiththetype of gas indica...

Страница 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Страница 3: ...10 Step 3 Installing the Vent System 12 A Vent System Approvals 12 B Installing Vent Components 18 C Vent Termination 21 Step 4 Positioning Leveling and Securing the Fireplace 24 Step 5 The Gas Contr...

Страница 4: ...1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas fireplaces are...

Страница 5: ...eplace and its components are tested and safe when installed in accordance with this Installers Guide Report to your dealer any parts damaged in shipment particularly the condition of the glass Do not...

Страница 6: ...unit is to be installed The vent system configuration to be used Gas supply piping Electrical wiring Framing and finishing details Whether optional accessories devices such as a fan wall switch or re...

Страница 7: ...the face of the fireplace is one inch 25 mm The back of the fireplace may be recessed 21 1 2 inches 546 mm into combustible construction Minimum Clearances from the Vent Pipe to Combustible Materials...

Страница 8: ...below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING 1 2 CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE 0...

Страница 9: ...3 8 INCHES 34 93mm AT EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 48D 7 3 8 187mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35...

Страница 10: ...nting configuration used Terminations Kits Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical...

Страница 11: ...Up Vertical Venting NOTE On vertical venting configurations where the vertical component is over 10 feet you may want to install the vertical baffle VERT BAF see Figure 7 STRAIGHT UP VERTICAL VENTING...

Страница 12: ...e 90 Elbow VENTING WITH ONE 1 90 ELBOW VENTING WITH ONE 1 90 ELBOW V FT H FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MAX 12 4MM H 20 MAX...

Страница 13: ...914 mm 6 MAX 1 86 m 15 MAX 4 65m 4 MIN 1 22 m 8 MAX 2 48 m 20 MAX 6 2m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 20 MAX 6 2m Figure 12 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V FT H H...

Страница 14: ...914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX 2 48m 20 MAX 6 2m V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4 MAX 1 22m...

Страница 15: ...m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m NOTE H H1 20 MAX 6 2m V V1 H H1 40 MAX 12 4m V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX...

Страница 16: ...inch 127mm fireplace starting collar Make sure that the fiberglass rope gasket supplied with the fireplace seals between the first 8 5 8 inch 219mm vent component and the outer fireplace wrap Lock th...

Страница 17: ...e supports to the framing members Figure 17 Adding Venting Components For Vertical Runs The vent system must be supported every eight 8 feet 2 4m above the fireplace flue outlet by wall brackets To in...

Страница 18: ...the vent passes To install firestops for vertical runs that pass through ceilings Position a plumb bob directly over the center of the verti cal vent component Mark the ceiling to establish the center...

Страница 19: ...OR SIDING SEE THE FOL LOWING DIAGRAM FOR VENT TERMINATION CLEARANCES ROUND CAP TERMINATION PERFORATION CANNOT BE INSIDE THE WALL 7 1 2 191mm MINIMUM TRAPEZOID CAP TERMINATION 7 1 4 184mm WARNING THET...

Страница 20: ...or that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm f...

Страница 21: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems i...

Страница 22: ...position level and secure the fireplace Figure 27 Proper Positioning Leveling and Securing of a Fireplace Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The type of g...

Страница 23: ...vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching the pipe support the control so that the lines...

Страница 24: ...witch Position the remote wall switch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WA...

Страница 25: ...NSI or CAN CGAtesting standardsdonot require hearth extensions for gas fireplace appliances Figure 33 Sealant Material HIGH TEMPERATURE SIDE SEAL JOINT 300 F 149 C MIN TOP O O 0 0 FINISH WALL MATERIAL...

Страница 26: ...of the tie in the fireplace see Figure 35 WARNING USE WIRE CUT TERS DO NOT ATTEMPT TO CUT THE TIE WITH A KNIFE 3 Grasp the log assembly by the ends Do NOT grasp the log as sembly by the center Remove...

Страница 27: ...rward on the refractory see Figure 37 7 Cut shrink wrap and remove from around the log assembly WARNING REMOVE ALL PACKAGING FROM LOGS 8 Install embers See ember placement instructions for details WAR...

Страница 28: ...e chemicals used in the paint and logs Step 12 Lighting the Fireplace You ve reviewed all safety warnings you ve checked the fireplace for gas leaks you know the vent system is unobstructed and you ve...

Страница 29: ...annually By Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically B...

Отзывы: