Heat-N-Glo 6000XLSB Скачать руководство пользователя страница 20

24

Figure 25.   Gas Supply Line

• Insert insulation from the outside of the fireplace and

pack the insulation tightly to totally seal between the

pipe and the outer casing.

• At the gas line access hole the gap between the supply

piping and gas access hole can be plugged with non-

combustible insulation to prevent cold air infiltration.

Step 6.  The Gas Supply Line

NOTE: Have the gas supply line installed in accordance

with local  building codes by a qualified installer

approved and/or licensed as required by the locality.
NOTE: Before the first firing of the fireplace, the gas

supply line should be purged of any trapped air.
NOTE: Consult local building codes to properly size

the gas supply line leading to the 1/2 inch

(13 mm) hook-up at the unit.

This gas fireplace is designed to accept a 1/2 inch

(13 mm) gas supply line. To install the gas supply line:
• A listed (and State of Massachusetts approved) 1/2 inch

(13mm) tee-handle manual shut-off valve and a listed

flexible gas connector are connected to the 1/2 inch

(13mm) inlet of the control valve. 

NOTE:

 If substituting

for these components, please consult local codes for

compliance.

• Locate the gas line access hole in the outer casing of

the fireplace.

• The gas line may be run from either side of the fireplace

provided the hole in the outer wrap does not exceed 2” in

diameter and it does not penetrate the actual firebox.

• Open the fireplace lower grille, insert the gas supply line

through the gas line hole, and connect it to the shut-off

valve.

• When attaching the pipe, support the control so that the

lines are not bent or torn.

• After the gas line installation is complete, use a soap

solution to carefully check all gas connections for leaks.

WARNING: DO NOT USE AN OPEN FLAME

TO CHECK FOR GAS LEAKS

.

!

Step 7.   Gas Pressure Requirements

Pressure requirements for Heat-N-Glo gas fireplaces

are shown in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is

provided on the inlet and outlet side of the gas control for a

test gauge connection to measure the manifold pressure.

Use a small flat blade screwdriver to crack open the screw

in the center of the tap. Position a rubber hose over the tap

to obtain the pressure reading.
The fireplace and its individual shut-off valve must be

disconnected from the gas supply piping system during

any pressure testing of the system at test pressures in

excess of one-half (1/2) psig (3.5 kPa).
The fireplace must be isolated from the gas supply piping

system by closing its individual shut-off valve during any

pressure testing of the gas supply piping system at test

pressures equal to or less than one-half (1/2) psig (3.5 kPa).

USE A WRENCH ON 

SHUT-OFF VALVE WHEN 

TIGHTENING GAS LINE

GAS VALVE 

FLEX

CONNECTOR

MANUAL

SHUT-OFF VALVE 

CONTROL

 VALVE

GAS LINE

ACCESS HOLE

Содержание 6000XLSB

Страница 1: ...TH APPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyfor usewithth...

Страница 2: ...he installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Firepla...

Страница 3: ...ing the Vent System 13 A Vent System Approvals 13 B Installing Vent Components 16 C Vent Termination 20 Step 4 Positioning Leveling and Securing the Fireplace 23 Step 5 The Gas Control Systems 23 Step...

Страница 4: ...SAC22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada 1Approvals and Codes High Altitude Installations U L Listed gas fireplac...

Страница 5: ...enefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the f...

Страница 6: ...10 Figure 1 Diagram of the 7000XLS and 6000XLSB...

Страница 7: ...ance diagrams on pages 19 and 20 in this manual Step 2 Framing the Fireplace Fireplace framing can be built before or after the fireplace is set in place Framing should be positioned to accommo date w...

Страница 8: ...AP 1 3 8 INCHES 34 93mm AT EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Страница 9: ...etailed installation instructions are included with each vent termination kit and should be used in conjunction with this Installers Guide Theflameandemberappearancemayvarybasedonthetype of fuel burne...

Страница 10: ...stall the vertical baffle included in the manual bag assembly to improve flame appearance Figure 7 Venting with One 90 Elbow VENTING WITH ONE 1 90 ELBOW Figure 8 Venting with Two 90 Elbows VENTING WIT...

Страница 11: ...86 m 18 MAX 5 485 m 4 MIN 1 22 m 8 MAX 2 48 m 24 MAX 7 31 m V1 V H H1 40 MAX 12 4m 8 MAX 2 48m 24 MAX 7 31m V H H H1 1 MIN 305 mm 2 MAX 610 mm 6 MAX 1 82 m 2 MIN 610 mm 4 MAX 1 22 m 12 MAX 3 65 m 3 M...

Страница 12: ...ent end with four 4 equally spaced indented sections When the internal beads of each 8 5 8 inch 219mm outer pipe line up rotate the pipe section clockwise about one quarter 1 4 turn Theventpipeisnowlo...

Страница 13: ...eding component in the vent system 90 elbows may be installed and rotated to any point around the preceding component s vertical axis If an el bow does not end up in a locked position with the pre ced...

Страница 14: ...ops for horizontal runs that pass through either interior or exterior walls Cut a 12 inch by 12 inch 305mm X 305mm hole through the wall NOTE The center of the hole is one 1 inch 25 4mm above the cent...

Страница 15: ...11 inch 280mm X 280mm hole through the ceiling using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 18 Ceiling Firestop Ceiling Side If...

Страница 16: ...of the wall firestop to secure the vent pipe in place For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges in the cap Figure 20 Round Trapezoid Ter...

Страница 17: ...oor that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm...

Страница 18: ...FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems i...

Страница 19: ...ition level and secure the fireplace Figure 23 Proper Positioning Leveling and Securing of a Fireplace Figure 24 Gas Control System STANDING PILOT Step 5 The Gas Control System WARNING THIS UNIT IS NO...

Страница 20: ...fireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn Afte...

Страница 21: ...itch in the desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 110 120 VAC...

Страница 22: ...IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND TOP AND SIDES ARE SEALED A 300 F MINIMUM SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBL...

Страница 23: ...gs might need to be repositioned slightly to avoid excessive flame impingement Step 10 Installing Trim Logs and Ember Material Placing the Ember Material Ember material is shipped with this gas firepl...

Страница 24: ...n the gas supply lines When first lighting the fireplace it will take a few minutes for the lines to purge themselves of this air Once the purging is complete the fireplace will light and will operate...

Страница 25: ...ncy Once annually By Qualified service technician Task Brush or vacuum the control compartment fireplace logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Perio...