Heat-N-Glo 6000TRXI Скачать руководство пользователя страница 24

24

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

V

= VENT  TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

     Figure 32.  Vent Termination Minimum Clearances

A

= 12" ....................... clearances above grade, veran-

da, porch, deck or balcony

B

= 12" ....................... clearances to window or door

that may be opened, or to per-
manently closed window.

D*

= 18" ....................... vertical clearance to ventilated

soffit located above the terminal
within a horizontal distance of 2
feet (60 cm) from the center-line
of the terminal

E*

= 18" ....................... clearance to unventilated soffit

F

=  9" ......................... clearance to outside corner

G

= 6" .......................... clearance to inside corner

H

= 3 ft. (Canada) ....... not to be installed above a gas

meter/regulator assembly within
3 feet (90cm) horizontally from the
center-line of the regulator

I

= 3 ft. (U.S.A.)

6 ft. (Canada) ....... clearance to service regulator

vent outlet and electric service

J

= 9" (U.S.A.)

12" (Canada) ......... clearance to non-mechani-

cal air supply inlet to build-
ing or the combustion air in-
let to any other appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) ......... clearance to a mechanical

air supply inlet

L** = 7 ft. ......................... clearance above paved

sidewalk or a paved driveway
located on 

public

 property

M*** = 18" ......................... clearance under veranda,

porch, deck or balcony

N

= 6” ........................... non-vinyl siding

12” ......................... vinyl siding

O

= 18” ......................... non-vinyl soffit and overhang

42” ......................... vinyl soffit and overhang

P

= 8 ft.

D

E

B

L

v

v

v

v

v

v

v

v

B

B

A

H

M

X

J or K

I

A

G

F

U.S.

(3 FT)

B

CAUTION: 

IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS NECESSARY TO INSTALL THE VINYL PROTECTOR

KIT TO THE TOP OF THE EXTERIOR FIRESTOP (FOR ALL ROUND TERMINATION CAPS). IT IS STRONGLY RECOMMENDED
WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT.

 42” minimum for vinyl clad soffits.

  ** a vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings
and serves both dwellings.

 *** only permitted if veranda, porch, deck or balcony is fully open on

a minimum of 2 sides beneath the floor.

NOTE 1

: On private property where termination is less than 7 feet

above a sidewalk, driveway, deck, porch, veranda or balcony, use of
a listed cap shield is suggested.

NOTE 2

: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 

1

. There must be 3 feet minimum

between termination caps. 

2. 

 All mechanical air intakes within 10 feet

of a termination cap must be a minimum of 3 feet below the termination
cap. 

3.

 All gravity air intakes within 3 feet of a termination cap must be

a minimum of 1 foot below the termination cap.

O

N

P

R

Q

(See Note 1)

(See Note 1)

(See Note 2)

NOTE 3

: Local codes or regulations may require different

clearances.

NOTE 4: 

Termination caps may be hot. Consider their proximity to

doors or other traffic areas.

WARNING: In the U.S:

 Vent system termination is 

NOT

 permitted

in screened porches. You must follow side wall, overhang and
ground clearances as stated in the instructions.

In Canada:

 Vent system termination is 

NOT

 permitted in screened

porches. Vent system termination is permitted in porch areas
with two or more sides open. You must follow all side walls,
overhang and ground clearances as stated in the instructions.

Heat-N-Glo assumes no responsibility for the improper perfor-
mance of the fireplace when the venting system does not meet
these requirements.

    

Q

MIN

     R

MAX

  1 cap

  3 feet

   2 x Q 

ACTUAL

  2 caps

  6 feet

   1 x Q 

ACTUAL

  3 caps

  9 feet

2/3 x Q 

ACTUAL

  4 caps

12 feet

1/2 x Q 

ACTUAL

Q

MIN

 = # termination caps x 3        R

MAX

 = (2 / # termination caps) x Q

ACTUAL

Содержание 6000TRXI

Страница 1: ...RENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 This appliance is only for use with the type of gas indicate...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...lling Vent Components 19 C Vent Termination 23 Step 4 Positioning Leveling and Securing the Fireplace 25 Step 5 Install the Optional Heat Zone Kit 26 Step 6 The Gas Control Systems 26 Step 7 The Gas S...

Страница 4: ...s de pi ce se trouve la page suivante 14 4 5 17 18 16 6 Log set assembly 2 3 1 15 7 8 9 10 11 12 13 19 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts 6000TRXI Beginning Manufac...

Страница 5: ...old Gasket Joint Diversifi Vari 385 410 Rheostat Knob Black Bouton de Rh ostat Noir 100 512 Flex Ball Valve Assembly Fl chir l Assembl e de Soupape de Balle 302 320A Rheostat Assembly Assembl e de Rh...

Страница 6: ...absence of local codes with the National Electric Code ANSI NFPA No 70 in the United States or to the CSA C22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitt...

Страница 7: ...enefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the f...

Страница 8: ...LS RATING PLATE AND LABELS TRIM DOOR HOOD TOP STANDOFFS 41 1 8 1044mm 38 965mm 36 1 8 916mm 25 1 4 642mm 34 5 8 879mm 8 5 8 219mm VENT COLLARS ELECTRICAL ACCESS 26 7 8 682mm 12 3 4 323mm 3 1 2 90mm GA...

Страница 9: ...tructing the Fireplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not...

Страница 10: ...g material The dia gram below shows framing reference dimensions CAUTION MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS BEFORE FRAMING Shows center of 12 x 12 vent f...

Страница 11: ...36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 48D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 8 5 8 220mm 8 1 2 216mm 6 7 16 164mm 11 1 16 281mm 6 1 2 165mm 8 1 2 216mm 5 1 16 129mm 8 5 8 220mm 35 3 4 908mm...

Страница 12: ...rminations Kits Identifying Vent Components The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vertical rise to horizontal run in...

Страница 13: ...want to install the vertical baffle 385 128 See flue restrictor installation in structions Figure 6 Flex Vent The flex vent must be supported with the spacing be tween support intervals not exceeding...

Страница 14: ...tem with the chart to find the appropriate position to set the Flue Restrictor 1 2 3 4 5 SETTINGS 1 2 3 4 5 Figure 10 CHART Vertical Top Vent NG Top Vent LP Rear Vent NG Rear Vent LP 4 1 1 No Restrict...

Страница 15: ...MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H 40 MAX 12 4MM H 20 MAX 6 2m Figure 13 Venting with One 90 Elbow NOTE If a 90o elbow is first attached to the unit the maximum horizontal r...

Страница 16: ...15 Venting with Two 90 Elbows VENTING WITH TWO 2 90o ELBOWS V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m V H H1 40 MAX 12 4m H H1 20 MA...

Страница 17: ...V H H1 H2 40 MAX 12 4 m H 8 MAX 2 48 m H H 1 H2 20 MAX 6 2 m V H H H1 H2 1 MIN 305mm 2 MAX 610mm 5 MAX 1 52m 2 MIN 610mm 4 MAX 1 22m 10 MAX 3 1m 3 MIN 914mm 6 MAX 1 86m 15 MAX 4 65m 4 MIN 1 22m 8 MAX...

Страница 18: ...m V V1 H H1 40 MAX 12 4m V FT H H1 FT 1 MIN 305mm 5 MAX 1 52m 2 MIN 610mm 10 MAX 3 1m 3 MIN 914mm 15 MAX 4 65m 4 MIN 1 22m 20 MAX 6 2m H H1 20 MAX 6 2m NOTE V V1 H H1 40 MAX 12 4m Figure 17 Venting wi...

Страница 19: ...NENT 1 Attach the First Vent Component to the Starting Collars To attach the first vent component to the starting collars of the fireplace WARNING THE REAR VENT COLLAR SEAL CAP MUST REMAIN ATTACHED TO...

Страница 20: ...o install support brackets for horizontal runs Place the pipe supports around the vent pipe Nail the pipe supports to the framing members Figure 24 Adding Venting Components HEAT SHIELD 3 MIN 76mm COM...

Страница 21: ...her interior or exterior walls Cut a 12 inch by 12 inch 305mm X 305mm hole through the wall NOTE The center of the hole is one 1 inch 25 4mm above the center of the horizontal vent pipe Position the f...

Страница 22: ...g using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 29 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an attic p...

Страница 23: ...POSITIONED SO THAT THEARROW IS POINT ING UP For trapezoidal cap termination kits Using screws secure the cap to the exterior wall through the flanges in the cap Figure 31 Trapezoid Termination Caps WA...

Страница 24: ...STRONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 42 minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is located between...

Страница 25: ...n and snow from the vent system Attach a flashing to the roof using nails and use a non hardening mastic around the edges of the flashing base where it meets the roof Attach a storm collar over the fl...

Страница 26: ...EMUSTBEWIREDDIRECTLYTOTHEFIRE PLACE JUNCTION BOX Figure 36 Gas Controls System STANDINGPILOT Step 5 installing the Optional Heat Zone Kit NOTE There must be NO INSULATION or other com bustibles inside...

Страница 27: ...gged with non combustible insulation to pre vent cold air infiltration Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When attaching th...

Страница 28: ...ilot Ignition Wiring Diagram Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the factory installed junction box before the fireplace is permanently insta...

Страница 29: ...RROUND SEE THE DIAGRAM BELOW Hearth Extensions A hearth extension may be desirable for aesthetic reasons However ANSI or CAN CGAtesting standards donot require hearth extensions for gas fireplace appl...

Страница 30: ...d slightly to avoid excessive flame impingement Step 11 Installing Trim Logs and Ember Material Placing the Ember Material Ember material is shipped with this gas fireplace To place the ember material...

Страница 31: ...gas valve has been turned to the OFF position in which case the air would have to be purged NOTE The fireplace should be run 3 to 4 hours on the initial start up Turn it off and let it cool completely...

Страница 32: ...burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Ma...

Отзывы: