![Heat Controller HTD Series Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/heat-controller/htd-series/htd-series_installation-operation-and-maintenance-manual_2115774034.webp)
34
Installation, Operation & Maintenance
HTV/HTD/HTH SERIES
Heat Controller, Inc.
Unit Operating Conditions
Table 10: Water Temperature Change Through Heat Exchanger
Antifreeze Type
Antifreeze
%
Cooling
Heating
WPD
Corr. Fct.
EWT 30°F
EWT 90°F
EWT 30°F
Total Cap
Sens Cap
Power
Htg Cap
Power
Water
0
1.000
1.000
1.000
1.000
1.000
1.000
Propylene Glycol
5
0.995
0.995
1.003
0.989
0.997
1.070
15
0.986
0.986
1.009
0.968
0.990
1.210
25
0.978
0.978
1.014
0.947
0.983
1.360
Methanol
5
0.997
0.997
1.002
0.989
0.997
1.070
15
0.990
0.990
1.007
0.968
0.990
1.160
25
0.982
0.982
1.012
0.949
0.984
1.220
Ethanol
5
0.998
0.998
1.002
0.981
0.994
1.140
15
0.994
0.994
1.005
0.944
0.983
1.300
25
0.986
0.986
1.009
0.917
0.974
1.360
Ethylene Glycol
5
0.998
0.998
1.002
0.993
0.998
1.040
15
0.994
0.994
1.004
0.980
0.994
1.120
25
0.988
0.988
1.008
0.966
0.990
1.200
Antifreeze Correction Table
Table 9a: HT Coax Water Pressure Drop
Model
GPM
Pressure Drop (psi)
30°F
50°F
70°F
90°F
026
2.3
3.0
3.4
4.5
6.0
0.7
1.1
1.3
2.0
3.1
0.4
0.7
0.9
1.4
2.3
0.4
0.6
0.8
1.2
1.9
0.5
0.7
0.8
1.2
1.8
038
3.0
4.5
6.0
6.8
9.0
1.5
2.6
3.8
4.5
6.9
0.9
1.7
2.7
3.2
5.2
0.8
1.5
2.3
2.7
4.4
0.9
1.5
2.2
2.6
4.1
049
4.5
6.0
6.8
9.0
12.0
1.5
2.6
3.8
4.5
6.9
0.6
1.1
1.4
2.5
4.2
0.5
1.0
1.3
2.3
3.8
0.3
0.9
1.2
2.2
3.5
064
6.0
7.5
9.0
11.3
12.0
15.0
0.9
1.7
2.5
3.7
4.1
6.1
0.2
0.9
1.5
2.6
3.0
4.7
0.2
0.7
1.3
2.3
2.6
4.1
0.3
0.8
1.4
2.3
2.6
4.0
072
7.0
8.5
10.5
12.8
14.0
17.0
1.4
2.2
3.3
4.6
5.4
7.6
0.7
1.3
2.2
3.4
4.1
6.0
0.5
1.1
1.9
3.0
3.6
5.4
0.7
1.2
2.0
2.9
3.5
5.2
024
036
048
060
070