background image

Heat Controller, Inc. 

HBH/V CompaCt 

IOM Instructions

Ground-Loop Heat Pump Applications

Pre-Installation

Prior to installation, locate and mark all existing 
underground utilities, piping, etc. Install loops for new 
construction before sidewalks, patios, driveways, and other 
construction has begun. During construction, accurately 
mark all ground loop piping on the plot plan as an aid in 
avoiding potential future damage to the installation.

Piping Installation

The typical closed loop ground source system is shown 
in Figure 13. All earth loop piping materials should be 
limited to polyethylene fusion only for in-ground sections 

of the loop. Galvanized or steel fittings should not be 

used at any time due to their tendency to corrode. All 

plastic to metal threaded fittings should be avoided due 

to their potential to leak in earth coupled applications. A 

flanged fitting should be substituted. P/T plugs should be 

used so that flow can be measured using the pressure 

drop of the unit heat exchanger. 

Earth loop temperatures can range between 25 and 
110°F [-4 to 43°C].  Flow rates between 2.25 and 3 gpm 
per ton [2.41 to 3.23 l/m per kW] of cooling capacity is 
recommended in these applications. 

Test individual horizontal loop circuits before backfilling. 

Test vertical U-bends and pond loop assemblies prior to 
installation. Pressures of at least 100 psi [689 kPa] should 
be used when testing.  Do not exceed the pipe pressure 
rating.  Test entire system when all loops are assembled. 

Flushing the Earth Loop

Upon completion of system installation and testing, flush 

the system to remove all foreign objects and purge to 
remove all air. 

Antifreeze

In areas where minimum entering loop temperatures drop 
below 40°F [5°C] or where piping will be routed through 
areas subject to freezing, antifreeze is required. Alcohols 
and glycols are commonly used as antifreeze. Freeze 
protection should be maintained to 15°F [9°C] below the 
lowest expected entering loop temperature. For example, 
if 30°F [-1°C] is the minimum expected entering loop 
temperature, the leaving loop temperature would be 25 to 
22°F [-4 to -6°C] and freeze protection should be at 15°F 
[-10°C].  Calculation is as follows:
30°F - 15°F = 15°F [-1°C - 9°C = -10°C]. 

All alcohols should be premixed and pumped from 
a reservoir outside of the building when possible or 
introduced under the water level to prevent fumes. 

Calculate the total volume of fluid in the piping system. 

Then use the percentage by volume shown in table 
2 for the amount of antifreeze needed. Antifreeze 
concentration should be checked from a well mixed 

sample using a hydrometer to measure specific gravity.

CAUTION!

  The following instructions represent industry 

accepted installation practices for closed loop earth coupled 
heat pump systems. Instructions are provided to assist the 
contractor in installing trouble free ground loops. These 
instructions are recommendations only. State/provincial 
and local codes MUST be followed and installation MUST 
conform to ALL applicable codes. It is the responsibility of 
the installing contractor to determine and comply with ALL 
applicable codes and regulations.

Table 2: Antifreeze Percentages by Volume

Low Water Temperature Cutout Setting - CXM Control

When antifreeze is selected, the FP1 jumper (JW3) should 
be clipped to select the low temperature (antifreeze 13°F 
[-10.6°C]) set point and avoid nuisance faults (see “Low 
Water Temperature Cutout Selection” in this manual).  NOTE:  
Low water temperature operation requires extended range 
equipment.

CAUTION!

CAUTION!

Type

Minimum Temperature for Low Temperature Protection

10°F [-12.2°C]

15°F [-9.4°C]

20°F [-6.7°C]

25°F [-3.9°C]

Methanol
100% USP food grade Propylene Glycol
Ethanol*

25%
38%
29%

21%
25%
25%

16%
22%
20%

10%
15%
14%

* Must not be denatured with any petroleum based product

CAUTION!

  Ground loop applications require extended range 

equipment and optional refrigerant/water circuit insulation.

Содержание HBH/V Compact

Страница 1: ... Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com Installation Operation Mainenance Manual Commercial Horizontal Vertical Packaged Water Source Heat Pumps HBH V Compact ...

Страница 2: ...nd Water Systems 14 17 Water Quality Standards 18 Electrical Line Voltage 19 Electrical Data 20 21 Electrical Power Low Voltage Wiring 22 24 Electrical Thermostat Wiring 25 CXM Controls 26 CXM Control Safety Features 27 28 Unit Starting Operating Conditions 29 Piping System Cleaning Flushing 30 Unit System Checkout 31 Unit Start Up Procedure 32 33 Unit Operating Procedures Temperatures 34 37 Preve...

Страница 3: ...traQuiet Option Compressor incorporates spring mounting system 015 060 include compressor discharge muf er blower housing is covered with high density noise suppression material Application Units can be applied in WLHP GWHP or GLHP applications Basic Unit Description HB H A 036 C 3 3 0 A L B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 HB HEAT CONTROLLER COMPACT 410A MODEL TyPE H HORIZONTAL NON PAINTED CONFIG...

Страница 4: ...pon receipt of the equipment carefully check the shipment against the bill of lading Make sure all units have been received Inspect the packaging of each unit and inspect each unit for damage Insure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report Concealed damage not discovered during unloading mus...

Страница 5: ...aution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety glasses and gloves when handling parts and servicing heat pumps General Information Prepare units for installation as follows 1 Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been ...

Страница 6: ...24 1 14x24 1 18x24 Weight Operating lbs 103 105 114 153 158 189 197 203 218 263 278 Weight Packaged lbs 113 115 124 158 163 194 202 209 224 270 285 Horizontal Air Coil Dimensions H x W 10x15 10x15 10x15 16x22 16x22 16x22 16x22 20x25 20x25 20x35 20x35 Filter Standard 1 Throwaway 10x18 10x18 10x18 16x25 16x25 18x25 18x25 20x28 or 2 20x14 20x28 or 2 20x14 1 20x24 1 20x14 1 20x24 1 20x14 Weight Operat...

Страница 7: ...cause cabinet condensation such as unconditioned spaces subject to 100 outside air Consideration should be given to access for easy removal of the filter and access panels Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a closet provisions must be made for return air to freely enter the space by means of a louvered door etc ...

Страница 8: ...s Cableado del termostato Válvula compensadora opcional Salida de agua Entrada de agua Válvula invertida opcional para control de baja presión de agua puede montarse en forma interna Válvula a bola con tapón P T integrado opcional Manguera trenzada de acero inoxidable con accesorio giratorio en J Circuito de edificación Disyuntor de energía de la unidad fabricado por terceros Alimentación de energ...

Страница 9: ...nel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or contact with sheet metal edges Reroute if necessary 4 Check refrigerant tubing for contact with other components 5 Reinstall top panel and screws noting that the location for some screws will have changed 6 Manually spi...

Страница 10: ...NE IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW Duct System Installation Proper duct sizing and design is critical to the performance of the unit The duct system should be designed to allow adequate and even airflow through the unit during operation Air flow through the unit MUST be at or above the minimum stated airflow for the unit to avoid equipment damage Duct syst...

Страница 11: ... to access for easy removal of the filter and access panels Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a closet provisions must be made for return air to freely enter the space by means of a louvered door etc Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to...

Страница 12: ...ate hose inside the cabinet as a trapping loop therefore an external trap is not necessary Figure 10a shows typical condensate connections Figure 10b illustrates the internal trap for a typical vertical heat pump Each unit must be installed with its own individual vent where necessary and a means to flush or blow out the condensate drain line Do not install units with a common trap and or vent Ven...

Страница 13: ...n angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum Insulation is not required on loop water piping except where the piping runs through unheated areas outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient conditions Insulation is required if loop water temperature drops below the dew point ...

Страница 14: ...emove dirt piping chips and other foreign material prior to operation see Piping System Cleaning and Flushing Procedures in this manual The flow rate is usually set between 2 25 and 3 5 gpm per ton 2 9 and 4 5 l m per kW of cooling capacity Heat Controller recommends 3 gpm per ton 3 9 l m per kW for most applications of water loop heat pumps To insure proper maintenance and servicing P T ports are...

Страница 15: ...ly used as antifreeze Freeze protection should be maintained to 15 F 9 C below the lowest expected entering loop temperature For example if 30 F 1 C is the minimum expected entering loop temperature the leaving loop temperature would be 25 to 22 F 4 to 6 C and freeze protection should be at 15 F 10 C Calculation is as follows 30 F 15 F 15 F 1 C 9 C 10 C All alcohols should be premixed and pumped f...

Страница 16: ...IOM Instructions HBH V Compact Heat Controller Inc Ground Loop Heat Pump Applications Figure 13 Typical Ground Loop Application ...

Страница 17: ......

Страница 18: ...ter In Water Out Water Control Valve Optional Filter P T Plugs Ground Water Heat Pump Applications Water Coil Low Temperature Limit Setting For all open loop systems the 30 F 1 1 C FP1 setting factory setting water should be used to avoid freeze damage to the unit See Low Water Temperature Cutout Selection in this manual for details on the low limit setting ...

Страница 19: ...pmÊlevel CopperÊalloyÊ bronzeÊorÊbrass ÊcastÊcomponentsÊareÊOKÊtoÊ 0 5Êppm AmmoniaÊionÊasÊhydroxide Êchloride Ê nitrateÊandÊsulfateÊcompounds All 0 5Êppm Maximum MaximumÊAllowableÊatÊmaximumÊwaterÊtemperature ChlorideÊLevels 50 FÊ 10 C 75 FÊ 24 C 100ϒ F 38ϒ C Copper 20ppm NR NR CuproNickel 150Êppm NR NR 304ÊSS 400Êppm 250Êppm 150 ppm 316ÊSS 1000Êppm 550Êppm 375 ppm Titanium 1000Êppm 550Êppm 375 pp...

Страница 20: ...ding General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial plate Line and low voltage wiring must be done in accordance with local codes or the National Electric Code whichever is applicable WARNING To avoid possible injury or death due to electrical shock open the power supply disconnect switch and secure it in an open position during insta...

Страница 21: ...9 292 1 11 2 60 0 2 70 13 9 16 7 25 3 208 230 60 3 197 254 1 8 9 58 0 3 00 11 9 14 1 20 4 460 60 3 414 506 1 4 2 28 0 1 70 5 9 7 0 15 036 1 208 230 60 1 197 254 1 16 7 79 0 1 80 18 5 22 7 35 8 265 60 1 239 292 1 13 5 72 0 2 00 15 5 18 9 30 3 208 230 60 3 197 254 1 10 4 73 0 1 80 12 2 14 8 25 4 460 60 3 414 506 1 5 8 38 0 1 24 7 0 8 5 15 042 1 208 230 60 1 197 254 1 17 9 112 0 3 00 20 9 25 4 40 3 2...

Страница 22: ...7 254 1 16 7 79 0 3 00 19 7 23 9 40 8 265 60 1 239 292 1 13 5 72 0 2 70 16 2 19 6 30 3 208 230 60 3 197 254 1 10 4 73 0 3 00 13 4 16 0 25 4 460 60 3 414 506 1 5 8 38 0 1 70 7 5 9 0 15 042 1 208 230 60 1 197 254 1 17 9 112 0 3 00 20 9 25 4 40 3 208 230 60 3 197 254 1 13 5 88 0 3 00 16 5 19 9 30 4 460 60 3 414 506 1 6 0 44 0 1 70 7 7 9 2 15 5 575 60 3 518 633 1 4 9 34 0 1 40 6 3 7 5 15 048 1 208 230...

Страница 23: ...nd phase shown on the unit serial plate Line and low voltage wiring must be done in accordance with local codes or the National Electric Code whichever is applicable Figure 15 HB Single Phase Line Voltage Field Wiring Three phase wiring is similar except that all three power wires are directly connected to the contactor Transformer CXM Control Contactor CC BR Low Voltage Connector CB L2 L1 Unit Po...

Страница 24: ...or alta M para velocidad de ventilador media L para velocidad de ventilador baja La configuración de fábrica es velocidad media Connect the blue wire to H for High speed fan M for Medium speed fan L for Low speed fan Medium is factory setting Fan Motor Figure 16 PSC Motor Speed Selection Figure 17 HB Low Voltage Field Wiring Thermostat Connections The thermostat should be wired directly to the CXM...

Страница 25: ... When wired as shown the slow closing valve will operate properly with the following notations 1 The valve will remain open during a unit lockout 2 The valve will draw approximately 25 35 VA through the Y signal of the thermostat Note This valve can overheat the anticipator of an electromechanical thermostat Therefore only relay or triac based thermostats should be used Low Voltage VA Ratings Comp...

Страница 26: ...position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wall Thermostat wire must be 18 AWG wire Wire the appropriate thermostat as shown in Figures 22 through 25c to the low voltage terminal strip on the CXM control board Practically any heat pump thermostat will work with Heat Controller units provided it has the correct numb...

Страница 27: ...from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field selection to disable the UPS feature On Enabled Off Disabled DIP switch 2 Stage 2 Selection provides selection of whether compressor has an on delay If set to stage 2 the compressor will have a 3 second delay before energizing Also if set for stage 2 the alarm relay will NOT cycle during test mode On Stage 1 Off Sta...

Страница 28: ...ick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure loss of charge fault The low pressure switch input is bypassed for the initial 60 seconds of a comp...

Страница 29: ...laces If the control is in test mode the control will lockout with code 9 after 30 seconds if a The compressor is on in the cooling mode and the FP1 sensor is colder than the FP2 sensor or b The compressor is on in the heating mode and the FP2 sensor is colder than the FP1 sensor Diagnostic Features The LED on the CXM board advises the technician of the current status of the CXM control The LED ca...

Страница 30: ...W 1 5 to 3 0 gpm ton 1 6 to 3 2 l m per kW 1 5 to 3 0 gpm ton Rev 23 Jan 2009B Cooling Heating Cooling Heating Cooling Heating Air Limits Min ambient air DB 45ºF 7ºC 39ºF 4ºC 45ºF 7ºC 39ºF 4ºC 45ºF 7ºC 39ºF 4ºC Rated ambient air DB 80 6ºF 27ºC 68ºF 20ºC 80 6ºF 27ºC 68ºF 20ºC 80 6ºF 27ºC 68ºF 20ºC Max ambient air DB 110ºF 43ºC 85ºF 29ºC 110ºF 43ºC 85ºF 29ºC 110ºF 43ºC 85ºF 29ºC Min entering air DB ...

Страница 31: ...or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this period shut off the circulating pump and drain the solution Repeat system cleaning if desired 8 When the cleaning process is complete remove the short circuited hoses Reconnect the hoses to the proper supply and return the...

Страница 32: ...ater temperature Check water temperature for proper range and also verify heating and cooling set points for proper operation 8 System pH Check and adjust water pH if necessary to maintain a level between 6 and 8 5 Proper pH promotes longevity of hoses and fittings see table 3 8 System flushing Verify that all hoses are connected end to end when flushing to insure that debris bypasses the unit hea...

Страница 33: ...exchanger to table 7 In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature drop across the air coil when compressor is operating Air temperature drop should be between 15 F and 25 F 8 C and 14 C g Turn thermostat to OFF position A hissing noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize before beg...

Страница 34: ...F 32 C 006 0 75 0 05 0 5 3 7 0 3 2 3 0 2 1 6 0 2 1 6 1 1 0 07 0 8 5 3 0 5 3 5 0 4 2 7 0 3 2 2 1 5 0 09 1 3 8 8 0 9 6 1 0 7 4 8 0 6 4 0 009 1 1 0 07 1 3 9 0 0 6 4 4 0 4 2 8 0 3 1 9 1 8 0 11 2 1 14 1 1 4 9 4 1 1 7 4 0 9 6 2 2 3 0 14 3 5 24 3 2 6 17 9 2 1 14 7 1 8 12 7 012 1 5 0 09 1 9 12 8 1 1 7 6 0 8 5 3 0 6 4 1 2 3 0 15 3 6 25 0 2 6 17 8 2 1 14 3 1 8 12 1 3 0 0 19 6 7 46 1 5 0 34 3 4 1 28 3 3 6 24...

Страница 35: ...notes Airflow is at nominal rated conditions Entering air is based upon 70 F 21 C DB in heating and 80 67 F 27 19 C in cooling Subcooling is based upon head pressure at compressor service port Cooling air and water values can vary greatly with changes in humidity level Table 8a HB Series Typical Unit Operating Pressures and Temperatures 60 Hz I P Units ...

Страница 36: ...IOM Instructions HBH V Compact Heat Controller Inc Unit Operating Pressures and Temperatures Table 8b HB Series Typical Unit Operating Pressures and Temperatures 60 Hz I P Units ...

Страница 37: ...Heat Controller Inc HBH V Compact IOM Instructions Unit Operating Pressures and Temperatures Table 8c HB Series Typical Unit Operating Pressures and Temperatures 60 Hz I P Units ...

Страница 38: ...er Water Flow gpm l m Rise Cooling F C Drop Heating F C For Closed Loop Ground Source or Closed Loop Systems at 3 gpm per ton 3 2 l m per kW 9 12 5 6 7 4 8 2 2 4 4 For Open Loop Ground Water Systems at 1 5 gpm per ton 1 6 l m per kW 20 26 11 1 14 4 10 17 5 6 9 4 Table 8d HB Series Typical Unit Operating Pressures and Temperatures 60 Hz I P Units ...

Страница 39: ... filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan motor and reduce air flow resulting in poor performance It is especially important to provide consistent washing of these filters in the opposite direction of the normal air flow once per month using a high pressure wash similar to those found at self serve car washes Condensate Drai...

Страница 40: ...in cooling Check fan motor operation and airflow restrictions Too high of external static Check static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp within design parameters X Improper temperature limit setting 30 F vs 10 F 1 C vs 12 C Normal airside applications will require 30 F 1 C only X X Bad thermistor Check temp and impedance correlation per c...

Страница 41: ...exchanger Perform Scaling check and clean if necessary X X Inlet Water too Hot or Cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace in heating Check fan motor operation and airflow restrictions Too high of external static Check static vs blower table X Reduced or no water flow Check pump operation o...

Страница 42: ...E SUCTION HWG HEATING CYCLE ANALYSIS PSI SAT PSI SAT F F AIR COIL F F FP2 HEATING LIQUID LINE F EXPANSION VALVE AIR COIL F F PSI SAT PSI SAT F F F F WATER IN WATER OUT PSI PSI F F WATER IN WATER OUT PSI PSI Look up pressure drop in I O M or spec catalog to determine flow rate Look up pressure drop in I O M or spec catalog to determine flow rate Use 500 for water 485 for antifreeze FILTER DRIER FLA...

Страница 43: ...04 2009 01 2010 ...

Отзывы: