Heat Controller A-VMH36QC-1 Service Скачать руководство пользователя страница 20

20

Installation Manual 

VMH SerieS

 

Heat Controller, Inc.

POWER

L N

TO  A

TO  B

L(A)

L(B)

N(A)

N(B)

S(A)

S(B)

One-two models:

One-three models:

One-four models:

One-five models:

Fig.55

POWER

L N

S(A)

L(A) N(A)

TO A

L(C) N(C) S(C)

L(B) N(B) S(B)

TO B TO C 

POWER

TO A

L N

L(A) N(A) S(A)

TO B TO C  TO D

L(B)

L(C)

L(D)

N(B)

N(D)

N(C) S(C)

S(D)

S(B)

NOTE:please refer to the following figures,if the client want wire by themselves.

ELECTRICAL  WORK

27

POWER

L2

S

L2

L1

L1

SUPPLY

L1(A)

L1(A)

L1(C)

L1(C)

L1(D)

L1(A)

L1(A)

L1(D)

L1(E)

L1(B)

L1(B)

L1(B)

L1(B)

L1(C)

L2(A)

L2(A)

L2(C)

L2(C)

L2(D)

L2(A)

L2(A)

L2(D)

L2(E)

L2(B)

L2(B)

L2(B)

L2(B)

L2(C)

S(A)

S(A)

S(C)

S(C)

S(D)

S(A)

S(A)

S(D)

S(E)

S(B)

S(B)

S(B)

S(B)

S(C)

S

TO A TO B

S

L2

L2

POWER

S

TO  A

L2

L1

L1

L2

SUPPLY

TO C

TO B

S

S

L2

L2

L1

L1

POWER

POWER

Y/G

Y/G

Y/G

TO A

TO A TO B

L1 L2

SUPPLY

SUPPLY

Y/G

Y/G

Y/G

Y/G

Y/G

Y/G

TO B

TO C

TO C

TO D

TO D

TO E

L1 L2

Model A

Model A

Model A

Model A

Model B

Magnetic ring(not supplied,

optional part)

Model B

Model B

Model B

TO E

TO D

TO C 

L(C)

L(D) N(D)

N(C) S(C)

S(D) L(E) N(E) S(E)

POWER

L

N

TO B

TO A

L(B) N(B) S(B)

L(A) N(A) S(A)

(Used to hitch to the connective 

cable of indoor and outdoor 

units after installation.)

Ferrile Core Filter

Содержание A-VMH36QC-1 Service

Страница 1: ...87 2100 www heatcontroller com INSTALLATION MANUAL Indoor Models B VCH12FC 1 B VCH18FC 1 B VMH09FC 1 B VMH12FC 1 B VMH18FC 1 Version C InverterFlex Ductless Mini Split Heat Pumps High Wall and Ceiling...

Страница 2: ...ct improvement The actual shape should prevail Contact an authorised service technician for repair or maintenance of this unit Contact an authorised installer for installation of this unit The air con...

Страница 3: ...llow the local national wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found...

Страница 4: ...ominal Capacity 18 18kBtu H 27 27kBtu H 36 36kBtu H D Dual Zone T Tri Zone Q Quad Zone Indoor Models B vmh09Fc 1 Indoor Inverter Heat Pump M Mini Split high wall mount C Ceiling cassette Capacity 09 0...

Страница 5: ...1x1 9k 12k 18k Dual 1x2 9k 9k 9k 12k Indoor unit combinations for A VMH27TC 1 Comb Combinations Unit A Unit B Unit C TRI 1x1 9k 12k 18k TRI 1x2 9k 9k 9k 12k 9k 18k 12k 12k TRI 1x3 9k 9k 9k Indoor uni...

Страница 6: ...al wall mounted wireless thermostat that can take the place of the wireless remote controller CAUTION INSTALLATION INSTRUCTIONS 5 CAUTIONS One Two One Three One Four One Five More than 12cm Air filter...

Страница 7: ...8 9 52 1 4 6 35 5 16 5ft 10 33ft 15 50ft 20 0 2 oz ft 12K 18K 1 2 12 7 1 4 6 35 Max Total length for all rooms Dual zone m Tri zone m Quad zone m 30 100ft 45 150ft 60 200ft NOTES Capacity test is base...

Страница 8: ...Fig 1 1 Selecting Installation Place 2 Four way cassette type 1 Install the main body A The existing ceiling to be horizontal a Please cut a quadrangular hole of 600 600mm in the ceiling according to...

Страница 9: ...5 Seal outdoor heat pumps only Drain Joint FERRILE COR FILTER clip on optionally installed on the communication cable between the indoor and outdoor unit to reduce EMI RFI noise FLARE NUT ADAPTER 3 8...

Страница 10: ...ike 3 Connective Pipe and Drainage Installation 1 Run the drain hose sloping downward Do not install the drain hose as illustrated in Fig 7 Drainage Fig 7 Do not block water flow by a rise Do not put...

Страница 11: ...dle the tubing connecting cable and drain hose with tape securely evenly as shown in Fig 11 Because the condensed water from rear of the indoor unit is gathered in ponding box and is piped out of room...

Страница 12: ...to see that it is securely fastened see Fig 12 3 For easier installation separate the bottom of the indoor unit from the wall by inserting a spaces such as a piece of foam between the unit and the wa...

Страница 13: ...allation hooks from the height of ceiling then cut off the unnecessary part If the ceiling is extremely high please determine the length of the installation hook according to facts Cut the installatio...

Страница 14: ...against the wall or on bulgy objects Never crash or strike it a Slide two grid switches toward the middle at the same time and then pull them up Refer to Fig 21 o b Draw the grid up to an angle of abo...

Страница 15: ...of the ceiling s opening Guarantee that hooks of four corners are fixed well f Keep fastening the screws under the panel hooks until the thickness of the sponge between the body and the panel s outle...

Страница 16: ...oor installation precaution INSTALLATION INSTRUCTIONS 530 560 290 335 624 366 590 333 760x590x285 845x700x320 900x860x315 990x965x345 Outdoorunitdimension mm L1xHxW1 L2 mm W2 mm Mountingdimensions Out...

Страница 17: ...he following procedure A Cut the pipes and the cable 1 Use the piping kit accessory or pipes purchased locally 2 Measure the distance between the indoor and the outdoor unit 3 Cut the pipes a little l...

Страница 18: ...rench as shown in Fig 51 52 Caution Excessive torque can break nut depending on installation conditions Outer diameter in mm A in mm Max Min o 1 4 6 35 0 5 1 3 0 276 0 7 o 3 8 9 35 0 63 1 6 0 394 1 0...

Страница 19: ...nect the communication cable to each indoor unit then to the appropriate terminal block on the outdoor unit Ensure that the wiring matches between indoor and outdoor units 4 Use the cable clamp on the...

Страница 20: ...A L1 D L1 E L1 B L1 B L1 B L1 B L1 C L2 A L2 A L2 C L2 C L2 D L2 A L2 A L2 D L2 E L2 B L2 B L2 B L2 B L2 C S A S A S C S C S D S A S A S D S E S B S B S B S B S C S TO A TO B S L L L2 L2 POWER S TO A...

Страница 21: ...both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage Unit charge is located on the rating plate Unit is precharged to include enough refrigerant for 16 5 f...

Страница 22: ...operation of the vacuum pump Evacuate for 15 minutes or more and check that the compound meter indicates 29 92 inHg 1x105Pa 6 Turn the stem of the packed valve B about 45 counterclock wise for 6 7 se...

Страница 23: ...by a soft brush to check for leakage of the connecting points of th piping If bubbles come out the pipes have leakage 2 Leak detector Use the leak detector to check for leakage Safety and leakage che...

Страница 24: ...e taken Manual operation is used only when the remote controller is disable or maintenance necessary Press the Manual control button to select the AUTO or COOL the unit will operate under Forced AUTO...

Страница 25: ...25 Heat Controller Inc VMH Series Installation Manual 04 2009 10 2012...

Отзывы: