Heat Controller 7602-444 Скачать руководство пользователя страница 4

4

Operating Manual 

7602-444 SERVICE TOOL

 

Heat Controller, Inc.

2.0  Menu Structure

System Confi guration
 Airfl ow Selection
  

Option Selection

  

Unit Confi guration

 Valve 

Confi guration

Service Mode 
 Manual 

Operation

 Control 

Diagnostics

 Dipswitch 

Confi guration

 Fault 

History

 

Clear Fault History

Menu Structure

Start-up Screen

System Confi guration Menu

SERVICE TOOL MENU

SYSTEM CONFIG

SERVICE MODE

ACDU01                                                        1.00

SELECT OPTION   

SYSTEM CONFIGURATION

OPTION SELECTION

UNIT CONFIG

SELECT OPTION   

 PREVIOUS                                        SELECT 

3.0  System Confi guration

Use the System Confi guration option on the start-up screen 
to adjust critical equipment settings.

The System Confi guration information will be automatically 
obtained from each communicating control in the system.

Note 1: The Airfl ow Selection menu (section 3.1) will not be 
present if the connected communicating control is confi gured 
for No Blower.

Note 2: 

The Valve Confi guration menu (section 3.4) will 

not be present if the connected communicating control is 
confi gured for No Loop Confi guration (OTHER). 

3.1 AIRFLOW 

S

ELECTION

Adjust the airfl ow settings for each system operating mode 
using the up/down arrow buttons.  Press the center button to 
select each item.
 • 

Airfl ow Settings (defaults stored in control) - 

 

 

valid range:  obtained from control (in 25 CFM   

  

increments)

 

•  Blower Off Delay (default 60 seconds) – valid 

 

 

range:  0 to 255 seconds (in 5 second increments)

NOTE 1:  The Airfl ow Settings will only be present if the 
connected communicating control is confi gured for ECM 
blower.

Содержание 7602-444

Страница 1: ...Heat Controller Inc 1900 Wellworth Ave Jackson MI 49203 517 787 2100 www heatcontroller com OPERATION MANUAL 7602 444 Communicating Service Tool...

Страница 2: ...3 1 Airflow Selection 4 3 2 Option Selection 5 3 3 Unit Configuration 5 3 5 Valve Configuration 5 4 0 Service Mode 6 4 1 Manual Operation 6 4 2 Control Diagnostics 6 4 3 Dipswitch Configuration 7 4 4...

Страница 3: ...1 Configure items like airflow heat pump options and configuration unit family unit size etc AND 2 Diagnose the unit by operating it manually performing control diagnostics viewing dip switch configu...

Страница 4: ...information will be automatically obtained from each communicating control in the system Note 1 The Airflow Selection menu section 3 1 will not be present if the connected communicating control is co...

Страница 5: ...nfiguration settings including Heat Pump Family Heat Pump Size Blower Type and Loop Configuration using the up down arrow buttons Press the center button to select each item Heat Pump Family default s...

Страница 6: ...e heat pump at the thermostat Navigate between diagnostic screens using the left right arrow buttons SERVICE MODE MANUAL OPERATION CONTROL DIAGNOSTICS DIPSWITCH CONFIG FAULT HISTORY CLEAR FAULT HISTOR...

Страница 7: ...TSTAT 4 ON RV O THERMOSTAT 5 ON DEHUMID OFF 6 ON EH2 AUX HEAT 7 ON BOILERLESS 8 ON SEE DXM2 AOM PREVIOUS NEXT CONTROL CONFIGURATION DIPSWITCH S2 1 ON ACCESSORY 1 2 ON ACCESSORY 2 3 ON 4 ON ACCESSORY 2...

Страница 8: ...MP HEAT 1 11 11 AM 11 14 FAULT TEMP CONDITIONS FAULT FLOW CONDITIONS FAULT I O CONDITIONS FAULT CONFIG COND FAULT POSSIBLE CAUSES PREVIOUS SELECT FAULT TEMPERATURE CONDITIONS LT1 LOW WATER TEMP HEAT 1...

Страница 9: ...ult History will clear all fault codes stored in the thermostat as well as the fault history in any connected communicating controls DXM2 AXM FAULT CONFG CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM...

Страница 10: ...Date Page Description 17 Sept 12 All First Published Revision History 9 17 12 97B0106N03 97B0106N03...

Отзывы: