27
Heat & Glo • SL-5/5LP-IFT, SL-7/7LP-IFT, SL-9/9LP-IFT Installation Manual • 2632-980 Rev. E • 4/21
Two Elbows
Top Vent - Horizontal Termination - (continued)
Note
: Use SLP Series
components only.
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
Fire Risk.
• When using SLP-HRC-SS termination cap
on top vented fireplaces, a one foot minimum
vertical vent section is required before installing
first elbow.
WARNING *
V Minimum
H
1
+ H
2
Maximum**
SL-5-IFT
SL-7-IFT
SL-9-IFT
90 Elbow *
1/2 ft. 152 mm 1/2 ft. 152 mm 0 ft.
0 mm
1/2 ft.*
152 mm 1 ft. 305 mm
1 ft.
305 mm 1 ft.
305 mm
1-1/2 ft.
457 mm 2 ft. 610 mm
2 ft.
610 mm 2 ft.
610 mm
2-1/2 ft.
762 mm 4 ft.
1.2 m
4 ft.
1.2 m
4 ft.
1.2 m
3-1/2 ft.
1.1 m
6 ft.
1.8 m
6 ft.
1.8 m
6 ft.
1.8 m
4-1/2 ft.
1.4 m
14 ft.
4.3 m
14 ft.
4.3 m
14 ft.
4.3 m
H + H
1
MAX. =14 ft. (4.3 m)
V + H + H
1
MAX. = 40 ft. (12.2 m)
*See warning below
Figure 4.13
**
Note
: When using
SLP-FLEX (6-5/8 in.)
venting, there
MUST be a 25% reduction in total H when using flex vent.
See Figure 4.8.