July 12, 2006

Page  5

Heat & Glo · Mission Bay · 250-7512F

NOTE:

  The  following  requirements  reference  various 

Massachusetts and national codes not contained in this 

document.

For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in whole 

or in part for residential purposes, including those owned or 

operated  by  the  Commonwealth  and  where  the  side  wall 

exhaust vent termination is less than seven (7) feet above 

finished grade in the area of the venting, including but not 

limited  to  decks  and  porches,  the  following  requirements 

shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter shall 

observe that a hard wired carbon monoxide detector with an 

alarm and battery back-up is installed on the floor level where 

the gas equipment is to be installed. In addition, the installing 

plumber or gas fitter shall observe that a battery operated or 

hard wired carbon monoxide detector with an alarm is installed 

on each additional level of the dwelling, building or structure 

served by the side wall horizontal vented gas fueled equip-

ment. It shall be the responsibility of the property owner to 

secure the services of qualified licensed professionals for the 

installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled 

equipment is installed in a crawl space or an attic, the hard 

wired carbon monoxide detector with alarm and battery back-

up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not 

be met at the time of completion of installation, the owner shall 

have a period of thirty (30) days to comply with the above 

requirements; provided, however, that during said thirty (30) 

day period, a battery operated carbon monoxide detector with 

an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 and 

be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently 

mounted to the exterior of the building at a minimum height 

of eight (8) feet above grade directly in line with the exhaust 

vent terminal for the horizontally vented gas fueled heating 

appliance or equipment. The sign shall read, in print size no 

less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

Î

G.  Requirements for the Commonwealth of     

      Massachusetts

Inspection

The state or local gas inspector of the side wall horizontally 

vented gas fueled equipment shall not approve the installa-

tion unless, upon inspection, the inspector observes carbon 

monoxide detectors and signage installed in accordance with 

the provisions of 248 CMR 5.08(2)(a) 1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a) 

1 through 4:

The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition of 

NFPA 54 as adopted by the Board; and 

Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separated from 

the dwelling, building or structure used in whole or in part 

for residential purposes.

MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided

When  the  manufacturer  of  Product  Approved  side  wall 

horizontally vented gas fueled equipment provides a vent-

ing system design or venting system components with the 

equipment, the instructions provided by the manufacturer for 

installation  of  the  equipment  and  the  venting  system  shall 

include:

Detailed instructions for the installation of the venting sys-

tem design or the venting system components; and 

A  complete  parts  list  for  the  venting  system  design  or 

venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall hor-

izontally vented gas fueled equipment does not provide the 

parts for venting the flue gases, but identifies “special vent-

ing systems”, the following requirements shall be satisfied by 

the manufacturer:

The referenced “special venting system” instructions shall 

be included with the appliance or equipment installation 

instructions; and 

The “special venting system” shall be Product Approved 

by the Board, and the instructions for that system shall 

include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all vent-

ing instructions, all parts lists for venting instructions, and/or 

all  venting  design  instructions  shall  remain  with  the  appli-

ance or equipment at the completion of the installation.

See  Gas  Connection  section  for  additional  Common-

wealth of Massachusetts requirements.

Содержание MISSION-BAY

Страница 1: ...ing property damage personal injury or death This appliance may be installed as an OEM installation in manufactured home USAonly ormobilehomeandmustbeinstalledinaccordancewith the manufacturer s instr...

Страница 2: ...APPAREIL POUR ASSISTANCE OU DES INFORMATIONS SUPP L MEN TAIRES CONSULTEZ UN INSTALLATEUR QUALIFI UNE AGENCE DE SERVICE OU UN FOURNISSEUR DE GAZ CAUTION HOT WHILE IN OPER ATION DO NOT TOUCH SEVERE BURN...

Страница 3: ...on 6 Gas Information A Fuel Conversions 22 B Gas Pressures 24 C Gas Connection 24 Section 7 Electrical Information A Recommendation for Wire 26 B Connecting to the Appliance 26 C Standing Pilot Igniti...

Страница 4: ...ss WARNING Do NOT use this appliance if any part has been under water Immediately call a quali ed service technician to inspect the appliance and to replace any part of the control system and any gas...

Страница 5: ...nt terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBS...

Страница 6: ...face Remove log set and component pack from rebox Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the instal la...

Страница 7: ...e Risk Provide adequate clearance Around air openings To combustibles For service access Locate appliance away from traf c areas NOTE For actual appliance dimensions refer to Section 12 Fire Risk Loca...

Страница 8: ...12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7 5 Over 20 12 to 21...

Страница 9: ...ations a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and only permitted if veranda porch deck or balcony is fully open on...

Страница 10: ...h vertical and horizontal vent aspects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect See Figure 5 1 Two 45 elbows may be used in place of one...

Страница 11: ...A single vertical to horizontal 90 elbow is already calculated into the allowable 15 ft 5m run Each additional 90 elbow reduces the maximum horizontal distance by 3 ft 914mm Example The use of three e...

Страница 12: ...so they match and slide into the entry slots on the male ends see Figure 5 4 Push the pipe sections completely together then twist lock one section clockwise approximately one quarter turn until the t...

Страница 13: ...ilt in The pilot hole will be 2 in 51mm closer to the bottom of the square than the top Using a framing square draw a 14 in x 14 in 356mm x 356mm square around the pilot hole See Figure 5 7 WOOD SCREW...

Страница 14: ...ion cap must be sealed with silicone Termination caps shall not be recessed into a wall or siding Step 1 Check the installation instructions for required 1 in 25mm clearances air space to combustibles...

Страница 15: ...b bob from the roof to the hole previously drilled in the ceiling and mark the spot where the vent will penetrate the roof Determine if ceiling joists roof rafters or other framing will obstruct the v...

Страница 16: ...in the current CAN CGA B149 Installation Codes in Canada the National Fuel Gas Code NFPA 54 ANSI Z223 1 in USA or local codes Note that for steep roof pitches the vent height must be increased See Roo...

Страница 17: ...3mm GREATER IN SIZE THAN PATTERN OF SUPPORT BOX AS IT IS PROJECTED ONTO ROOF LINE Figure 5 17 Step 1 Follow installation Steps 1 and 2 under vertical installation section pages 14 15 Step 2 Remove shi...

Страница 18: ...e the four corners and the overlapping sections of the trim collar to the ceiling You may want to predrill the holes for the overlapped sections for ease of installation Figure 5 19 3 Class A Metal Ch...

Страница 19: ...et metal screws Step 7 The connection between the appliance and the retro connector may be completed with sections of direct vent pipe Step 1 Before cutting any holes assemble the desired sections of...

Страница 20: ...to the top adapter using three sheet metal screws Figure 5 21 page 18 Step 6 Feed the flex liner through the flashing into the chimney Carefully feed the flex liner down the chimney to the bottom and...

Страница 21: ...ING IN MASONRY WALL THREE MASONRY BOLTS NOT INCLUDED RETRO CONNECTOR FOUR MASONRY BOLTS NOT INCLUDED RETRO CONNECTOR WALL THIMBLE COVER Step 10 Slide wall thimble cover over retro connector and secure...

Страница 22: ...installed It is only necessary to remove the left brick panel for burner removal Loosen the shutter adjustment wingnut located underneath the appliance It is helpful to remove the nut completely Slide...

Страница 23: ...g screws A pressure regulator tower B and diaphragm C Figure 6 6 Ensure that the rubber gasket D is properly posi tioned and install the new HI LO pressure regulator assem bly to the valve using the n...

Страница 24: ...e pressure is greater than 1 2 psig NOTE A listed and Commonwealth of Massachusetts approved 1 2 inch 13mm T handle manual shut off valve and exible gas connector are connected to the 1 2 inch 13mm co...

Страница 25: ...ting appliance it will take a short time for air to purge from lines When purging is complete the appliance will light and operate normally Air only needs to be purged again if gas valve has been turn...

Страница 26: ...rmostat see individ ual thermostat instructions to ensure proper operation of appliance 4 Use low resistance thermostat wire for wiring from igni tion system to the wall switch and thermostat 5 Use th...

Страница 27: ...g controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Ignitor VALVE Thermopi le Gas Pilot Ignitor Thermocouple Red 28 in 711mm Switch ON OFF Red 2...

Страница 28: ...liance C Door Crown Installation D Grille Installation 2 Screws 2 Vis 2 Screws 2 Vis Figure 8 1 Remove door from appliance Remove existing black crown by removing the four screws indicated from the ba...

Страница 29: ...care as breakage can easily occur PLEASE NOTE Logs have been designed to work specifically with the burner of this appliance Exact placement will ensure proper operation of your gas appliance and red...

Страница 30: ...action may void the coverage provided by the owner s home insurance CAUTION All wiring should be done by a qualified electrician and shall be in compliance with local codes and with the National Elect...

Страница 31: ...ted inside the pedestal Secure the bracket assembly with the wing nut provided NOTE THE SWITCH BRACKET ASSEMBLY MUST BE INSTALLED SO THAT THE SENSOR SWITCH MAKES CONTACT WITH THE BOTTOM OF THE FIREBOX...

Страница 32: ...Mission Bay 250 7512F BLOWER BLOWER RECEP TACLE BLACK WHITE WHITE GROUND GRN 110 120 VAC BLACK JUNCTION BOX BLACK TEMPER ATURE SENSOR SWITCH BLUE BLACK BLACK VARIABLE SPEED SWITCH GROUND WIRE BLACK B...

Страница 33: ...o adjust the shutter loosen the wingnut Retighten the wingnut after adjustment K Glass Replacement Use only Door and GlassAssembly replacement as speci ed in Section 12 of this manual available from y...

Страница 34: ...T use this appliance if any part has been under water Immediately call a quali ed service technician to inspect the appliance and to replace any part of the control system and any gas control which ha...

Страница 35: ...731 3 5 95 6 0 1 0 0 65 963 7 5 3 1 655 0 76 9 964 0 7731 5 7 5 0 669 6 0 7731 5 5 6 9 46 965 19 0 15 65 963 256 31 0 3 5 95 36 2 1 6 0 76 1 165 6 56 69 1 1 415 6 3 9 6 5 4 33 69 15 3 15 5 9 0 3669 6...

Страница 36: ...uring initial operation Smoke may set off smoke detectors Smoke and odors may be irritating to sensitive individuals CAUTION Prevent accidental appliance operation when not attended Unplug or remove b...

Страница 37: ...e thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocoupl...

Страница 38: ...exhaust gases back into the system Check for proper vent connection at ue collar and all vent joints c Horizontal vent improperly pitched The horizontal vent cap should slope down only enough to prev...

Страница 39: ...by quali ed technician recommended Check Condition of glass glass assembly and glass seal Obstructions of combustion and ventilation air Obstructions of termination cap Burner ignition and operation...

Страница 40: ...ration Sand and repaint as neces sary 2 Replace appliance if rebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off b...

Страница 41: ...mensions are actual appliance dimensions Use for reference only For clearances to combustibles refer to Section 3 Location Inches Millimeters Location Inches Millimeters A 22 1 2 570 E 29 1 8 740 B 10...

Страница 42: ...mm 6 1 2 in 165mm 6 5 8 in 168mm 17 24 in 432 610mm 11 3 4 in 298mm 5 3 4 in 146mm 6 5 8 in 168mm 6 3 8 in 162mm 6 1 2 in 165mm 9 5 8 in 244mm 6 5 8 in 168mm 6 1 2 in 165mm 6 3 8 in 162mm 9 5 8 in 244...

Страница 43: ...nger 950 Vinyl Protector Kit SL Pipe DRC RADIUS Decorative Radius Cover HTI DV WT Wall Thimble 844 9550 Slim Line Wall Thimble TERMINATION KITS SLK 01TRD Trapezoid Termination Kit 7 3 4 inch 11 inch 2...

Страница 44: ...37 Burner Assembly BRNR MB 35 Burner Pan 474 0080 36 Burner Support Kit Left and Right 842 5190 Component pack includes warranty card ON OFF valve mineral wool touch up paint and manual 479 5120 17 C...

Страница 45: ...ver SMART STAT HNG HNG Smart Batt Remote 2 Battery receiver SMART BATT HNG Blower Assembly GFK 160A Glass Assembly GLA MB Item Part Description Alphabetical Order SKU Pedestal Assembly 479 5020 5 Pede...

Страница 46: ...1 6 381 9 2 9 8 B 8 90 6 381 9 3 381 0 3 97 98 8 8 2 373 30 37 8 C 89 9 C 23 A 8 C B 9 3 09 8 2 3 8 8 C 97 98 8 8 7 C 9 2 7 8 0 A2 2 96 A3 2 2 9 9 2 0 9 C 23 A 8 C 86 B 6C 29 3D 8 9 C 38 A 3 381 8C 7...

Страница 47: ...nstructions included Read understand and follow these instruc tions for safe installation and operation Leave this manual with party responsible for use and operation This product may be covered by on...

Отзывы: