background image

Heat & Glo  •  FB-IN, FB-GRAND  •  783-908  Rev. J  •  2/07

31

Troubleshooting (continued)

Symptom

Possible Cause

Corrective Action

3. Continued

c. Defective valve.

Turn the valve knob to the ON position. Place the 
ON/OFF switch in the ON position. Check the millivolt 
meter a the thermopile terminals. The millivolt meter 
should read greater than 125mV. If the reading is ac-
ceptable, and if the burner does not come on, replace 
the gas valve.

d. Plugged burner ori

¿

 ce.

Check the burner ori

¿

 ce for stoppage. Remove stop-

page.

e. Wall switch or wires are defective.

Follow the corrective action in Symptom and Pos-
sible Cause 1.a above. Check the switch and wiring. 
Replace where defective.

4. Frequent pilot outage 
problem.

a. Pilot 

À

 ame may be too high or too low, or blow-

ing out (high pressure), causing pilot safety to drop 
out.

Clean thermocouple and adjust the pilot 

À

 ame for 

maximum 

À

 ame impingement. Follow lighting instruc-

tions carefully.

5. The pilot and main 
burner extinguish while 
in operation.

a.  No LP in tank.

Check the LP (propane) tank. Re

¿

 ll the fuel tank.

b.  Inner vent pipe leaking exhaust gases back into 
the system.

Check venting system for damage. Replace/repair 
improperly assembled pipe sections.

c. Glass too loose and air tight packet leaks in 
corners after usage.

Replace glass panel assembly.

d. Bad thermopile or thermocouple.

Replace if necessary.

e. Improper vent cap installation.

Check for proper installation and freedom from debris 
or blockage.

6. Glass soots.

a. Flame impingement.

Adjust the log set so that the 

À

 ame does not exces-

sively impinge on it.

b. Improper air shutter setting.

Adjust the air shutter located on the control panel.

c. Debris around air shutter.

Inspect the opening at the base of the burner. NO MA-
TERIAL SHOULD BE PLACED IN THIS OPENING.

7.  Flame burns blue 
and lifts off burner.

a. Insuf

¿

 cient oxygen being supplied.

Ensure that the vent cap is installed properly and free 
of debris. Ensure that the vent system joints are tight 
and have no leaks.

Ensure that no debris has been placed at the base of, 
or in the area of the air holes in the center of the base 
pan beneath the burner.

Ensure that the glass is tightened properly on the unit, 
particularly on top corners.

Содержание FB-GRAND

Страница 1: ...tallation in Mobile Homes CAN CSA Z240MH This appliance is only for use with the type s of gas indicated on the rating plate Leave this manual with party responsible for use and operation DO NOT DISCA...

Страница 2: ...led installed in in accordance accordance with with local local codes codes if if any any if if not not follow follow ANSI ANSI Z223 1 Z223 1 in in the the USA USA or or CAN CGA CAN CGA B149 B149 inst...

Страница 3: ...ts 11 B Connecting Vent Pipe 11 C Placing Securing and Leveling the Appliance 12 D Installing Adaptor and Termination Cap 13 8 Gas Information A Fuel Conversions 14 B Gas Pressures 14 C Gas Connection...

Страница 4: ...part has been under water Immediately call a quali ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water This pro...

Страница 5: ...T comply with local regional state and national codes and regulations Consult insurance carrier local building re of cials or authorities having jurisdiction about restrictions installation inspection...

Страница 6: ...nstallation of the insert only when a 1 4 inch airspace is provided between the insert and the oor of outer wrap Figure 3 1 Fireplace Opening NOTE For actual appliance dimensions refer to Section 16 B...

Страница 7: ...ce to all clearance speci cations in manual Fire Risk Odor Risk Clearance to combustible material under the insert is 1 4 inch 0 6 cm Use leveling legs to raise insert minimum 1 4 inch above combustib...

Страница 8: ...12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 Figure 4 1 Minimum height from roof to lowest discharge opening 4 4 T...

Страница 9: ...peration of this appliance or other appliances connected to the ue Vent this appliance directly outside Use separate vent system for this appliance B Horizontal Venting Horizontal venting is NOT allow...

Страница 10: ...d fuels unless all original parts have been replaced and the replace re approved by the authority having jurisdiction F Remote Control The receiver for the remotes must be installed BETWEEN the base p...

Страница 11: ...e factory installed 3 inch collar in the stainless steel section of pipe see Figure 7 1 Use 3 screws to attach either a 4 foot or 30 foot section of inlet air vent to the inlet collar on the collar sl...

Страница 12: ...r to shorten Install fiberglass insulation pieces to back face of surround Attach surround Follow instructions accompanying surround Push insert so that surround becomes tight against face of replace...

Страница 13: ...with self tapping screws included in kit Figure 7 4 To help eliminate cold air drafts it may be necessary to place non combustible insulation around the ues as they go though the damper Note The LINK...

Страница 14: ...sig Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1 2 psig Verify inlet pressures High pressure may cause over re condition Low pressure may c...

Страница 15: ...e check with the local gas utility If installing this appliance at an elevation above 4500 feet in Canada check with local authorities CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk Ch...

Страница 16: ...perate It is recommended that a 110 VAC junction box be connected for use with fan or remote control See Figure 9 2 for junction box wiring Prevent accidental appliance operation when not attended Unp...

Страница 17: ...nsert is required Detach exible liner from back of unit if insert is installed Remove the four screws on the cover plate see Figure 9 3 Figure 9 3 FAN COVER PLATE POWER CORD GROUND WIRE Bend up the ta...

Страница 18: ...UST BE REPLACED IT MUST BE REPLACED WITH TYPE 1050 C RATED WIRE JUNCTION BOX VARIABLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BLOWER RECEPTACLE BLK BLK BLK BLK WHT G...

Страница 19: ...ow voltage wires and ON OFF switch at tached to outer right side of the insert see Figure 10 2 2 Disconnect the ON OFF switch from the low voltage wire leads and insert the ON OFF switch through the h...

Страница 20: ...e used safely D Ember Placement Explosion Risk Follow ember placement instructions in manual Do NOT place embers directly over burner ports Replace ember material annually Improperly placed embers int...

Страница 21: ...locate the logs with respect to the grate assembly Please refer to grate assembly LOG NUMBER 1 SRV768 701 Place log 1 onto the grate Push log back until it rests against locating tabs B and D E D B A...

Страница 22: ...ss both at spots on log 1 and log 3 with the Y in log 4 placed on log 1 The back of log 4 should make contact with the back of the rebox LOG NUMBER 2 SRV768 704 Position log 2 onto grate such that tab...

Страница 23: ...03 GRATE ASSEMBLY This model uses locating tabs to positively locate the logs with respect to the grate assembly Please refer to grate assembly LOG 1 SRV773 701 Position log 1onto the grate such that...

Страница 24: ...face of log LOG 3 SRV768 704 Position log 3 onto grate such that the tabs D and E t into the slots on bottom surface of log and the right back side of log is ush against tab F LOG 4 SRV573 702 Place l...

Страница 25: ...door on the appliance Fasten the latches on the glass frame FIREBOX SURROUND LOCATING TABS G Air Shutter Setting Optimal ame appearance is dependent on the air shutter setting Adjustments should be m...

Страница 26: ...r to the owner s information manual provided with this appliance For assistance or additional information consult a quali ed installer service agency or the gas supplier Do NOT use this appliance if a...

Страница 27: ...combustion and ventilation air If not installed operated and main tained in accordance with the man ufacturer s instructions this product could expose you to substances in fuel or fuel combustion whic...

Страница 28: ...roducts used in the paint and logs During this break in period it is recommended that some windows in the house be opened for air circulation This will help avoid setting off smoke detectors and help...

Страница 29: ...ensation on the glass This is a result of gas combustion and temperature variations As the appliance warms this condensation will disappear Blue ames This is a result of normal operation and the ames...

Страница 30: ...impingement Ensure that the thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt meter lead w...

Страница 31: ...k Check the LP propane tank Re ll the fuel tank b Inner vent pipe leaking exhaust gases back into the system Check venting system for damage Replace repair improperly assembled pipe sections c Glass t...

Страница 32: ...embly with care NOTE Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white lm on glass CAUTION When cleaning glass door Avoid striking scrat...

Страница 33: ...aint as necessary 2 Replace appliance if rebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect fo...

Страница 34: ...16 in 71 mm 9 9 16 in 142 mm REF 15 15 Reference Materials A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only For framing dimensions and clearances refer...

Страница 35: ...ex Liner Kits Figure 15 3 Direct Vent Flex Liner Accessory Kits Direct Vent Flex Liner Accessory Kits see Figure 15 3 Flash Damp Zero clearance damper ashing kit for use with LINK DV 30B or LINK DV4 3...

Страница 36: ...roduct or added thereafter are NOT covered by this warranty unless expressly authorized and approved by HEAT GLO in writing 6 Any damages caused by environmental conditions inadequate ventilation or d...

Страница 37: ...___________________________________________________ ________________________________________________________________________________ Printed in U S A Copyright 2006 This product may be covered by one...

Отзывы: