Heat & Glo LifeStyle 8000TVD Скачать руководство пользователя страница 12

12

Step 3. Negative Pressure Make-up Air

Negative Pressure warning

:  When negative pressure is

present, an atmospherically vented fireplace (with a draft
hood) may not function properly and it may down draft. In
the case of a gas appliance, spillage of the combustion
gases may occur. 

This may create a dangerous carbon

monoxide situation in the house.

The causes of negative pressure to a house can include
the following:

Stack effect in the building.

Exhaust only appliances (mechanically and
atmospherically vented).

Inadequate make-up air (which is increasingly
more prevalent in new construction).

NOTE: 

This fireplace will operate correctly only if adequate

ventilation is provided to allow proper draft to the fireplace
system. Heat-N-Glo assumes no responsibility for the
improper performance of the fireplace system caused by
inadequate draft due to environmental conditions, down
drafts, tight sealing construction of the structure, or
mechanical exhausting devices which create a negative air
pressure within the structure where the fireplace is located.

It is recommended that all natural venting non-air tight gas
fireplaces have outside air connected to them. It is also
recommended that the building be mechanically or passively
balanced to allow atmospherically vented appliances, such
as top vented gas fireplaces with draft hoods, to draft
properly. If the home experiences negative pressure or is
likely to experience negative pressure, connection to an
outside air source is mandatory.

Installing Optional Outside Make-up Air:

This unit is equipped to accept outside air. By using outside
make-up air, the amount of room air used for combustion
will be reduced. It is recommended that an AK-TV air kit be
used with this appliance.

WARNING: IN A NEGATIVE PRESSURE CON-
DITION (LIKELY TO OCCUR IN NEW HOMES
THAT DO NOT HAVE  ADEQUATE MAKE-UP
AIR) THE OUTSIDE AIR KIT MUST BE IN-
STALLED TO OBTAIN PROPER PERFOR-
MANCE AND TO HELP PREVENT SPILLAGE
OF COMBUSTION GASES.

Air Damper

Before lighting the burner, open the damper. Close the
damper when the burner is off.

Detailed installation instructions for Model AK-TV Outside
Air kit are found in the kit.

Figure 4.  Make-up Air

!

A 4-inch side collar/damper (found in AK-TV Kit) must be
installed on the fireplace by attaching the side collar to the
outer wrap of the fireplace at the right-hand rear corner using
sheetmetal screws. See Figure 4. Attach one end of a 4-
inch flexible air duct (not provided in the AK-TV Kit) to the
side collar and the other end of the duct to the make-up air
termination cap. Use plastic tie straps to secure the ends
of the flex duct to each collar.

AIR DAMPER

ASSEMBLY

4-INCH DUCT

COLLAR

Содержание 8000TVD

Страница 1: ...iters Laboratories Listed 379 900I 1 04 READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE THIS INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE Please contact your Heat N...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...ystem Approvals 13 B System Components 13 C Bedroom Installation in Canada 14 D Vent Termination 14 Step 5 Positioning Leveling and Securing the Fireplace 14 Step 6 The Gas Control Systems 14 Step 7 T...

Страница 4: ...um ros de pi ce se trouve la page suivante 10 11 12 13 14 16 15 17 4 6 2 1 3 8 7 9 Log Set Assembly 18 5 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts 8000TVD Beginning Manufa...

Страница 5: ...he 1 SRV582 701 11 Log 2 B che 2 SRV582 703 12 Log 3 B che 3 SRV582 702 13 Log 4 B che 4 SRV582 704 14 Log 5 B che 5 SRV402 701 15 Log 6 B che 6 SRV582 706 16 Log 7 B che 7 SRV582 707 17 Log 8 B che 8...

Страница 6: ...Allumeur pi zo 291 513 4 Pilot Assembly NG Module de veilleuse GN 485 510A 4 Pilot Assembly LP Module de veilleuse PL 485 511A 5 Valve Bracket Parenth se de Valve 550 169 6 Orifice NG 32C Assembl e d...

Страница 7: ...ilot Assembly LP Module de veilleuse PL PRE 002324001 POST 002324001 385 511A 4021 026 5 Valve Bracket Parenth se de Valve PRE 002324001 POST 002324001 385 169 2025 101 6 Ground Strap Courroie de Rais...

Страница 8: ...particular installation Refer to the National Fuel Gas Code ANSI Z223 1 NFPA54 1Approvals and Codes current edition The Uniform Mechanical Code current edition and local Building Officials for the op...

Страница 9: ...Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the followi...

Страница 10: ...3 8 1026mm 9 1 8 233mm GAS LINE ACCESS 43 1091mm 48 3 8 1229mm 3 1 2 89mm 8 3 8 212mm ELECTRICAL ACCESS 21 1 2 548mm 9 1 2 241mm 35 1 2 902mm 17 3 4 450mm 6 152mm B VENT VENT COLLAR STANDOFFS HOOD GAS...

Страница 11: ...ew heads that secure the unit together A 49 B 40 1 2 C 22 Figure 3 Framing Dimensions Minimum Clearances from the B Type Vent Pipe to Combustible Materials is 1 25mm all around the pipe Step 2 Framing...

Страница 12: ...ely balanced to allow atmospherically vented appliances such as top vented gas fireplaces with draft hoods to draft properly If the home experiences negative pressure or is likely to experience negati...

Страница 13: ...lar Look at the vent pipe through the holes in the 10 5 8 ring to check that the vent pipe is attached NOTE It is always better to first attach a straight section of vent to the unit before attaching...

Страница 14: ...replace Place the fireplace into position see Figure 7 Level the fireplace from side to side and from front to back Shim the fireplace with non combustible material such as sheet metal as necessary Se...

Страница 15: ...ireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn Step...

Страница 16: ...he desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 1 10 120 VAC TO THE W...

Страница 17: ...The fireplace can be used as necessary Once power 110 VAC is re stored disconnect red and black wire leads to extend bat tery life Optional Accessories Optional fan and remote control kits require tha...

Страница 18: ...e materials can be used to cover up the gap between the sheet rock and the fireplace Do not obstruct or modify the air inlet outlet grilles When overlapping on both sides leave enough space so that th...

Страница 19: ...8 hours This will help to cure the chemicals used in the paint and logs Heat N Glo fireplaces manufactured with tempered glass may be installed in hazardous locations such as bathtub enclo sures as de...

Страница 20: ...lly By Qualified service technician Task Make a visual check of the straight flame sensor rod see Figure 33 Use emery cloth to carefully remove any existing film or white deposits Checking Flame Patte...