HearthRite HR06MN-1 Скачать руководство пользователя страница 5

5

       WARNING:   Rework  worksheet, add-
ing  the  space  of  the  adjoining
unconfined  space.  The  combined  spaces
must   have  enough  fresh air  to supply  all
appliances  in  both  spaces.

VENTILATION  AIR
Ventilation  Air  From  Inside Building
This  fresh  air  would  come  from  an
adjoining  unconfined  space.  When
ventilating   to  an  adjoining  unconfined
space, you  must  provide  two permanent
openings: one  within  12

"

  of  the  ceiling

and  one  within  12

"

  of  the  floor  on  the

wall  connecting  the  two  spaces  (see
options 1 and 2,  Figure  2). You  can  also
remove  door  into  adjoining  room (see
option 3, Figure 2). 

Follow  the  National

Fuel  Gas  Code  NFPA 54/ANS Z223.1.
Section  5.3,  Air  for  Combustion  and
Ve n t i l a t i o n    f o r     r e q u i r e d   s i z e   o f
ventilation  grills  or  ducts

 Example:
 Gas  water  heater          40,000        Btu/Hr
 Vent  free  heater    +      10,000        Btu/Hr
 total                         =      50,000       Btu/Hr

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                        Btu/Hr
     Gas furnace                                                              Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas Fireplace logs                                                   Btu/Hr
     Other gas appliances* +                                          Btu/Hr
    Total                                =                                        Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.

4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.
                          Btu/Hr (maximum the space can support)
                         Btu/Hr (actual amount of Btu/Hr used)
         

Example :  46,100 Btu/Hr(maximum the space can support)

                           50,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From

Inside  Building, page 5.
B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors, page 6 .

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

AIR  FOR  COMBUSTION  AND
VENTILATION

Continued

Содержание HR06MN-1

Страница 1: ...performed by a qualified installer service agency or gas supplier Table of Contents ImportantSafetyInformation 2 Product Features 3 ProperVentilation FreshAir 4 Installation 6 OperatingYourHeater 10 C...

Страница 2: ...WARNING Do not use any accessory not approved for use with this heater WARNING Any change to this heater or its controls can be dangerous 1 This appliance is only for use with the type of gas indicate...

Страница 3: ...t has complied with all the requirements of the authority having jurisdiction State of Massachsetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachuset...

Страница 4: ...ods described in the National Fuel Gas Code ANS Z223 1 Section 5 3 or applicable local codes Unusually Tight Construction The air that leaks around doors and windows may provide enough fresh air for c...

Страница 5: ...n the space Vent free heater Btu Hr Gas water heater Btu Hr Gas furnace Btu Hr Vented gas heater Btu Hr Gas Fireplace logs Btu Hr Other gas appliances Btu Hr Total Btu Hr Do not include direct vent ga...

Страница 6: ...shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the CSA AGA design certified equipment shutoff valve from your dealer CAUTION If you install the heater i...

Страница 7: ...one of two ways 1 Attaching to wall stud 2 Attaching to wall anchor Attaching to Wall Stud This method provides the strongest hold Insert mounting screws through mounting bracket and into wall studs A...

Страница 8: ...aching Mounting Bracket To Wall Note Wall anchors mounting screws and spacers are in hardware package The hardware package is provided with heater Attaching to Wall Stud Method For attaching mounting...

Страница 9: ...design certified equipment shutoff valve from your dealer IMPORTANT Install an equipment shutoff valve in an accessible location The equipment shutoff valve is for turning on or shutting off the gas...

Страница 10: ...lve see Figure 13 2 Open main gas valve located on or near gas meter 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figu...

Страница 11: ...knob while continuing to turn until the knob locks at the desired setting position Do not operate between locked positions TO TURN OFF GASTOAPPLIANCE Shutting Off Heater 1 Turn control knob clockwise...

Страница 12: ...his will allow air to bleed from the gas system If control knob does not pop up when released contact a qualified service person or gas supplier for repairs 6 With control knob pressed in push down an...

Страница 13: ...leaner or pressurized air to clean Exterior Use a soft cloth dampened with a mild soap and water mixture Wipe the cabinet to remove dust Check pilot flame pattern and burner flame pattern often PILOT...

Страница 14: ...sed in 2 Control knob is not pressed in long enough 3 Equipment shutoff valve is not fully open 4 Thermocouple connection is loose at control valve 5 Pilot flame is not touching thermocouple This allo...

Страница 15: ...ked positions 1 Residues from manufacturing processes 1 Metal is expanding while heating or contracting while cooling 1 When heated the vapors from furniture polish wax carpet cleaners etc turn into w...

Страница 16: ...ral gas company 3 Clean ODS pilot see Cleaning page 13 1 Locate and correct all leak s see Checking Gas Connections page 10 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2...

Страница 17: ...n the front of this manual FLOOR MOUNTING STAND For locating heater on the floor away from a wall Complete installation instructions provided with floor mounting stand REPLACEMENT PARTS Note Use only...

Страница 18: ...1 8 ILLUSTRATED PARTS BREAKDOWN HR06MN...

Страница 19: ...9 02 ML079 01 ML119 01 ML057 04 ML060 02 ML083 03 MB28001 ML070 31E DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Burner Assembly ODS Pilot Assembly Thermocouple Ignitor Elect...

Страница 20: ...2 0 ILLUSTRATED PARTS BREAKDOWN HR10MN...

Страница 21: ...9 01 ML119 01 ML057 04 ML060 02 ML083 03 MB28001 ML070 01E DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Burner Assembly ODS pilot Assembly Thermocouple Ignitor Electrode ODS...

Страница 22: ...2 2 ILLUSTRATED PARTS BREAKDOWN HR10TN...

Страница 23: ...ML079 01 ML057 04 ML060 02 ML083 03 MB28001 ML070 29E PARTS AVAILABLE NOT SHOWN DESCRIPTION Cabinet Assembly Lower Front Panel Assembly Reflector Unit Burner Assembly ODS Pilot Assembly Thermocouple...

Страница 24: ...2 4...

Отзывы: