background image

8

 

»

Aluminum tape or mastic

 

»

Miscellaneous hanging materials - field provided

NOTE: 

 Be sure to review ‘Rules for Safe Installation and 

Operation’ on page 1 of this document before 

 

start-up of this unit.

Forced Air Handler/Furnace System with an HRV/ERV

Forced air handler/furnace system with an HRV/ERV This 

application provides filtration of all Outdoor Air (OA) that is 

brought into the home through the HRV/ERV, thus reducing 

the introduction of dust, pollen and mold from the outdoor 

air. For systems that have HRV/ERV units installed, we 

recommend ducting the ‘fresh air’ outlet from the HRV/ERV 

into the HEPA system. If the HRV/ERV CFM (cubic feet 

per minute) rating is lower than that of the HEPA system, 

an additional return needs to be installed into the HEPA 

system. 
The output air from the HEPA system then needs to be 

installed into the main return of the air handler/furnace 

system.

Example of Return to Return Installation with HRV/

ERV

For homes with a forced air handler/furnace system and an 

HRV/ERV system.

Additional Return
Air Handler / Furnace

Air Handler / Furnace Filter

HEPA System

HRV /

ERV

Figure 14. Typical Return to Return Application 

(HRV/ERV)

NOTE: 

This filtration system is an ADDITIONAL filter, and 

does NOT replace the existing air handler/furnace 

system filter.

Preparation

Here are some things to consider as you decide where to 

install the HEPA system with an HRV/ERV.

1. 

Location:

 

»

Make sure there is room to open the HEPA filter ac

-

cess panel for filter changes/inspections.

 

»

Keep the HEPA system in a location where you can 

still access the air handler/furnace filter.

 

»

Keep the HEPA system away from possible water 

damage

 

»

Vibration pads will reduce vibration for installations 

where the unit is placed on the floor.

 

»

Install HEPA System on floor or suspended platform.  

If the unit is suspended, screws must not penetrate 

through the cabinet.  Make sure that you have the 

proper chains/straps/joists and equipment to keep 

unit secure.

2. 

Inlet (Marked as ‘Air In’ on unit):

 

»

Most HRV/ERV systems will not move as much air 

as the HEPA system. For these systems, install an 

additional return from another treated air source into 

the HEPA system.

 

»

If using an additional return duct, it should be in-

stalled upstream of any humidifiers.  The fresh air 

outlet of the HRV/ERV should be “Y” connected to 

the additional return duct then connected to the inlet 

of the HEPA system.

 

»

The additional return duct (if any) should be installed 

at least 8 ft. away from the outlet duct on the main 

return.

 

»

Duct both the HRV/ERV and the additional return 

into the inlet of the HEPA system.

3. 

Outlet (Marked as ‘Clean Air Out’ on unit):

 

»

Outlet duct should be installed as close to the air 

handler/furnace inlet as possible but not directly into 

the return air elbow of the main return.

 

»

To reduce static pressure, install outlet with a 45 de-

gree takeoff directly up-line from the return air elbow 

of air handler/furnace.

4. 

Ducting

 

»

If HEPA system is installed where inlet and outlet 

collars face down, metal elbows must be connected 

to both inlet and outlet collars.

 

»

Each connection must be sealed with aluminum 

tape or mastic, including all take offs.

 

»

Installed duct runs should be as straight as possi-

ble (if the duct runs are too long, reduced CFM may 

result).

 

»

If duct is exposed to unconditioned air, externally in-

sulated flex duct is highly recommended.

 

»

Externally insulated flex duct can also be used for 

noise reduction purposes

 

»

For best indoor air quality, do not use duct-board or 

fiberglass inside of ducts.

5. 

Electricity

The unit must be plugged into a grounded 120V, 60Hz out-

let.

Required Materials for Installation of Unit:

1. 

For Model: HEPA-20

 

»

8” diameter flex or rigid duct (as required)

 

»

6” diameter flex or rigid duct (as required)

 

»

6” diameter 45 degree takeoff

 

»

Aluminum tape or mastic

 

»

Miscellaneous hanging materials - field provided

2. 

For Models: HEPA-40 and HEPA-60

 

»

10” diameter flex or rigid duct (as required)

 

»

8” diameter flex or rigid duct (as required)

Содержание HEPA Bypass Air Filtration Systems HEPA-20

Страница 1: ...nel d Ensure HEPA cartridge is installed and locked into place brace the unit press HEPA cartridge down and turn it clockwise to lock it into place e Replace the HEPA filter access panel and latch it...

Страница 2: ...s HEPA HEPA filter media is 99 97 efficient at capturing particles which are 0 3 micron in size or larger Inner Charcoal Filter Carbon Canister Carbon media is used to capture chemicals and odors also...

Страница 3: ...l Retaining Clips 4 Inlet Collar Cabinet Outlet Collar On Off Switch Motor Section Access Panel Figure 1 Cabinet Parts HEPA Filter STAGE 2 Carbon Pre Filter STAGE 1 HEPA Filter Mesh Protects HEPA Filt...

Страница 4: ...n during filter replacement Filter Change Schedule NOTE Failure to properly maintain your HEPA system will decrease the efficiency and air flow For enhanced odor control the Coconut Shell Carbon Can i...

Страница 5: ...er making sure that the ends overlap d Hook one end of the clip onto the overlapping section of carbon pre filter as shown in figure 13 e Press down on the hooked section while you pull it across stre...

Страница 6: ...let and turn it on Dealer Motor Assembly Replacement Instructions 1 Accessing the motor assembly a Turn the unit off and unplug it from any electrical source before opening the cabinet b To remove the...

Страница 7: ...nd equipment to keep unit secure 2 Inlet Marked as Air In on unit Inlet ducts should be installed upstream of any hu midifiers and be installed on the main return Inlet duct should be installed at lea...

Страница 8: ...that you have the proper chains straps joists and equipment to keep unit secure 2 Inlet Marked as Air In on unit Most HRV ERV systems will not move as much air as the HEPA system For these systems ins...

Страница 9: ...d be installed at least 8 ft away from the outlet duct on the main return Inlet duct should be installed at opposite end of the room from the outlet duct s if in the same room Diffusers are recommende...

Страница 10: ...2X17 92X10 92X10 Carbon Pre Filter X4137 X4138 X4138 Inner Charcoal Filter X2678 92X09 92X09 Carbon Canister 94X98 98X75 98X75 Optional Blower Interlock 24V relay X2680 X2680 X2680 Usethisunitonlyinth...

Отзывы: