How Does the Control Work?
EXTERNAL CONTROL
• When the measured humidity is greater than the setting, the control will turn
on the dehumidifier and
ON
will blink on the LCD display.
• When the measured humidity falls 3% below the setting, the control will turn
off the dehumidifier and
ON
will stop blinking.
REMOTE CONTROL
• The control sends the dryness level to the dehumidifier.
• Once per Cycle Period (set by your installer in the dehumidifier), the
dehumidifier will sample the air in the area served by the dehumidifier.
• If the dew point of the incoming air is above the dryness level, the dehumidifier
will turn on and
ON
will blink on the LCD display.
• When the dew point of the incoming air falls below the setting, the dehumidifier
will turn off and
ON
will stop blinking.
Control Limits
The control limits are used to make sure the dehumidifier does not run when
conditions are outside of the operating limits. Dehumidifiers are not as effective
when conditions are outside of the operating limits. For example, the dehumidifier
will not remove much moisture when conditions are cool and dry. Control limits
allow the dehumidifier to work efficiently within the operating range and turn off
when conditions are outside of these limits.
•
Dew Point Lower Limit:
40°F External Control
•
Temperature High Limit:
99°F External Control
104°F Remote Control
•
Temperature Low Limit:
50°F Remote Control
EXTERNAL CONTROL – SEQUENCE OF OPERATION
• The dehumidifier will turn off if one of the control limits has been exceeded.
• If the control measures a dew point below 40°F OR a temperature above 99°F,
the control will deactivate the dehumidifier output if actively dehumidifying,
the dehumidifier will stop dehumidifying, and
ON
and
*
will blink on the
LCD screen (see
Figure 2
).
• The control will resume normal operation when conditions fall back within
the control limits.
REMOTE CONTROL – SEQUENCE OF OPERATION
• The dehumidifier will turn off if one of the control limits has been exceeded.
• If the dehumidifier measures a temperature below 50°F or above 105°F, the
dehumidifier will stop dehumidifying.
• The control will resume normal operation when conditions in the remote
space fall back within the dehumidifier control limits.
Cleaning the Control
The surface of the Y6456 Dehumidifier Control can be cleaned with water or
a non-abrasive household cleaner, including glass cleaner.
Do not spray any
liquid directly onto the control.
Spray water or a cleaner onto a soft cloth and
gently wipe the surface of the control.
7
6
Содержание Y6456
Страница 5: ...10010836 11 15 B2206365A...