HCWB2 REQUIRED MAINTENANCE

Component identification for the following procedure is
listed in figure 3.

Electric shock hazard. Can cause injury
or death. Disconnect all electrical power
supplies before servicing.  Shut off wa-
ter supply before disconnecting or tap-
ping into any water supply line.

WARNING

!

1 − Disconnect main power to furnace.

2 − Make a note of the humidistat setting and turn

humidistat to the 

OFF 

position.

3 − Turn off water supply.

4 − Slide the plastic latch to release the humidifier cover.

Swing the cover open, then lift it away from the
assembly.

5 − Turn the damper handle to the SUMMER" position.

Grasp the tabs on the pad assembly frame and lift the
assembly out of the humidifier cabinet.

6 − Unsnap the pad assembly from the tabs on the sides

of the distribution tray. Remove the distribution tray
from the pad assembly. Lightly scrape off any mineral
deposits from the surface of the distribution tray.

7 − Slide the humidifier pad out of the frame. Twist and

flex the frame to loosen the calcium deposits on the
frame or use a putty knife to clean the frame. Replace
the humidifier pad annually or more frequently if
necessary. Slide the pad back into the frame with the
black mark facing up. Snap the distribution tray back
into place.

8 − Position the pad frame assembly so that the tabs are

pointing outward. Align the drain extension on the
pad assembly with the drain spud in the humidifier
base. Reinsert the humidifier pad assembly in the
base. Push the pad assembly in at the top until the
assembly snaps into place. Replace the front cover.
Turn the damper handle to the WINTER" position.

9 − Remove the drain hose from the bottom of the

humidifier. Bend and flex the hose to loosen any
internal calcium deposits. Flush the hose with water
under pressure and slip it back onto the drain spud.
The drain hose should have a constant downward
slope and must not be flattened or blocked.

10− Turn on water supply.

11− Check humidifier operation:

Manual Humidistat −

 Adjust humidistat to highest

setting and make sure the furnace blower is
operating. Humidifier will operate if RH is less than
50%.

Universal Humidistat −

 Check system operation by

setting the knob to 

TEST 

position. With furnace

blower operating and furnace calling for heat,
humidifier will operate for one minute. Press the

RESET 

button on the side of the control to reset the

Change Humidifier Pad" indicator.

12− Set manual humidistat or universal humidistat to its

original position.

FIGURE 4

HCWB2 Humidifier Parts Identification

HUMIDIFIER

BASE

HUMIDIFIER PAD

ASSEMBLY

(with frame tabs

pointing outward)

SOLENOID

VALVE

DRAIN HOSE

DISTRIBUTION

TRAY

DAMPER

WINTER/SUMMER

ADJUSTMENT LEVER

(Close damper during

summer operation)

LATCH

TABS

Содержание HCWB2 Series

Страница 1: ...use injury or death Disconnect all electrical power supplies before servicing Shut off water supply before disconnecting or tapping into any water supply line WARNING Risk of Equipment Damage After humidifier installation is completed turn water supply back on CAUTION Humidifier Operation This humidifier provides the proper relative humidity RH during the heating season The humidifier is wired to ...

Страница 2: ... KNOB MANUAL HUMIDISTAT TABLE 1 Relative Humidity RH Settings Outside Temperature Fahrenheit Recommended RH 40 45 30 40 20 35 10 30 0 25 10 20 20 15 To check the humidifier operation set the humidistat above the click point make sure that the water saddle valve is open and that there is power to the unit The furnace blower motor must be operating for the humidifier to function After the humidifier...

Страница 3: ...Turn the control dial setting to the OFF position Then slowly turn the dial clockwise until you hear the solenoid valve click on Slowly turn the dial counterclockwise until you hear the solenoid valve click off At this point make note of the dial setting 4 Locate your dial setting on table 3 Follow the dial setting to the right until it intersects with the current outdoor temperature This is the R...

Страница 4: ...ING Annual Maintenance For best performance you should replace the humidifier pad at least annually Call your dealer for preventative maintenance and replacement components Annual Shutdown For the summer humidifier shutdown turn the universal humidistat or manual humidistat to the OFF setting HCWB2 12 17 and 17A and HCWP2 18 and 18A and close the damper HCWB2 12 12A 17 and 17A Maintenance NOTE Ann...

Страница 5: ... 8 Position the pad frame assembly so that the tabs are pointing outward Align the drain extension on the pad assembly with the drain spud in the humidifier base Reinsert the humidifier pad assembly in the base Push the pad assembly in at the top until the assembly snaps into place Replace the front cover Turn the damper handle to the WINTER position 9 Remove the drain hose from the bottom of the ...

Страница 6: ...Snap the distribution tray back into place 9 Position the pad frame assembly so that the tabs are pointing outward Align the drain extension on the pad assembly with the drain spud in the humidifier base Reinsert the humidifier pad assembly in the base Push the pad assembly in at the top until the assembly snaps into place 10 Remove the drain hose from the bottom of the humidifier Bend and flex th...

Отзывы: