Sprinkler Operation

The Sprinkler operating device is state of the art heat 

responsive frangible glass bulb supplied by a world 

leader in this innovative technology. The glass bulb 

contains fluid  which expands when exposed to heat.
When rated temperature of cover plate is reached, the 

solder melts and cover plate detaches & falls down. 

Further, when rated temperature is reached, the 

bulb shatters and water flows through the sprinkler 

and strikes deflector, forming an uniform water spray 

pattern to control or extinguish fire.

Care and Handling

Sprinklers must be handled with due care, they must 

be stored at ambient temprature for best results. 

Storage as well as any onward shipment is to be made 

in original packing only. Sprinklers must be visually 

inspected carefully before installation. Sprinklers 

visibly damaged, dropped or exposed to temperature 

in excess of the maximum ambient temperature 

 

 

permitted should never be installed. Never install any 

glass bulbs sprinkler if the bulb is cracked or if there 

is a loss of liquid from the Bulb.
Sprinkles must be installed after the piping is in place, 

to prevent mechanical damage.
Do not attempt to make-up for insufficient adjustment 

in the cover plate by over tightening the sprinkler. 

Installation 

 

1.  The unit must be installed in the Pendent position 

for the Concealed Sprinkler.

2. Use only a non-hardening pipe joint compound or 

tape seal. Apply only to the make threads.

3.  Hand tighten the sprinkler into fitting.
4. For Concealed Sprinklers, use a HD sprinkler 

wrench. Tighten the unit into the fitting. A lead-

tight joint requires only 7 to 14 ft.-lbs (9.5 to 

19.0Nm) of torque. A tangential force of 14 to 

28 ft.-lbs (62.3 to 124.5N) delivered through a 

6”(150mm) handle will deliver adequate torque. If 

the torque level reaches over 21 ft.-lbs (28.6 Nm) 

it may distort the orifice seal, resulting in leakage. 

For exposed piping systems, the sprinkler should 

be oriented so the frame arms are parallel with the 

branch line pipe.

5.  The HD sprinkler described herein must be installed 

and maintained in accordance with the latest 

edition of HD technical data, the latest standards 

of the National Fire Protection Association (NFPA) 

and Factory Mutual (FM) or to the standard of any 

other authorities having jurisdiction. The owner 

is solely responsible for maintaining their fire 

protection system and devices in proper operating 

condition. 

Inspection Testing and Maintenance

Refer to NFPA 25 for inspection testing and 

maintenance requirement or to the authority having 

jurisdiction. For detail of warranty refer HD’S current 

price list, conditions of sale or contact HD sales 

directly.
Sprinklers must never be altered after manufacture. 

Any alteration such as painting and coating will directly 

harm the sprinkler and cause malfunctions. Sprinkler 

in contact with corrosive products should be replaced 

if they cannot be cleaned completely.  
Visual inspections are recommended after installation. 

After installation, a close-up inspection annually will 

suffice. 
Inspection and maintenance of fire protection system 

is the resposibility of the owner. It is recommended 

that automatic sprinkler system be inspected and 

tested according to local and/or national regulations. 
Exposure to ultraviolet or direct sunlight for extended 

period may cause the liquid dye in glass bulb to fade 

or lose colour.  Colourless or faded coloured bulbs are 

not a problem, as long as the fluid level has not been 

affected. The loss of colour in the liquid will not effect 

sprinkler performance, as long as the bulb is intact 

and not damaged. The loss of colour may be an issue 

in identifying sprinkler temperature rating, but the 

temperature rating is still stamped on the sprinkler 

deflector. 

Caution 

1. The Sprinkler must be installed and maintained in 

compliance with this document.

2. In false ceiling, a cut out must be to minimum 

55mm & maximum 68mm, and must be concentric 

to sprinkler. A template gauge must be used to 

check the cut out to avoid damage or improper 

fitment of cover.

3.  Sprinkler adjustment with reference to false ceiling 

is 6.6 mm. For more details, refer figure in Page-3.

4. Improper fitment may result into fall of cover 

plates.

5. Cover plates must be installed only after hydro-

testing and false ceiling painting.

6.  Always use HD Wrench for installation. Any other 

wrench may damage the sprinkler.

Wrench for Concealed Sprinkler

Содержание HD 104

Страница 1: ...Response 5mm glass bulb or Quick response 3mm glass bulb with standard coverage LISTED Style Concealed Sprinkler Temperature Standard Response with 5mm Response glass bulb Quick Response with 3mm glass bulb Coverage Standard Coverage K Factor 5 6 US 80 metric Nominal BSPT NPT Optional Thread Size Max Working 175 PSI 12 Bar Pressure Factory 500 PSI 35 Bar Hydrostatic Test Pressure Min Operating 7 P...

Страница 2: ...dance with the latest edition of HD technical data the latest standards of the National Fire Protection Association NFPA and Factory Mutual FM or to the standard of any other authorities having jurisdiction The owner is solely responsible for maintaining their fire protection system and devices in proper operating condition Inspection Testing and Maintenance Refer to NFPA 25 for inspection testing...

Страница 3: ...G BULB DEFLECTOR GUIDE SCP DEFLECTOR COVER LOAD SCREW 1 2 BSPT NPT FRAME DEFLECTOR CAP CAP SEAT LOAD SCREW SEAL BULB DEFLECTOR GUIDE 1 2 3 4 5 6 7 8 ASTM C48600 ASTM C51000 JIS C5191 ASTM C11000 ASTM S30400 ASTM C26000 JIS C2600 BERY NICKEL SPRING TEFLON TAPE NORBULB N5 ASTM S30400 SPRING COVER 9 10 ASTM S30400 ASTM C26800 1 3 6 9 4 8 7 2 10 5 ...

Страница 4: ...shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product HD FIRE shall not be liable for any damages or charges sustained in the adaptation or use of its engineering data services In no event shall HD Fire s product liability exceed an amount equal to the sale price The foregoing warranty is exclusive and in lieu of all other warranties and rep...

Отзывы: