13
P3IC / P3ICP
A2382-3.0 en/de/fr
HBM
5
Electrical connection
The pressure transducers can be connected both to carrier frequency and DC
amplifiers.
In the standard version, the pressure transducers come complete with a 3 m
long connection cable with free ends.
They are also available with an MS plug, a D15 plug or with a welded HS6P
plug, as options.
Pin assignments P3IC / P3ICP
The allocation of the pin assignment is shown in Table 5.1. The cable shield is
connected to the transducer housing (see HBM ”Greenline shielding design”;
Internet download at http://www.hbm.com/Greenline).
Pin assignment
P3IC cable version
P3ICP plug version
Bridge excitation voltage (+)
green
Pin 3
Bridge excitation voltage (-)
brown
Pin 2
Measurement signal (+)
white
Pin 1
Measurement signal (-)
yellow
Pin 4
Sense lead (+)
rose
Pin 6
Sense lead (-)
blue
Pin 7
Pt100
red
Pin 8
Pt100
gray
Pin 5
Tab. 5.1:
Pin assignment of the P3IC / P3ICP pressure transducer in cable and
plug version
1
4
6
Sense lead (-)
Pt100
Measurement signal (+)
Bridge excitation voltage (-)
Bridge excitation voltage (+)
Measurement signal (-)
Sense lead (+)
Pt100
2
7
8
5
white
yellow
green
rose
brown
blue
red
gray
3
Pressure transducer,
8‐pin panel connector