Electrical connections, LEDs
ClipX
a4643-1.0 HBM: public
23
6.2
Shielding and grounding design
The supply voltage connection, as well as the signal and sense leads, must be
installed in such a way that electromagnetic interference does not adversely
affect module functionality (HBM recommendation: “Greenline shielding design”
– see
). Always connect the cable shield by the
shortest possible length to the plug terminals and, as far as possible, lay the
shield flat at the control cabinet inlet with shield connection terminal blocks, e.g.
type SKS 8-SNS35 – 3062786 from Phoenix Contact – see illustration.
Fig. 7:
Shield connection terminal block for flat contacting of cable shields (ex-
ample)
Double-shielded connecting cables, e.g. for sensors
We recommend using HBM cable Kab 7.5/00-2/2/2 wherever possible. The
cable is double-shielded and low in capacitance. When using double-shielded
cables, connect the outer shield only to the connection for the housing (ground
symbol
, labeled “Outer cable shield” in the connection diagrams), not to one
of the GND connections (
). In the case of control cabinets, also lay this shield
contacting on the cabinet – see illustration of shield clamp. Connect the inner
shields of the sensor cables to the connection labeled “Inner cable shield” (
).
Use the shortest lines possible for the connections.
Applications in areas with potentially explosive atmospheres are exceptions.
There connect
all
cable shields to the potential equalization connection.
Single-shielded cables
Connect the shields of single-shielded cables to the connection for the housing
(ground symbol
, labeled “Outer cable shield” or “Cable shield” in the connec-
tion diagrams), not to one of the GND connections (
). In the case of control
cabinets, also lay this shield contacting on the cabinet – see illustration of shield
clamp.
S
S
S
Содержание ClipX
Страница 1: ...Operating Manual Bedienungsanleitung English Deutsch ClipX...
Страница 3: ...Operating Manual Bedienungsanleitung English Deutsch ClipX...
Страница 6: ...4 a4643 1 0 HBM public ClipX...
Страница 10: ...Safety instructions 8 a4643 1 0 HBM public ClipX...
Страница 12: ...Symbols on the instrument 10 a4643 1 0 HBM public ClipX...
Страница 106: ...Calibration certificates 104 a4643 1 0 HBM public ClipX...
Страница 116: ...Maintenance 114 a4643 1 0 HBM public ClipX...
Страница 118: ...Disposal 116 a4643 1 0 HBM public ClipX...
Страница 123: ...Operating Manual Bedienungsanleitung English Deutsch ClipX...
Страница 126: ...Inhaltsverzeichnis 4 a4643 1 0 HBM public ClipX...
Страница 130: ...Sicherheitshinweise 8 a4643 1 0 HBM public ClipX...
Страница 132: ...Symbole auf dem Ger t 10 a4643 1 0 HBM public ClipX...
Страница 192: ...ClipX in Betrieb nehmen 70 a4643 1 0 HBM public ClipX...
Страница 230: ...Kalibrierzertifikate 108 a4643 1 0 HBM public ClipX...
Страница 240: ...Wartung 118 a4643 1 0 HBM public ClipX...
Страница 242: ...Entsorgung 120 a4643 1 0 HBM public ClipX...
Страница 247: ......