CONNECTING INTERFACES AND I/OS
28
7.1.2
Connection to a CANopen/DeviceNet bus system
Up to 126 AEDs can be connected to the same bus line via the CANopen interface, and up
to 62 AEDs via DeviceNet. In both cases, the factory-set bus address is 63 and the bit
rate 125kBit/s.
CAN bus cable length and bit rate
Bit rate in kBit/s
10
20
50
125
250
500
800
1000
Max. cable length
in m
5000
2500
1000
500
250
100
50
25
DeviceNet cable length and bit rate
Bit rate in kBit/s
125
250
500
Max. cable length
in m
500
250
100
The max. cable length is the total line length, calculated from the length of all the stub
lines per node (bus nodes) and the line length between the nodes. The length of the stub
lines for each node (Fig. 7.4) is limited and depends on the bit rate used (see additional
CAN bus documentation: CiA DS102 V2.0 and DeviceNet: DeviceNet Specification Vol
ume 1, Appendix B, Cable profiles).
The recommended bus wiring is shown in Fig. 7.3.
CAN H
CAN L
Master
Node 1
Node X
...
120Ω
120Ω
IN
OUT
IN
OUT
IN
OUT
Bus termination
Bus termination
Fig. 7.3
Recommended connection variant
The interface driver of the AED is based on the 0V connection of the supply voltage. The
interface driver of the master must also be based on this potential. Use a shielded cable
as the bus cable. Another option for connecting stub lines is shown in Fig. 7.4.
Содержание AED 9101D
Страница 1: ...AED ENGLISH DEUTSCH Operating Manual Bedienungsanleitung ...
Страница 3: ...AED Transducer Electronics 9101D 9201B 9301B 9401A and 9501A ENGLISH DEUTSCH Operating Manual ...
Страница 53: ...AED Aufnehmer Elektroniken 9101D 9201B 9301B 9401A und 9501A ENGLISH DEUTSCH Bedienungsanleitung ...
Страница 103: ......
Страница 104: ...HBK Hottinger Brüel Kjaer www hbkworld com info hbkworld com A05803 01 X00 00 ...