Assembly Instructions M8098-EN
M8098-EN 2018-03
5/6
12.
Reconnect mains plug and switch on main switch.
13.
Press the
key to switch on the unit and check it for leaks.
14.
Proceed as follows in order to calibrate the temperature
sensor:
When setting partameters set
DFM recognition
to the
"integrated“ value (in
Settings / Various)
, continue with Step
When setting parameters set
DFM recognition
to the "modular“
value (in
Settings / Various)
Fig. 10: Sensor calibration during
integrated operation
Integrated operation
15.
Temperature sensor main line ext 1..8 and temperature
sensor return line ext. Proceed as follows in order to calibrate
1..8 , if necessary, the temperature sensor:
With a constant deviation set parameter
Sensor… offset
under
Service / Calibration / Temperature
.
With a linear deviation, set parameter
Sensor… asc.cor.
under
Service / Calibration / Temperature
.
Fig. 11: Sensor calibration during modular
operation
Operation Modular
16.
Proceed as follows, if necessary calibrate the temperature
sensor for the main line and temperature sensor of the return
line:
Select the module affected e.g. "A1“ with the
or
buttons.
With a constant deviation set parameter
Sensor… offset
under
Service / Calibration / Temperature
.
With a linear deviation, set parameter
Sensor… asc.cor.
under
Service / Calibration / Temperature
.
17.
Switch the unit off by press the
key.
18.
Main switch off.