HB Products HBDF MK2 Скачать руководство пользователя страница 11

 

instruction manual - HBDF –mk2 – defrost sensor (013-UK) 19/03-2019 WWW.HBPRODUCTS.DK 

11 / 17

 

 

WE INCREASE 

UPTIME

 AND 

EFFICIENCY

 

IN THE REFRIGERATION INDUSTRY 

Installation, 

Continued

 

 

Place the wire between the fins on the inlet side (or where ice build-up occurs).  

The distance between the vertical sections of the wire (windings) can be varied from 100 to 500mm depending on 
evaporator size and wire length. When estimating length to be ordered, consider both the vertical sections of the wire 
and the connecting, horizontal arches.  
Note: when calibrating the HBDF, only consider the active, vertical sections of the wire.( Sensor length in mm.) 
 
Fasten wire with cable binders or HB Snap On Clips.  
 

  

 

 

 

 

 

 

 

Sensor PT1000 location 
(Example) 

The active part is the 
vertical sections of the wire 
placed between fins.  

Not active  

 

PT1000  

Содержание HBDF MK2

Страница 1: ...NDUSTRY Instruction Manual HBDF MK2 Defrost Sensor Demand defrost for automatic defrosting of evaporators Simple Setup only two parameters and execution of a zero start point during start up Can opera...

Страница 2: ...nd defrost for automatic defrosting of evaporators 1 Table of Contents 2 Safety Instructions 4 Introduction 5 Measuring Principle 6 Design 6 Software 6 Technical Data 7 Function 8 Installation 10 HBDF...

Страница 3: ...7 01 03 2019 MME MME When running only mA output it stops at 18mA and goes to 19mA when heater set point is reached see page 8 Choice of FREEZER or ICE BANK mode see page 3 1 4 2 07 03 2019 LSN Altera...

Страница 4: ...E Contains important additional information about the product and provides further tips The person responsible for operation must commit to adhering to all the legislative requirements preventing acci...

Страница 5: ...rs and execution of a zero start point and a Calibration with frozen dry evaporator surface surface with thin layer of frozen ice as after defrost is the optimal start point The length of the wire ent...

Страница 6: ...When liquid covers the sensor the measured capacity is changed The conductivity of a material can vary depending on temperature chemical composition and the homogeneity of the material and therefore...

Страница 7: ...tricity consumption 600 mA Electrical connection Screw terminals Analogue output 4 20 mA Max load 500 ohm Relay output 2 x 5A NO NC Relay output 24V 2 x 3A NO NC Installation conditions Ambient temper...

Страница 8: ...with mA and digital start and stop function Advanced Calibration The calibration should be carried out before ice begins to build up When the evaporator is free of ice the sensor emits 4mA Depending...

Страница 9: ...mk2 1 4 0 12 09 2017 MME When running only mA output it stops at 18mA and goes to 19mA when heater set point is reached The PLC must have a timer delay to ensure frost condition remaining water drople...

Страница 10: ...n to measure when all the ice has melted 5 Normally installed with a standard unshielded cable If the EMC is higher than described in EN 61326 a shielded cable must be used Note To have a proper groun...

Страница 11: ...the wire windings can be varied from 100 to 500mm depending on evaporator size and wire length When estimating length to be ordered consider both the vertical sections of the wire and the connecting...

Страница 12: ...st start level E g 50 stops the mA output at 12mA Defrost stop temp Defrost stop temperature when the digital stop relay is activated and the sensor delay starts running mA only function is 19mA Senso...

Страница 13: ...s built in relays for start stop defrost and external temperature sensor for measuring when the ice is melted Should normally be used with a master defrost controller or a PLC simple defrost with elec...

Страница 14: ...WWW HBPRODUCTS DK 14 17 WE INCREASE UPTIME AND EFFICIENCY IN THE REFRIGERATION INDUSTRY Application examples Safety Defrosting with hot gas must be performed in a safe way in order to ensure that ther...

Страница 15: ...st with electric heater LED Indication and Calibration The HBDF MK2 sensor is primarily designed to measure ice thickness where the analoge 4 20mA output indicates the ice thickness the built in relay...

Страница 16: ...fan sensor delay timer end Fault Detection Fault Reason Correction of fault No LED is on no function No supply to the sensor or defective cable Check for fault in the power supply or replace the supp...

Страница 17: ...ronical part Complaints are processed by HB Products dealers distributors Please consider their complaint procedures before returning the sensor Spare Parts Position Designation Specification Product...