ONLY USE GENUINE HAYWARD REPLACEMENT PARTS
51300803801 REV B
EQUIPMENT PAD
:
Place the heater on a level surface such as concrete or a fabricated slab (pad). This allows proper drainage of conden-
sation and rainwater from the base of the unit. If possible, the pad should be placed at the same level or slightly higher than the filter system
equipment pad.
FLOORING:
This heater may be installed on either non-combustible flooring or combustible flooring that does not reduce the bottom clear-
ance of the heater. Do not install on carpet. Ultralite™ or equivalent concrete-over-foam HVAC pads are acceptable.
Figure 4: Outdoor Minimum Clearances
ANCHORING:
The heater is equipped to be anchored to a concrete equipment pad when required by local codes. Follow all relevant Local,
State and National requirements regarding wind load anchoring. Anchor your heater to the pad through the same anchor point used to secure
the heater to the pallet when it was delivered. You will need the following to complete the installation:
Concrete tapping screws: (FIELD-SUPPLIED, Tapcons®, qty = 4, stainless steel, size to be ¼”diameter with a minimum length of 1-1/2”)
Fender washers: (FIELD SUPPLIED, stainless steel, qty = 4, size to be an OD of 0.75”)
1. Obtain Tapcons®. Be sure the overall length of the concrete tapping screw is at least 1-1/2”.
2. Position the heater on the pad so that all Tapcons® can “bite” into the pad. Observe local codes regarding pad construction, some juris-
dictions specify a minimum thickness for concrete pads.
3. Install the Tapcons® through the provided holes in the flanges of the heater feet with the washers on the top of the mounting flanges into
the equipment pad.
4. Anchoring is completed when all (4) feet are secured to the pad with washers and Tapcons®.